ASHRAE STANDARD 62.1 VENTILATION ANALYSIS UNIVERSITY RIDGE AT EAST STROUDSBURG UNIVERSITY EAST STROUDSBURG, PA PREPARED FOR: JAE-WEON JEONG, PH.D.

Similar documents
The relationships between the extent of mould problems and physical building characteristics in high-rise apartment buildings

Building Science Fundamentals Ventilation May 25-26, Joseph Lstiburek, Ph.D, P.Eng, ASHRAE Fellow. Adventures In Building Science

On Smoke Control by Pressurization in Stairwells and Elevator Shafts

On Smoke Control by Pressurization in Stairwells and Elevator Shafts

A STUDY ON AN ESTIMATION METHOD OF THE EFFECTIVE OPENING AREA OF ENTRANCE DOORS AND WINTER AIRFLOW RATE INTO ATRIUM BUILDINGS

Analyzing Ventilation Effects of Different Apartment Styles by CFD

Balanced ventilation in apartment buildings

Measuring Air Change Rates using the PFT Technique in Residential Buildings in Northern Portugal

Protecting the Stair Enclosure in Tall Buildings Impacted by Stack Effect

Passive Cooling Measures for Multi-Unit Residential Buildings

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!

Vestibule Requirement Intent

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Energy variations in apartment buildings due to different shape factors and relative size of common areas

CHAPTER 4 LIGHT, VENTILATION & OCCUPANCY LIMITATIONS

Elements for an acoustic classification of dwellings and apartment buildings in France C. Guigou-Carter, R. Wetta, R. Foret, J.-B.

1. Project No.: 812 Muslim Commercial Bank, Karachi Mechanical & Electrical System

MEMORANDUM September 7, 2018

NFPA (2012). In a high-rise building, stairwell pressurization systems typically utilize multiple fans distributed over the height of the stair, a duc

Fee Type How Determined Rate Permit Processing Charge Flat Permit or Plan Review Submittal $32.00

MONITORED RESULTS FROM AN INNOVATIVE SOLAR RENOVATION OF MULTI STOREY HOUSING - EU SHINE ENGELSBY, FLENSBURG

REQUEST FOR Rezone to Open Space Designation (Public Hearing) PLANNING COMMISSION MEETING DATE January 11, 2017

Attic Floor Bedrooms 1 & 2 Family Dwellings

Impacts of Maximum Allowable Building Footprint on Natural Ventilation in Apartment Building

Founded 2000 Midwest LEED for Homes Provider 501(c)3 non profit; mission:

MULTIFAMILY PERFORMANCE PROGRAM Technical Topic New Buildings Savings Opportunity - Stairwell Lighting

GOTTINGEN STREET H A L I FA X, NS

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 7 Heiselberg, Per Kvols. Publication date: 2016

The Impact of Balconies on Wind Induced Ventilation of Singlesided Naturally Ventilated Multi-storey Apartment

The effect of the wind speed velocity on the stack pressure in medium-rise buildings in cold region of China

General Information RETAIL AND RESTAURANT

HOUSING CODE CHECKLIST FOR RENTAL INSPECTIONS

ELECTRICAL LOAD CHARACTERISTICS OF SUPERINSULATED MULTIFAMILY HOUSING: A CASE STUDY

Guide Note 6 Consideration of Hazardous Substances in the Appraisal Process

Large Building Air Leakage Testing

MARKHAM. City of. Comprehensive Zoning By-law Project. Task 4b. Review and Assessment of Minor Variances

Real Estate Assessment Checklist. 1. This assessment checklist has most of the essential features to look for in a house,

City Center Market-Rate Housing Study

Stairwell Pressurization in a Cold Climate

LANE COUNTY BUILDING & ELECTRICAL PROGRAMS PERMIT FEE GUIDE

RESIDENTIAL MARKET ANALYSIS

Washington Department of Revenue Property Tax Division. Valid Sales Study Kitsap County 2015 Sales for 2016 Ratio Year.

Analysis of Infill Development Potential Under the Green Line TOD Ordinance

BUILDING PERMIT FEE ESTIMATE

Plan for acquisition of historical consumption data and household typology for each dwelling

Following is an example of an income and expense benchmark worksheet:

Article 19: Southeastern San Diego Planned District ( Southeastern San Diego Planned District added by O N.S.)

COMFORT WITH COURTYARDS IN DHAKA APARTMENTS

PLANNED UNIT DEVELOPMENTS (Ordinance No.: 3036, 12/3/07; Repealed & Replaced by Ordinance No.: 4166, 10/15/12)

City of Hesperia CDBG Funded Energy Efficiency Rehabilitation Program. Program Guidelines

FOR SALE or LEASE 2086 New Danville Pike, Lancaster, PA Pequea Township

Boiler Design Documents Appraisal Procedure

This fee structure applies to applications submitted on or after January 1, 2018.

Phoenix Military Academy High School 145 S Campbell Ave Chicago, IL Co-locating on this campus are MARINE MILITARY HS and PHOENIX MILITARY HS

Residential Air Leakage Testing and Mechanical Ventilation Verification

High-Rise Fire Sample Scenario with Stairwell Pressurization by Steve Kerber Fire Engineering Simulation

Alex Haley Elementary Academy S Eggleston Ave Chicago, IL 60628

Office Space For Lease

CHAPTER 10 ARTICLE II DIVISION 2: MINIMUM STANDARDS

BUILDING AN ADU GUIDE TO ACCESSORY DWELLING UNITS PLANNING DIVISION

Residential Air Leakage Testing and Mechanical Ventilation Verification

Rent Stabilization, Vacancy Decontrol and Reinvestment in Rental Property in Berkeley, California

Where rivers connect

Evacuation Design Focused on Quality of Flow

World Renewable Energy Congress (WRECX) Editor A. Sayigh 2008 WREC. All rights reserved. 822

STAFF REPORT. Permit Number: Porter. Kitsap County Board of Commissioners; Kitsap County Planning Commission

Sustainable Suite Design Competition: Front Street Hotel

RENTAL MARKET REPORT. Manitoba Highlights* Highlights. Housing market intelligence you can count on

On the Relationship between Track Geometry Defects and Development of Internal Rail Defects

Housing Quality Standards 24 CFR

Anemomaster

Refurbishment of. Apartments how do you calculate? Refurbishment costs and life expectancy. Refurbishment Costs. Life expectancy

Existing Land Use. Typical densities for single-family detached residential development in Cumberland County: 1

OBTAINING A CERTIFICATE OF OCCUPANCY FOR UNAPPROVED DWELLING UNITS

CITY OF CORTEZ COUNCIL RESOLUTION NO. 45, SERIES 2016

LAND USE APPLICATION Land Use Compatibility Statement Recreational Marijuana Uses

LAND USE APPLICATION Land Use Compatibility Statement Recreational Marijuana Uses

Camp Washington Zoning Proposed Changes 11/30/2018

Community Affairs and Planning Committee Paul Allore, MCIP, RPP Director of Planning and Development Services

LANE COUNTY BUILDING & ELECTRICAL PROGRAMS PERMIT FEE GUIDE

The New NYC Building Code Chapter 10 Means of Egress. New York City Department of Buildings. Technical Affairs. Fatma M. Amer, P.E.

THE VALUE OF LEED HOMES IN THE TEXAS REAL ESTATE MARKET A STATISTICAL ANALYSIS OF RESALE PREMIUMS FOR GREEN CERTIFICATION

Evaluating Unsmoothing Procedures for Appraisal Data

Charles Kozminski Elementary Community Academy

What issues regarding FHA lending have been raise throughout this chapter and which ones place great responsibility on the appraiser?

Planning and Building Department

CHARLESTON PLACE TENANT CALCULATION CHECK/DATA TABULATION SHEET(S) Forms must be completed by the Tenant's Mechanical or Electrical Engineer.

William Howard Taft High School

FROM: Acting General Manager, Planning and Development FILE: (SWM St. Helen's Park)

Our Focus: Your Future 2007 YEAR END HOUSING MONITORING AND SUBDIVISION STATUS REPORTS

FOR SALE OR LEASE PROPERTY FEATURES:

2014 Plan of Conservation and Development

Study of the energy performance of Korean apartment buildings with alternative balcony configurations

Tiny House on Wheels A Tiny House

Indoor climate and energy consumption in residential buildings in Estonian climatic conditions

Use of Comparables. Claims Prevention Bulletin [CP-17-E] March 1996

CASCO TOWNSHIP ALLEGAN COUNTY, MICHIGAN SHORT TERM RENTAL ORDINANCE ORDINANCE NO.

The Impact of Market Rate Vacancy Increases One Year Report

LLA 2018 CONFERENCE INNOVATIVE LIBRARIES: PATHS TO THE FUTURE

For Internal Use Only (as of August 5, 2013) Some details provided may still be changed.

Transcription:

ASHRAE STANDARD 62.1 VENTILATION ANALYSIS UNIVERSITY RIDGE AT EAST STROUDSBURG UNIVERSITY EAST STROUDSBURG, PA PREPARED FOR: JAE-WEON JEONG, PH.D. BY: MATTHEW CARR MECHANICAL OPTION OCTOBER 5, 2006

Table of Contents Executive Summary 2 Ventilation Rate vs. IAQ Procedure 3 Purpose 4 Assumptions 4 Procedure 5 Analysis 6 Conclusions 7 Appendix A 8 Appendix B 13 References 16 1

Executive Summary This report is intended to analyze the ventilation of the University Ridge student housing complex at East Stroudsburg University using the ASHRAE s Standard 62.1 Ventilation for Acceptable Indoor Air Quality. University Ridge is a 10 building complex of 160,000 ft 2 with four person apartments which are naturally ventilated with operable windows according to the required percentage of free area. Along with apartments, the complex also contains a commons area which includes lounges, a game room, conference room, offices and meeting room. Each of these previously described spaces are conditioned by split system DX duct furnace air handling units which are supplied by hot water from an adjacent water heater and each has an individual condensing unit. Each air handling unit supplies around 2,500 CFM of re-circulated air and a cooling capacity of 2.5 to 3.5 tons. Due to the spaces being naturally ventilated, the amount of overall complaints due to sick buildings has been shown to be statistically lower. 1 However, naturally ventilated systems must be used with caution due to certain conditions that affect performance, such as climatic, wind or atmospheric conditions. After analysis of the occupied spaces, it was found that only one unit,, did not meet Standard 62.1 on mechanical ventilation alone. All spaces which require natural ventilation meet or exceed the standard. The following report is prepared assuming that the windows are inoperable and require the proper amount of ventilation as stated in Section 6 of Standard 62.1 and that ventilation efficiency is 100%. 2

Ventilation Rate vs. IAQ Procedure ASHRAE Standard 62.1 lists two acceptable procedures to properly ventilate an occupied space with the required amount of outdoor air. Both methods serve as a way to effectively remove and reduce airborne contaminants. The Indoor Air Quality Procedure (IAQ) focuses on the amount of contaminants in the air and how much they need to be reduced by, given the concentration, to maintain acceptable indoor air quality. This procedure is based on system design parameters that analyze the contaminant sources, concentration levels, and the perceived acceptable concentration levels. Also, the IAQ procedure allows for the use of filters and such air cleaning procedures to be taken account of and used counted as removing contaminants. This procedure is mainly used where a design must attain specific contaminant levels and strengths in such places as hospitals or laboratories. 1 The Ventilation Rare Procedure (VRP) is a procedure used when minimum outdoor air is to be determined for general spaces. Predetermined outdoor air intake levels are used based on the spaces occupancy category. These predetermined rates are determined from the amount of contaminants and the source strengths for that particular type of space. The prescribed rates are meant to dilute and exhaust the contaminated air at a sufficient rate to maintain an acceptable indoor air quality. This VRP also accounts for the method in which air is delivered to a space using correction factors. When combining spaces into zones, this method determines the amount of outdoor air required in the zones. By comparison, the Ventilation Rate Procedure is a much more generalized, quicker and less in depth way of finding acceptable indoor air quality levels then the IAQ procedure. The IAQ procedure requires an intimate level of knowledge of the spaces, which is usually hard to come by during design, and thus requires more time for analysis. The VRP does not account for air cleaning devices like the IAQ method and therefore a space might provide more fresh air than might actually be needed. The IAQ procedure is best used for spaces which are sensitive to contaminant levels while the Ventilation Procedure is best used for generalized space where little information is known. 3

Purpose The purpose of the standard as stated in ANSI/ASHRAE Standard 62.1 is to specify minimum ventilation rates and indoor air quality that will be acceptable to human occupants and are intended to minimize the potential for adverse health effects. The standard is used as a basis for determining the amount of outdoor air required to supply an occupied space with enough fresh air to keep contaminants, such as pollution and ozone, to a minimum. This standard also takes into account indoor pollutants and re-circulated air when finding a required amount. Two methods can be applied to obtain the said results, either the Ventilation Rate Procedure or the Indoor Air Quality Procedure. For the purposes of this report, the Ventilation Rate Procedure shall be used. Assumptions Occupants Category for minimum ventilation rate in breathing zones (Table 6-1) shall be assumed in conjunction with architectural plans for occupancy conditions in the breathing zone. Occupant Density will be assumed as the same number of beds per apartment unit and the default values for density from Table 6-1 in the standard. Exhaust ventilation will be ignored for the purposes of this report. Spaces excluded were bathrooms, janitorial and electrical closets, and storage areas. Existing ventilation for spaces such as Vestibules and Stairwells were neglected. It is assumed that there is no smoking allowed in any of the spaces. Outdoor air is of sufficient quality to be used as ventilation without filtering. All operable windows are assumed to be closed and spaces are to be mechanically ventilated. All areas are taken from the inside of finished walls. 4

Procedure Step 1: Step 2: Step 3: Step 4: Step 5: Step 6: Step 7: Step 8: Step 9: Step 10: Occupied zones are identified and occupancy category, occupancy density and areas are taken from an electronic set of construction drawings. Determine R a and R p based on the assumptions above and Table 6-1 in Standard 62.1. Determine the Breathing Zone Outdoor Air Flow using the equation V bz = R p P z + R a A z Determine the Zone Air Distribution Effectiveness (E z ) from Table 6-2 Standard 62.1 and the configuration of the supply of cool air. Calculate the Zone Outdoor Air Flow: V oz = V bz /E z Find the Zone Primary Airflow V pz from the Construction Drawings. Calculate the Primary Outdoor Air Fraction: Z p = V oz /V pz Calculate the Uncorrected Outdoor Air Intake: V ou = D Σ all zones R p P z + Σ all zones R a A z A conservative diversity factor D of 1 was used because no data is available on the variance in population; therefore the assumption that P s was equal to P z was used. Determine the System Ventilation Efficiency E v, using the value of Z p as determined earlier, from Table 6-3. Calculate the Outdoor Air Intake: V ot = V ou /E v 5

Analysis The calculations in the Appendix analyze the amount of air required by 62.1 assuming that the windows were not operable and required mechanical ventilation. Also, the spaces that were designed with mechanical ventilation were compared to the found values. Compliance with Standard 62.1 Section 5, which deals with natural ventilation, was also verified using occupiable floor areas and operable window free areas. In Building 1, the First Floor is used as a commons area for the complex. Although this area has operable windows, ventilation is supplied by three separate units to the spaces. It was found after ASHRAE Standard 62.1 analysis that only unit DF-2 did not supply a sufficient amount of ventilation air to the spaces as seen in Appendix A. However, as previously stated, these two spaces are connected by a permanently unobstructed opening of sufficient size to the exterior wall with operable windows and can be argued to have enough outdoor air to meet 62.1. Units DF-3 and DF-4 supply their zones with a more than adequate amount of fresh air thus beating the Standard. The first, second, and third floor meet the requirements for window free area for natural ventilation as stated in Section 5 of 62.1 and can therefore be used for ventilation. If this was not the case, the whole building would need 1,452 CFM of outdoor air to meet the indoor air requirements of Standard 62.1. Analysis of Building 4 resulted in compliance with Section 5 of the Standard requiring 344 ft 2 of window area and having an actual area of 374 ft 2. The required amount of outside air for mechanical ventilation would be 267 CFM per floor. Investigation of Buildings 2-3,5-10 resulted in almost the same results as Building 4. The operable windows met the Standard with 401 ft 2 of required floor area and having 404 ft 2 of window area. The required amount of outside air for mechanical ventilation would be 270 CFM per floor. During analysis, the only systems that had a minor difference in their zone primary outdoor air fraction (Z p ) were DF-2 and DF-4; however, they only caused a minor difference since the max Z p for the systems were 0.228 and 0.196 respectively. These numbers resulted in system 6

ventilation efficiency (E v ) of 0.9. Since, most of the units were considered single zone, nominal outside air (V oz ) and required outside air (V ot ) were mostly equal as seen in Appendix A. The only systems that deviated from this were the two systems with different Z p values. Conclusions After evaluation of compliance of the mechanical system with ASHRAE Standard 62.1, it was found that all spaces comply except for zones on unit DF-2. All spaces utilizing natural ventilation from operable windows also pass Section 5 of Standard 62.1. As a result of this natural ventilation, much energy is saved because of the reduced air that must be heated and cooled to maintain a comfortable temperature and have been shown to have less sick building complaints as a result of the decrease in probability of a moisture problem. Overall, the design seems to be accurate and in order. 7

Appendix A Appendices 8

Building 1 Basement Level Room Name Area (ft 2 ) Occupancy R a (CFM/ft 2 ) R p (CFM/person) V bz (CFM) E z V oz V pz Z p V ou E v V ot DF-2 TV Room 633 13 0.06 5 103 103 700 0.147 103 0.9 114 Game Room 490 10 0.18 7.15 160 160 0.228 160 0.9 178 DF-3 Fitness Room 212 5 0.06 20 113 113 0.141 113 1 113 Corridor 188 0 0.06 0 11 11 0.014 11 1 11 Cyber Lounge 653 13 0.06 5 104 104 800 0.130 104 1 104 Required OA 292 Actual OA 150 Required OA 115 Actual OA 260 DF-4 Conference 175 8 0.06 5 51 51 0.112 51 1 51 Office 105 2 0.06 5 16 16 0.036 16 1 16 Group Meeting 633 10 0.06 5 Room 88 88 450 0.196 88 0.9 98 Reception 170 2 0.06 5 20 20 0.045 20 0.9 22 Office 111 2 0.06 5 17 17 0.037 17 0.9 19 Closet 38 0 0.12 0 5 5 0.010 5 0.9 0.9 File Room 107 0 0.12 0 13 13 0.029 13 0.9 14 Required OA 207 Actual OA 300 (ft 2 ) 3515 Floor Total OA 741 First Floor Unit C - 3 Person 605 3 0.06 5 Apartment 51 51 51 0.073 51 1 51 Unit D - 2 Person 598 2 0.06 5 Apartment 46 46 46 0.066 46 1 46 (2) - 4 Person Apartment 757 4 0.06 5 65 65 65 0.093 65 1 65 131 Corridor/Stairwell 327 0 0.06 0 20 20 20 0.028 20 1 20 (ft 2 ) 2717 Floor Total OA 150 Second Floor Apartment 757 4 0.06 5 65 65 65 0.093 65 1 65 262 Corridor/Stairwell 306 0 0.06 0 18 18 18 0.026 18 1 18 (ft 2 ) 3028 Floor Total OA 280

Third Floor Apartment 757 4 0.06 5 65 65 65 0.093 65 1 65 262 306 0 0.06 0 Corridor/Stairwell 18 18 18 0.026 18 1 18 (ft 2 ) 3028 Floor Total OA 280 Building 1 Total OA (CFM) 1452 Required Actual First-Third Floor Window Free Window Area (ft 2 ) Area Free Area 8773 350.92 365.1

Building 4 First Floor Apartment 717 4 0.06 5 63 63 63 0.090 63 1 63 252 Corridor/Stairwell 253 0 0.06 0 15 15 15 0.022 15 1 15 (ft 2 ) 2868 Floor Total OA 267 Second Floor Apartment 717 4 0.06 5 63 63 63 0.090 63 1 63 252 Corridor/Stairwell 240 0 0.06 0 14 14 14 0.021 14 1 14 (ft 2 ) 2868 Floor Total OA 266 Third Floor Apartment 717 4 0.06 5 63 63 63 0.090 63 1 63 252 Corridor/Stairwell 240 0 0.06 0 14 14 14 0.021 14 1 14 (ft 2 ) 2868 Floor Total OA 266 Required Actual Window Free Window Floor Area (ft 2 ) Area Free Area 8604 344.16 374.4 Building 4 Total OA (CFM) 800

Buildings 2-3/5-6/7-8/9-10 Basement (2) - 4 Person 717 4 0.06 5 Apartment 63 63 63 0.090 63 1 63 252 Corridor/Stairwell 185 0 0.06 0 11 11 11 0.016 11 1 11 (ft 2 ) 1434 Floor Total OA 263 First Floor 717 4 0.06 5 Apartment 63 63 63 0.090 63 1 63 252 Corridor/Stairwell 337 0 0.06 0 20 20 20 0.029 20 1 20 (ft 2 ) 2868 Floor Total OA 272 Second Floor 717 4 0.06 5 Apartment 63 63 63 0.090 63 1 63 252 Corridor/Stairwell 316 0 0.06 0 19 19 19 0.027 19 1 19 (ft 2 ) 2868 Floor Total OA 271 Third Floor 717 4 0.06 5 Apartment 63 63 63 0.090 63 1 63 252 Corridor/Stairwell 316 0 0.06 0 19 19 19 0.027 19 1 19 (ft 2 ) 2868 Floor Total OA 271 Required Actual Total Area per Window Free Window Building (ft 2 ) Area Free Area 10038 401.52 403.62 Building 2 Total 1096 Building 3 Total 1096 Building 5 Total 1096 Building 6 Total 1096 Building 7 Total 1096 Building 8 Total 1096 Building 9 Total 1096 Building 10 Total 1096 Total OA (CFM) 8768

Appendix B 13

Building 1 Building 4 Basement Level First Floor DF-2 TV Room 103 114 Apartment 63 63 Game Room 160 178 Corridor/Stairwell 15 15 Second Floor DF-3 Fitness Room 113 113 Apartment 63 63 Corridor 11 11 Corridor/Stairwell 14 14 Cyber Lounge 104 104 Third Floor Apartment 63 63 DF-4 Conference 51 51 Corridor/Stairwell 14 14 Office 16 16 Group Meeting Room 88 98 Reception 20 22 Office 17 19 Closet 5 0.9 File Room 13 14 First Floor Unit C - 3 Person Apartment 51 51 Unit D - 2 Person Apartment 46 46 (2) - 4 Person Apartment 65 65 Corridor/Stairwell 20 20 Second Floor Apartment 65 65 Corridor/Stairwell 18 18 Third Floor Apartment 65 65 Corridor/Stairwell 18 18

Buildings 2-3/5-6/7-8/9-10 Basement (2) - 4 Person Apartment 63 63 Corridor/Stairwell 11 11 First Floor Apartment 63 63 Corridor/Stairwell 20 20 Second Floor Apartment 63 63 Corridor/Stairwell 19 19 Third Floor Apartment 63 63 Corridor/Stairwell 19 19

References 1. ASHRAE. 2004. ANSI/ASHRAE Standard 62.1-2004 Ventilation for Acceptable Indoor Air Quality. American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. 16