Building Code Extracts from the National Building Code of Canada 2010

Similar documents
Building Code Extracts from the National Building Code of Canada 2010

Extracts from the National Building Code of Canada

2014 Alberta Building Code Classifications of Buildings and the Types of Occupancies Allowed within Buildings

(2) Determining Occupant Loads for the Operation of a Building (The Alberta Fire Code)

PLUMBING SYSTEMS CHAPTER 29

2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS

ARTICLE 834. PD 834. PD 834 was established by Ordinance No , passed by the Dallas City Council on December 8, (Ord.

Division S-19. PD Subdistrict 19.

2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC.

SECTION 838 "C-6" - GENERAL COMMERCIAL DISTRICT

ARTICLE 533. PD 533. C.F. Hawn Special Purpose District No. 1

Discuss the history of fires that resulted in much of the development of codes related to means of egress. Review mean of egress terminology

Copyright 2013, Queen s Printer for Ontario

DIVISION FIVE COMMERCIAL ZONES. 1. Permitted Uses of Land, Buildings, and Structures

Ontario Municipal Board Order issued on February 25, 2005 in Board File Nos. PL and PL CITY OF TORONTO. BY-LAW No.

City of Humble 114 W. Higgins, Humble, Texas ( 281 ) ( 281 )

ARTICLE 598. PD 598.

ARTICLE 535. PD 535. C.F. Hawn Special Purpose District No. 3

SCHEDULE C. Application 1 The provisions of this Schedule apply to all zones except:

Column 1 Column 2 Column 3 USE OR USE CATEGORY SPACES REQUIRED PER BASIC ADDITIONAL MEASURING UNIT. 2 per dwelling unit

E1-12: Final Decision AS

Magnesia Falls Drive, Suite 4 Rancho Mirage, CA

COTTON MILLS DISTRICT REDEVELOPMENT - C.M.D.R. - - G E N E R A L -

2010 City of San Mateo General Plan Update Zoning Code Revisions

SECTION SIX PERMITTED USES

Background: 5 th Edition (2014) Florida Building Code, Building

SECTION 13 COMMERCIAL DISTRICT 1 (C.1)

PART. Building Planning. Chapter 3: Building Use Chapter 4: Construction Types Chapter 5: Building Size Chapter 6: Special Uses and Considerations

CITY OF TORONTO. BY-LAW No

FOR SALE COMMERCIAL BEACHSIDE LOT

SERVICE COMMERCIAL ZONES

Permitted Uses and Conditional Uses Key: P Permitted Use C Conditional Use

Secondary Suites Changes between the 2006 ABC and the 2014 ABC Requirements

Section TOC-C Corridor permitted uses.

FOR SALE. +/- 2,400 Sq Ft Professional Office Condo Willoughby Business Centre SE Willoughby Boulevard, Stuart, Florida 34994

Retail Space for Lease in Neighborhood Shopping Center

ARTICLE 847. PD 847. PD 847 was established by Ordinance No , passed by the Dallas City Council on April 27, (Ord.

DRAFT ZONING BY-LAW AMENDMENT 75 DUBLIN STREET NORTH ZC1612

( ) 1. By-law , as amended, is hereby further amended: (1) by adding to Section the following zone:

East Side Community Meeting

Washington State Energy Code TABLE C (2) INTERIOR LIGHTING POWER ALLOWANCES: SPACE-BY-SPACE METHOD

CITY OF JERSEY CITY GENERAL DEVELOPMENT APPLICATION

The New NYC Building Code Chapter 10 Means of Egress. New York City Department of Buildings. Technical Affairs. Fatma M. Amer, P.E.

Presentation By. Chris Poujol. Jeffery Rodriguez. James Rigley

3. Miscellaneous Instructions and Definitions.

Disability (Access to Premises Buildings) Standards

SECTION 6 Page 1 of 24 SECTION 6 OFF-STREET PARKING AND OFF-STREET LOADING

13. Automobile maintenance service, but not commercial truck maintenance service

BUILDING CODE COMMISSION

Sec Tier 2 principal uses and structures. The principal uses of land and structures allowed in Tier 2 are provided below subject to the

NOW, THEREFORE, the Mayor and Council of the City of Alpharetta, Georgia hereby ordain:

ARTICLE 383. PD 383.

ORDINANCE NUMBER 2015-

Churches, synagogues, temples, mosques and other religious worship facilities, on lots of one acre or more.

ZONING. 145 Attachment 1

Building Classification City of New York

FOR DISCUSSION PURPOSES ONLY EDMONTON INTERNATIONAL AIRPORT VICINITY PROTECTION AREA REGULATION

2015 IBC Allowable Heights and Areas

GRANDSTAND/JERRY MYERS ARENA RENTAL FORM 2016/2017. Postal Code: Phone Number: (h) Event Date/Time:

No person shall within any General Commercial (C3) Zone use any lot or erect, alter or use any building or structure except as specified hereunder:

CUDAHY MUNICIPAL CODE

ZONING. 317 Attachment 4

Accessibility and ADA: Facility Standards Update. Technical Specifications: Chapters 8-10

Commercial Property with Great Visibility for Sale or Lease. For Sale at $1,500, or For Lease at $12.00/SF NNN

BYLAW NUMBER 159D2016

NEW ACCESSIBILITY CHANGES

ARTICLE 426. PD 426.

ADA/TAS Plan Review & Inspection Worksheet Texas Access

11.1 OFF STREET PARKING REGULATIONS

4. Public service facilities, such as police and fire stations.

C-2 District Schedule

ARTICLE 408. PD 408.

ARTICLE 631. PD 631. West Davis Special Purpose District

Sec. 20. District and intent -- UMD, Urban Mixed-Use District.

General USE Character of Occupancy of Building/Structure PRINCIPAL PRINCIPAL CONDITIONAL Zoning Classification 1. Indigenous family dwelling units

EDMONTON INTERNATIONAL AIRPORT VICINITY PROTECTION AREA REGULATION

ATTACHMENT C. Development Requirements

Division S-39. PD Subdistrict 39.

ARTICLE 468. PD 468. Oak Cliff Gateway Special Purpose District

ARTICLE 521. PD 521.

ORDINANCE NO

BYLAW NUMBER 20P2017

ARTICLE 428. PD 428.

The New NYC Building Code Chapter 11 Accessibility. New York City Department of Buildings. Technical Affairs. Keith Wen, R.A. Copyright Materials

C-5, C-5A and C-6 Districts Schedule

ARTICLE 462. PD 462.

expenses approximately $2.00 Sq.Ft. plus utilities SLC COMMERCIAL 2488 SE Willoughby Blvd, Stuart, FL

FILED: BRONX COUNTY CLERK 06/13/2014 INDEX NO /2013E NYSCEF DOC. NO. 24 RECEIVED NYSCEF: 06/13/2014. Exhibit A

SHOPPING CENTER DISTRICT (Zone BSC)

ARTICLE 406. PD 406.

GC General Commercial District

BUILDING CODE COMMISSION

ACCESSIBILITY CHAPTER 11

Institutional & Special Purpose Bldngs Code Communication Code

> 20,102sf, two story Office/Retail space on busy corner of Poquonnock Rd. & Mitchell St. > 1.21 acre > Town Water/Sewer/Gas > Zone GC

ARTICLE 440. PD 440.

DRS RWANDA STANDARD. Code of practice for fire safety. of building. Part 5: Exit requirements and personal hazard.

C-2B District Schedule

NOW, THEREFORE, BE IT ORDAINED BY THE COUNCIL OF THE CITY OF SAN JOSE:

PERMITTED USES: Within the MX-1 Mixed Use Neighborhood District the following uses are permitted:

Transcription:

3.2.6. Additional Requirements for High Buildings (See Appendix B.) Building Code 3.2.6.1. Application This Subsection applies to a building a) of Group A, D, E or F major occupancy classification that is more than i) 36 m high, measured between grade and the floor level of the top storey, or ii) 18 m high, measured between grade and the floor level of the top storey, and in which the cumulative or total occupant load on or above any storey above grade, other than the first storey, divided by 1.8 times the width in metres of all exit stairs at that storey, exceeds 300, b) containing a Group B major occupancy in which the floor level of the highest storey of that major occupancy is more than 18 m above grade, c) containing a floor area or part of a floor area located above the third storey designed or intended as a Group B, Division 2 or 3 occupancy, or d) containing a Group C major occupancy whose floor level is more than 18 m above grade. 3.2.7.3. Emergency Lighting 1) Emergency lighting shall be provided to an average level of illumination not less than 10 lx at floor or tread level in a) exits b) principal routes providing access to exit in open floor areas and in service rooms, c) corridors used by the public, d) corridors serving sleeping rooms in a treatment occupancy, e) corridors serving sleeping rooms in a care occupancy, except corridors serving sleeping rooms within individual suites of care occupancy, f) corridors serving classrooms, g) underground walkways, h) public corridors, i) floor areas or parts thereof where the public may congregate i) in Group A, Division 1 occupancies, or ii) in Group A, Division 2 and 3 occupancies having an occupant load of 60 or more, j) floor areas or parts thereof of daycare centreswhere persons are cared for, and k) food preparation areas in commercial kitchens. 2) Emergency lighting to provide an average level of illumination of not less than 10 lx at floor or catwalk level shall be included in a service space referred to in Sentence 3.2.1.1.(8). 3) The minimum value of the illumination required by Sentences (1) and (2) shall be not less than 1 lx. 4) In addition to the requirements of Sentences (1) to (3), the installation of battery-operated emergency lighting in buildings or part thereof where treatment is provided shall conform to the appropriate requirements of CSA Z32, Electrical Safety and Essential Electrical Systems in Health Care Facilities. 3.2.7.4. Emergency Power for Lighting 1) An emergency power supply shall be a) provided to maintain the emergency lighting required by this Subsection from a power source such as batteries or generators that will continue to supply power in the event that the regular power supply to the building is interrupted, and b) so designed and installed that upon failure of the regular power it will assume the electrical load automatically for a period of i) 2 h for a building within the scope of Subsection 3.2.6., ii) 1 h for a building of Group B major occupancy classification that is not within the scope of Subsection 3.2.6., and iii) 30 min for a building of any other occupancy. (See Appendix A.) 2) If self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, Emergency Lighting Equipment. 3.2.7.5. Emergency Power Supply Installation Except as required by Articles 3.2.7.6. and 3.2.7.7., an emergency electrical power supply system shall be installed in conformance with CAN/CSA- C282, Emergency Electrical Power Supply for Buildings. (See Sentence 3.2.7.8.(1) for emergency electrical power supply for voice communication systems). 154

3.4.5 Exit Signs Building Code 3.4.5.1. Exit Signs 1) Every exit door shall have an exit sign placed over or adjacent to it if the exit serves a) a building more than 2 storeys in building height, b) a building having an occupant load of more than 150, or c) a room or floor area that has a fire escape as part of a required means of egress 3) Internally illuminated exit signs shall be continuously illuminated and a) where illumination of the sign is powered by an electrical circuit, be constructed in conformance with CSA C22.2 No. 141, Emergency Lighting Equipment, or b) where illumination of the sign is not powered by an electrical circuit, be constructed in conformance with CAN/ULC-S572, Photoluminescent and Self-Luminous Signs and Path Marking Systems. 4) Externally illuminated exit signs shall be continuously illuminated and be constructed in conformance with CAN/ULC-S572, Photoluminescent and Self-Luminous Signs and Path Marking Systems. (See Appendix A.) 5) The circuitry serving lighting for externally and internally illuminated exit signs shall a) serve no equipment other than emergency equipment, and b) be connected to an emergency power supply as described in Article 3.2.7.4. 6) Where no exit is visible from a public corridor, from a corridor used by the public in a Group A or B major occupancy, or from principal routes serving an open floor area having an occupant load of more than 150, an exit sign conforming to Clauses (2)(b) and (c) with an arrow or pointer indicating the direction of egress shall be provided. 7) Except for egress doorways described in Sentence 3.3.2.4.(4), an exit sign conforming to Sentences (2) to (5) shall be placed over or adjacent to every egress doorway from rooms with an occupant load of more than 60 in Group A, Division 1 occupancies, dance halls, licensed beverage establishments, and other similar occupancies that, when occupied, have lighting levels below that which would provide easy identification of the egress doorway. 2) Every exit sign shall a) be visible on approach to the exit, b) except as permitted in Sentence (3), consist of a green pictogram and a white or lightly tinted graphical symbol meeting the colour specifications referred to in ISO 3864-1, Graphical symbols Safety colours and safety signs Part 1: Design principles for safety signs in workplaces and public areas, and c) conform to the dimensions indicated in ISO 7010, Graphical symbols Safety colours and safety signs Safety signs used in workplaces and public areas, for the following symbols (see Appendix A): i) E001 emergency exit left, ii) E002 emergency exit right, iii) E005 90-degree directional arrow, and iv) E006 45-degree directional arrow 3.4.5.2. Signs for Stairs and Ramps at Exit Level In a building more than 2 storeys in building height, any part of an exit ramp or stairway that continues up or down past the lowest exit level shall have a posted sign clearly indicating that it does not lead to an exit. 9.9.1.1. Signs 9.9.11.1. Application This Subsection applies to all exits except those serving not more than one dwelling unit or a house with a secondary suite. 9.9.11.2. Visibility of Exits Exits shall be located so as to be clearly visible or their locations shall be clearly indicated. 9.9.11.3. Exit Signs 1) Every exit door shall have an exit sign placed over it or adjacent to it if the exit serves a) a building that is 3 storeys in building height, b) a building having an occupant load of more than 150, or c) a room or floor area that has a fire escape as part of a required means of egress. 155

Building Code 2) Every exit sign shall a) be visible on approach to the exit, b) except as permitted in Sentence (3), consist of a green pictogram and a white or lightly tinted graphical symbol meeting the colour specifications referred to in ISO 3864-1, Graphical symbols Safety colours and safety signs Part 1: Design principles for safety signs in workplaces and public areas, and c) conform to the dimensions indicated in ISO 7010, Graphical symbols Safety colours and safety signs Safety signs used in workplaces and public areas, for the following symbols (see A-3.4.5.1.(2)(c) in Appendix A): i) E001 emergency exit left, ii) E002 emergency exit right, iii) E005 90-degree directional arrow, and iv) E006 45-degree directional arrow. 3) Internally illuminated exit signs shall be continuously illuminated and a) where illumination of the sign is powered by an electrical circuit, be constructed in conformance with CSA C22.2 No. 141, Emergency Lighting Equipment, or b) where illumination of the sign is not powered by an electrical circuit, be constructed in conformance with CAN/ULC-S572, Photoluminescent and Self-Luminous Signs and Path Marking Systems. 4) Externally illuminated exit signs shall be continuously illuminated and be constructed in conformance with CAN/ULC-S572, Photoluminescent and Self-Luminous Signs and Path Marking Systems. (See A-3.4.5.1.(4) in Appendix A.) 5) The circuitry serving lighting for externally and internally illuminated exit signs shall a) serve no equipment other than emergency equipment, and b) be connected to an emergency power supply as described in Sentences 9.9.12.3.(2), (3) and (7). 6) Where no exit is visible from a public corridor, from a corridor used by the public, or from principal routes serving an open floor area having an occupant load of more than 150, an exit sign conforming to Clauses (2)(b) and (c) with an arrow or pointer indicating the direction of egress shall be provided 9.9.11.4. Signs for Stairs and Ramps at Exit Level In buildings that are 3 storeys in building height, any part of an exit ramp or stairway that continues up or down past the lowest exit level shall be clearly marked to indicate that it does not lead to an exit, if the portion beyond the exit level may be mistaken as the direction of exit travel. 9.9.12. Lighting 9.9.11.4. Signs for Stairs and Ramps at Exit Level This Subsection applies to the lighting of all means of egress except those within dwelling units or a house with a secondary suite. 9.9.12.2. Required Lighting in Egress Facilities 1) Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps. 2) The minimum value of the illumination required by Sentence (1) shall be not less than 10 lx 2) If self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, Unit Equipment for Emergency Lighting. 9.9.12.3. Emergency Lighting 1) Emergency lighting shall be provided in a) exits, b) principal routes providing access to exit in an open floor area, c) corridors used by the public, d) underground walkways, and e) public corridors. 2) Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building. 3) Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of at least 30 min when the electric lighting in the affected area is interrupted. 156

Building Code 4) Illumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level. 5) The minimum value of the illumination required by Sentence (4) shall be not less than 1 lx. 6) Where incandescent lighting is provided, lighting equal to 1 W/m2 of floor area shall be considered to meet the requirement in Sentence (4). 7) Where self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141, Emergency Lighting Equipment. A-3.4.5.1. Graphical Symbols for Exit Signs ISO 7010, Graphical symbols Safety colours and safety signs Safety signs used in workplaces and public areas, identifies the following internationally recognized symbols for use at required exits Emergency exit RIGHT (E001) symbol from ISO 7010 Figure A-3.4.5.1.(2)(c)-B 90-degree directional arrow (E005) from ISO 7010 A-3.4.5.1.(4) Externally Illuminated Signs An external lighting source is required to properly charge photoluminescent signs. These types of signs must be lit in conformance with the charging requirements stated in CAN/ULC-S572. A-3.4.6. Application to Means of Egress The requirements in Subsection 3.4.6. apply to interior and exterior exits, as well as to ramps, stairways and passageways used by the public as access to exit. The treads, risers, landings, handrails and guards for the latter access to exit facilities must thus be provided in conformance with the appropriate requirements for exit facilities. 157

Appendix A Building Code Explonatory Material A-3.1.2. Use Classification The purpose of classification is to determine which requirements apply. This Code requires classification in accordance with every major occupancy for which the building is used or intended to be used. Where necessary, an application clause has been inserted in this Part to explain how to choose between the alternative requirements which multiple occupancy classification may present. A-3.1.2.1.(1) Major Occupancy Classification The following are examples of the major occupancy classifications described in Table 3.1.2.1.: Examples Group Divison Motion picture theatres A 1 Opera houses Television studios admitting a viewing audience Theatres, including experimental theatres Art Galleries Lecture halls A 2 Auditoria Librairies Bowling alleys Licensed beverage establishments Churches and similar places of worship Museums Club, non-residential Passenger stations and depots Community halls Recreational piers Court rooms Restaurants Dance halls Schools and colleges, non-residential Exhibition halls (other than classified in Group E) Undertaking premises Gymnasia Arenas A 3 Rinks Indoor swimming pools with without spectator seating Amusement park structures Grandstands A 4 (not elsewhere classified) Reviewing stands Bleachers Stadia Jails Psychiatric hospitals with detention quarters B 1 Penitentiaries Reformatories with detention quarters Police stations with detention quarters Prisons Care facilities with treatment Infirmaries B 2 Convalescent /recovery/rehabilitation Nursing homes with treatment centres with treatment Psychiatric hospitals without detention quarters Hospices with treatment Respite centres with treatment Hospitals Assisted/supportive living facilities Group homes B 3 Care facilities without treatment Hospices without treatment Children s custodial homes Nursing homes without treatment Convalescent/recovery/rehabilitation centres Reformatories without detention quarters without treatment Respite centres without treatment 158

Building Code Examples Group Divison Apartments Hotels C Boarding houses Houses Clubs, residential Lodging houses Colleges, residential Monasteries Convents Motels Dormitories Schools, residential Banks Medical offices D Barber and hairdressing shops Offices Beauty parlours Police stations without detention quarters Dental offices Radio stations Dry cleaning establishments, self-service, Small tool and appliance rental and service not using flammable or explosive solvents or establishments cleaners Laundries, self-service Department stores Shops E Exhibition halls Stores Markets Supermarkets Bulk plants for flammable liquids Flour mills F 1 Bulk storage warehouses for hazardous Grain elevators substances Lacquer factories Cereal mills Mattress factories Chemical manufacturing or Paint, varnish and pyroxylin product factories processing plants Rubber processing plants Distilleries Spray painting operations Dry cleaning plants Waste paper processing plants Feed mills Aircraft hangars Mattress factories F 2 Box factories Laundries, except self-service Candy plants Planing mills Cold storage plants Printing plants Dry cleaning establishments not using Repair garages flammable Salesrooms or explosive solvents or cleaners Service stations Electrical substations Storage rooms Factories Television studios not admitting a viewing audience Freight depots Warehouses Helicopter landing areas on roofs Wholesale rooms Laboratories Workshops Creameries Sample display rooms F 3 Factories Storage garages, including open air parking garages Laboratories Storage rooms Light-aircraft hangars (storage only) Warehouses Power plants Workshops Salesrooms 159