A STUDY ON AN ESTIMATION METHOD OF THE EFFECTIVE OPENING AREA OF ENTRANCE DOORS AND WINTER AIRFLOW RATE INTO ATRIUM BUILDINGS

Similar documents
Large Building Air Leakage Testing

The Impact of Balconies on Wind Induced Ventilation of Singlesided Naturally Ventilated Multi-storey Apartment

On Smoke Control by Pressurization in Stairwells and Elevator Shafts

On Smoke Control by Pressurization in Stairwells and Elevator Shafts

The effect of the wind speed velocity on the stack pressure in medium-rise buildings in cold region of China

NFPA (2012). In a high-rise building, stairwell pressurization systems typically utilize multiple fans distributed over the height of the stair, a duc

ASHRAE STANDARD 62.1 VENTILATION ANALYSIS UNIVERSITY RIDGE AT EAST STROUDSBURG UNIVERSITY EAST STROUDSBURG, PA PREPARED FOR: JAE-WEON JEONG, PH.D.

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Evacuation Design Focused on Quality of Flow

Where rivers connect

Protecting the Stair Enclosure in Tall Buildings Impacted by Stack Effect

Building Science Fundamentals Ventilation May 25-26, Joseph Lstiburek, Ph.D, P.Eng, ASHRAE Fellow. Adventures In Building Science

The effect of atrium façade design on daylighting in atrium and its adjoining spaces

Analyzing Ventilation Effects of Different Apartment Styles by CFD

Vestibule Requirement Intent

Sorting based on amenities and income

ctbuh.org/papers Study on Sky View Factor of High-Rise Residences for Shrinking Cities in Japan Title:

COMPARISON OF SAMPLING METHODS FOR AIR TIGHTNESS

Dwelling air-tightness in a 55 years old estate

Measuring Air Change Rates using the PFT Technique in Residential Buildings in Northern Portugal

Stairwell Pressurization in a Cold Climate

Indoor climate of an unheated apartment and its impact on the heat consumption of adjacent apartments

Impacts of Maximum Allowable Building Footprint on Natural Ventilation in Apartment Building

MULTIFAMILY PERFORMANCE PROGRAM Technical Topic New Buildings Savings Opportunity - Stairwell Lighting

Neighborhood Effects of Foreclosures on Detached Housing Sale Prices in Tokyo

Study of the energy performance of Korean apartment buildings with alternative balcony configurations

World Renewable Energy Congress (WRECX) Editor A. Sayigh 2008 WREC. All rights reserved. 822

Energy variations in apartment buildings due to different shape factors and relative size of common areas

2015 IBC Allowable Heights and Areas

Micro Factors Causing Fall in Land Price in Mixture Area of Residence and Commerce

The Change of Urban-rural Income Gap in Hefei and Its Influence on Economic Development

CHANGE IN VALUE ALTERATIONS MADE OCCUPANCY CHANGES

Element Z General Design Requirements Owner Standards and Other Requirements

Using Hedonics to Create Land and Structure Price Indexes for the Ottawa Condominium Market

Single Point of Failure and Inter-relationship between Stair Pressurisation System and Evacuation Strategy for Tall Buildings

Hedonic Pricing Model Open Space and Residential Property Values

2012 IBC Mixed Occupancies

Passive Cooling Measures for Multi-Unit Residential Buildings

ABSTRACT. Keywords: Adaptive behavior, Wind flow, Energy-saving, Energy consumption, Coastal areas

What Factors Determine the Volume of Home Sales in Texas?

Relationship of age and market value of office buildings in Tirana City

How Did Foreclosures Affect Property Values in Georgia School Districts?

Hedonic Regression Models for Tokyo Condominium Sales

The relationships between the extent of mould problems and physical building characteristics in high-rise apartment buildings

Financial Statement Instructions 324

Review of the Prices of Rents and Owner-occupied Houses in Japan

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 7 Heiselberg, Per Kvols. Publication date: 2016

Indoor climate and energy consumption in residential buildings in Estonian climatic conditions

ESCAPE ROUTES DESIGN SPECIFICATION ANALYSIS FOR OPTIMUM EVACUATION OF 200 PEOPLE IN HIGH-RISE BUILDING

TENANT DESIGN MANUAL UPDATED JULY 2016

The Improved Net Rate Analysis

Separating the Age Effect from a Repeat Sales Index: Land and Structure Decomposition

TENANT DESIGN MANUAL UPDATED JULY 2015

INTERGENERATIONAL MOBILITY IN LANDHOLDING DISTRIBUTION OF RURAL BANGLADESH

KIMBELL ART MUSEUM - LOUIS KAHN Forth Worth, Texas THE UNPROGRAMMED Gijs Loomans

Regression Estimates of Different Land Type Prices and Time Adjustments

Chapter 35. The Appraiser's Sales Comparison Approach INTRODUCTION

Chapter 11 Investments in Noncurrent Operating Assets Utilization and Retirement

11.433J / J Real Estate Economics

DESIGN OF FLOW AND HOLDING CAPACITY OF ESCAPE ROUTES IN BUILDINGS

THE IMPACT OF RESIDENTIAL REAL ESTATE MARKET BY PROPERTY TAX Zhanshe Yang 1, a, Jing Shan 2,b

HOUSING CODE CHECKLIST FOR RENTAL INSPECTIONS

Evaluation of Vertical Equity in Residential Property Assessments in the Lake Oswego and West Linn Areas

Lutron Stairwell Fixture Solutions

Breezewood Rentals, LLC Heated Shop and Storage Rental Application

for taxation 2019 Finnish revaluation of land Presented at the FIG Working Week 2017, May 29 - June 2, 2017 in Helsinki, Finland

MULTIFAMILY WEATHERIZATION FREQUENTLY ASKED QUESTIONS

2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC.

An Assessment of Current House Price Developments in Germany 1

FIREFIGHTING PROCEDURES VOLUME 1, BOOK 1, ADDENDUM 3 September 4, 2012 WIND IMPACTED FIRES IN FIREPROOF MULTIPLE DWELLINGS 1.

Companies are grouped into four types based on how they choose office space to rent.

PROPOSED DEVELOPMENT AT 8899 BEVERLY BOULEVARD (ROSEWOOD AVE AND BEVERLY BLVD SEWER)

ELECTRICAL LOAD CHARACTERISTICS OF SUPERINSULATED MULTIFAMILY HOUSING: A CASE STUDY

ATLANTA ZONING ORDINANCE UPDATE

PP Course # Instructor Information. Patrick Vandergriff 35 Cottonwood Canyon Road La Luz, NM

The Division of Responsibility within a Condominium Corporation

Suite Metering Provisions Under the Residential Tenancies Act, 2006 and the Energy Consumer Protection Act, Consultation Paper

Re: Parking Study Davenport Road Mixed Use Development

TENANT DESIGN MANUAL UPDATED JULY 2015

Waiting for Affordable Housing in NYC

CHAPTER 10 ARTICLE II DIVISION 2: MINIMUM STANDARDS

Governors State University Tornado & Severe Weather Shelter Plan August 4, 2016

TENANT DESIGN MANUAL UPDATED DECEMBER 2018

IFRS 16: Leases; a New Era of Lease Accounting!

ASSESSMENT OF ACCESSIBILITY IN APARTMENT MIXED-USE HOUSING -IN THE CASE OF KABUL

TENANT DESIGN MANUAL UPDATED JUNE 2015

Estimating the Value of Foregone Rights on Land. A Working Paper Prepared for the Vermillion River Watershed Joint Powers Organization 1.

1014 Ontario Municipal Board Commission des affaires municipales de l Ontario. Quad (King & Brant) Inc.

Determinants of residential property valuation

THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist.

MONITORED RESULTS FROM AN INNOVATIVE SOLAR RENOVATION OF MULTI STOREY HOUSING - EU SHINE ENGELSBY, FLENSBURG

TENANT DESIGN MANUAL UPDATE JUNE 2015

LEASE ACCOUNTING UNDER IFRS 16 AND IAS 17 A COMPARATIVE APPROACH

Islamabad, a town planning example for a sustainable city

Estimating User Accessibility Benefits with a Housing Sales Hedonic Model

DAYLIGHTING DESIGN. Strategies for Achieving Quality Daylighting. Spring 2014 College of Architecture, Texas Tech University 1

Regional Housing Trends

Water Use in the Multi family Housing Sector. Jack C. Kiefer, Ph.D. Lisa R. Krentz

Attachment 2: Draft Zoning By-law Amendment (Amends By-law No ) CITY OF TORONTO. BY-LAW No. XXX- 2017

REAL ESTATE RENOVATION DECISIONS BASED ON COST APPROACH APPRAISING PRINCIPLES Real estate renovation decisions

Transcription:

A STUDY ON AN ESTIMATION METHOD OF THE EFFECTIVE OPENING AREA OF ENTRANCE DOORS AND WINTER AIRFLOW RATE INTO ATRIUM BUILDINGS Kimiko Kohri Graduate School of Engineering, Utsunomiya University Utsunomiya 31-8585, Japan Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 3 ABSTRACT This study develops a simplified estimation method for calculating the effective opening area of automatically operated entrance doors and the winter airflow rate into entrance halls due to the stack effect. The relationships between the number of people passing through the doors and the average opening area ratio were obtained from detailed simulations of a variety of different types of doors, and were approximated by equations. The relationships between the effective entrance door opening areas and the outdoor airflow rates were determined by solving air balance equations for each of the six types of buildings. These relationships were also approximated by equations. The proposed estimation method, utilizing these two kinds of approximation equations, was used to examine the changes in the winter outdoor airflow rate through the entrance doors on a weekday for six different buildings. This method helps designers plan entrances and determine the proper heating equipment capacity. INTRODUCTION Automatically operated sliding doors with a vestibule are common entrances in Japan. In the winter, frequent use of this type of entrance door allows for a large amount of outdoor airflow to enter high-rise buildings. This may cause serious problems, especially in buildings with tall s, because the is often an easy route for the airflow due to the stack effect. A simplified estimation method for the winter airflow rate through entrance doors caused by the stack effect would help designers plan entrances and determine the proper heating equipment capacity. Previously, a simplified estimation method for the calculation of the effective entrance door opening area and the winter outdoor airflow rate due to the stack effect had been proposed (Kohri, 1). In this study, the method has been expanded and improved to include various door specifications for several types of s. ESTIMATION OF THE DOOR OPEN- ING AREA This method was developed to estimate the effective opening area of automatically operated sliding double doors with a vestibule under a given amount of entrance traffic. Figure 1 shows the opening and closing Effective opening area [m] difference in the start time of the opening action between the outisde and inside door 4 outside door Ae,o waiting time when fully open inside door Ae,i combined value Ae Maximum opening width: 1.6m Opening hight: 3m Coefficient of discharge:.65 5 Time [sec] * Ae={1/Ae,o +1/Ae,i } -1/ (b) Arrangement of (a) Opening and closing action of the doors the doors Figure 1 Standard entrance doors Effective opening area [m] 3 1 1 3 4 5 Time [min] * Number of people passing through the doors: people every 5 minutes inside door outside door compaund area Figure Changes in effective opening area of the standard doors at time intervals of. sec due to occurrence of persons passing through them - 657 665 -

actions of a typical entrance door when a person enters a building. These doors are used as the standard doors for the simulations in this study. Figure presents the results of a detailed simulation in which people pass through the doors every 5 minutes. The effective opening area was calculated every. seconds and the pattern of people passing through the entrance doors was assumed to be a Poisson distribution. The average effective opening area for a given entrance frequency depends on an averaging period unless the averaging period is enough long. The previous study found that 15 minutes of averaging is necessary for obtaining the average effective opening area that is independent of averaging periods. The effective opening area averaged over 15 minutes for the entrance traffic using the standard doors was obtained from the detailed simulation. The results are shown in Figure 3. The average opening area ratio is defined as the ratio of the average effective opening area to the maximum effective opening area. The curve shown in Figure 3 can be approximated as an exponential polynomial expression and the effective opening area of the doors A e (in square meters) can be estimated using the following equations. A e =ra e,max (1) r=1+a 1 exp(-a 1 X)+A exp(-a X) () where r is the average opening area ratio of the doors, A e,max is maximum effective opening area in square meters, X is the number of people passing through the doors every 5 minutes, and A 1, A, a 1, and a, are the coefficients of r. The average opening area ratio is affected by variety of factors, such as the maximum opening width of the door, the waiting time when the door is fully open, and the time from when the first door starts to open until the second door starts to open. Approximation equations for each of these factors were generated. The Average opening area ratio [-] 1.8.6.4. 3 Number of people passing through the doors [persons/5minutes] Figure 3 Relationship between average opening area ratio and number of people passing through the standard doors coefficients for the approximation equations are summarized in Table 1. Using the coefficients in Table 1, the effective opening area can be easily estimated for 36 different types of doors. The effects of the three door factors on the effective opening area are shown in Figure 4. Although the waiting time when the doors are fully open and maximum opening width significantly affect the effective opening area, the difference between the outside and inside door opening start times has only a slight effect. ANALYSIS OF AIR MOVEMENT IN SIX OFFICE BUILDINGS Besides entrance door conditions, other factors such as the building height, the indoor/outdoor temperature difference, the presence of elevator s, stairwells, and spaces with open ceilings, and the air tightness of the building also affect the outdoor airflow rate due to stack effect. This study focuses on the effect of Table 1 Coefficients in approximation equations of effective opening area for different types of doors Tw: waiting time when fully open [sec] ΔT: difference in the start time of the opening action between the outside and inside door A1 A α1 α :Coefficients for calculation of Ae Approximation equations of the average opening area A e [m] A e= r A emax r=1+ A 1 exp( - α1 x)+ A exp( - α x) r : Average opening area ratio of the doors [-] Aemax : Maximum effective area of the opening [m] x : The number of people passing through the doors [person/5minutes] Tw Δ T Wmax Coefficients A1 A α 1 α 1. -1.8.8.6.7 1.5 1.6 -.95 -.5.6.15. -.89 -.11.7.33 1. -1.13.13.6. 1.5 3. 1.6-1.9.9.7.16. -1.8.8.7.11 1. -1.14.14.6.35 6. 1.6-1.11.11.7.57. -1.11.11.7.51 1. -1...9.8 1.5 1.6-1.11.11..9. -1.8.8..8.5* 3.* 1. -1...9.19 1.6* -1.15.15.9.19. -1.17.17..16 1. -1.19.19.9.58 6. 1.6-1.17.17.9.57. -1.3.3..37 1. -1.6.6.1.7 1.5 1.6-1.8.8.13.. -1...13.15 1. -1...1.3 3.5 3. 1.6-1.3.3.13.1. -1.14.14.13. 1. -1.3.3.11.57 6. 1.6-1.1.1.1.61. -1...13.59 1. -1.8.8.17.15 1.5 1.6 -.96 -.4.17.37. -.93 -.7.17.5 1. -1...17.3 5. 3. 1.6-1.11.11.17.3. -1.8.8.17.33 1. -1.6.6.16.7 6. 1.6-1.56.56.18.36. -1.31.31.18.47 * standard condition - 658 666 -

Effective Opening Area [m] 3 3.5sec 5sec 3sec 1.5sec 1.5sec 1.5sec 9sec 6sec m 1.6m 1.m 3 Number of people passing through the doors [persons/5minutes] (a) Waiting time when fully open the. In most buildings with s, the outdoor airflow rate entering the building is substantially larger than in buildings with no. Atria are often used as entrance halls, thereby providing an easy route for upward airflow due to the winter stack effect. Airflow balance for a whole building was solved in order to clear the characteristics of winter air movement through each of several buildings. Air pressures at floor level in s on each floor and in elevator s and stairwells were treated as unknown values. Airflow balance equations for all the spaces in a building were solved simultaneously. In calculation of air leakage rate through exterior walls and interior walls between s and an, a flow exponent of /3 was assumed and the value of flow coefficient was assumed according to the air tightness of walls. These flow coefficients were presented for Japanese buildings by M. Hayakawa and T. Togari (1989). Crack sizes of doors like doors, elevator doors and stairwell doors were assumed to be the value obtained from the measurements in an existing office building (Kohri, 1). In this study, six different types of 3-story office buildings were used in the simulations, five of them with s and one without. All six building types have two entrances on the first floor. A detailed description of each of the building types is provided below. 1) Type S1 Building type S1 has an that is partially open to the adjacent s. The is used as an entrance hall and its ceiling is open up to the 3th story. Every floor has a corridor that surrounds the. Both the corridor and the hall to the elevator on each floor are open to the, with a balustrade on the side. Internal walls separate the offices from the corridor. 3 3 Number of people passing through the doors [persons/5minutes] (b) Difference in the start time of the opening action between the outside and inside door Number of people passing through the doors [persons/5minutes] (c) Maximun opening width Figure 4 Relationship between effective opening area and number of people passing through the doors for various doors Table Building schematics and the airflow balance conditions for 6 types of buildings (Building) Number of story above ground: 3 Building use: office Total occupants: about, persons (Office floor) Floor area: 1,6m/floor Space volume: 48m3/floor Area of building envelope: 7m/floor (Atrium) Ceiling height: 1m for building type S1, O1 and C 6m for building type S and O Space volume: 5,8m3 for building type S1, O1 8,8m3 for building type S and O 35,4m3 for type C (Air temperature and outside wind) Air temperature: outdoor o C o C office o C elevator s and stairwells 18 o C Outside wind: absent (HVAC system) The effects of HVAC systems are ignored. ) Type S Building type S s is similar to that of building type S1. The difference between the two is that the ceiling of the in building type S is only open up to the 15th story. 3) Type O1 Buildings type O1 has an open, meaning that there is no partition between the offices on each floor and the. The is used as an entrance hall and its ceiling is open up to the 3th story. 4) Type O Building type O has two open atria. The that begins on the first floor and is open up to the 15th story is used as an entrance hall. The other begins on the 16th floor and is open up to the 3th story - 659 667 -

5) Type C Building type C has a closed, meaning that there are partitions between the and the offices on every floor. The is used as an entrance hall and its ceiling is open up to the 3th story. 6) Type N Building type N has neither an nor any with an open ceiling. Table details the building schematics and the airflow balance conditions that will be used in the simulations. The intended use of the proposed estimation method is for determining the heating equipment s load requirements. In this paper, the building is assumed to be located in Tokyo and, therefore, the indoor and outdoor temperatures are typical heating design values used in the Tokyo area. For the purposes of this simulation, the outside wind is assumed to be absent and the effects of heating, ventilation and air-conditioning (HVAC) systems are ignored. Data for the air leakage through the doors and walls are given in Table 3. Before the relationship between the door effective opening area and the outdoor airflow rate was obtained, the air movement characteristics in the building due to the stack effect were analyzed using simulations. In this analysis, the total effective opening area of the two entrance doors is assumed to be square meters. This opening area is the value based upon 14 people passing through two standard doors. Figure 5 shows the floor plan and the airflow circuit network of building type S1. 38 unknown pressure locations are identified, including three in the elevator s and two in the stairwells. Airflow balance equations were used to determine the pressure values for these 38 spaces. Figure 6 presents the airflow balance in both the and the offices on each floor. In this study, the airflow rate in and out of a space is expressed as an air exchange rate in terms of air changes per hour (ACH). This value that defines the airflow rate relative to the volume of the offices on a typical floor. In building type S1, the main route of the upward airflow is through the. The outdoor air enters the through the entrance doors, and then the air moves to the s above the 9th floor. The elevator and stairwell air temperatures are assumed to be slightly lower than that of the. The air moves into the s through doors on the higher floors. The air moves into the through doors on the lower floors. Figure 7 shows the results of the simulation for building type N. The airflow moves out of the lower elevator s and into the higher elevator s on the 15th floor. The results of the simulations for building types O1, O, C, and S are shown in Figures 8-1, 8-, 8-3 and 8-4, respectively. The air movement characteristics of building type O1 are similar to those for Table 3 Data for air leakage (a) Effective opening area of doors Ae: effective opening area of each door [m] Door Ae Number of door Elevator door.35 9 on 1F and 1 on B1F 5 on each of the other floors Stairwell door. on each floor Room door.56 4 on each floor (b) walls Wall Tightness Wall area [m/floor] Exterior walls Average 44 for building type C in the 4 for the other type Exterior walls Tight 8 for building type S1, in the O1 and O 4 for building type S Interior walls Average 8 for building type C between the s and the arium Note) Air leakage rate through walls Q [lit/s m] was obtained from the following equation. Q=K P^(1/1.5) Where, K: flow coefficient [lit/(s m Pa^(1/1.5))] K=.43,.86,.173 for tight, average, leaky walls, respectively. building type S1, with the main upward airflow route through the. In building type O, the air flows out of the lower and flows into the higher via the elevator and stairwell s. In building type C, the upward airflow through the and the upward airflow through the s run parallel to each other. In building type S, the air flows from into the s and into the s above the 15th floor. In these simulations, the air leakage characteristics of walls and doors were assumed to be the reasonable value based on the results of the previous studies. It is difficult to directly verify the simulated value of airflow rate with measured value because of difficulty of measurement of airflow rate such as outdoor airflow rate entering through large openings at entrances and airflow balance in a whole building. Further study is necessary in order to clear the detail of air leakage characteristics of building component, especially inner walls and partitions. ESTIMATION OF THE OUTDOOR AIR- FLOW RATE THROUGH ENTRANCE DOORS These simulations were performed in order to obtain the relationship between the effective opening area of the entrance doors and the airflow rate through them. The results are shown in Figure 9. When the effective opening area is equal to square meters, the outdoor airflow rate for building types O1 and S1 was found to be about five times higher than in building type N. For - 66 668 -

entrance 1 : EV s for higher floors : EV s for lower floors : energency EV : stairwell A : stairwell B PF 17F-3F 16F entrance The 1st floor plan, F-14F 5, 4, Spaces in the building 1F entrance hall 1F B1F B1F entrance hall Airflow circuit network Figure 5 Floor plan and airflow circuit network of building typ S1 3F F F other s outdoor to s to to other s from from s from outdoor.5 to outdoor to from from from outdoor to outdoor to - -1 1-1 -.5.5 1 (a) Airflow balance in the (b) Airflow balance (c) Pressure difference in the office s * all the air exchange rates in this paper is defined as the airflow rates relative to the space volume on a typical floor. Figure 6 Airflow balance due to stack effect for building type S1 3-5 5 other s outdoor 3F 3 F F.3-1 1 Inflow Outflow Air exchange rate [ACH] (a) Airflow balance in the office s -5 5 (b) Pressure difference Figure 7 Airflow balance due to stack effect for building type N - 661 669 -

4, 5, 4, 4, other s outdoor : EV s for higher floors : EV s for lower floors : energency EV : stairwell A : stairwell B 3F F 3 F 5, Figure 8-1 Airflow balance due to stack effect for building type O1 11. - -1 1-1 -.5.5 1 (a) Airflow balance in the (b) Airflow balance in the office s -5 5 (c) Pressure difference 3F 3 F F 5, Figure 8- Airflow balance due to stack effect for building type O 7. - -1 1-1 -.5.5 1 (a) Airflow balance in the (b) Airflow balance in the office s -5 5 (c) Pressure difference 3F 3 F F 5, Figure 8-3 Airflow balance due to stack effect for building type C 6.6 - -1 1-1 -.5.5 1 (a) Airflow balance in the (b) Airflow balance in the office s -5 5 (c) Pressure difference 3F 3 F F Figure 8-4 Airflow balance due to stack effect for building type S 8.4 - -1 1-1 -.5.5 1 (a) Airflow balance in the (b) Airflow balance in the office s -5 5 (c) Pressure difference - 66 67 -

Air exchange rate of outdoor air through entrance doors (relative to the space volume on a typical floor) [ACH] 15 5 building type-o1 type-s1 type-s type-o type-c type-n 4 6 8 Total effective opening area of entrance doors [m] Figure 9 Relationship between effective opening area of entrance doors and winter outdoor airflow rate through them for 6 types of building Number of peoplepassing through the entrance [persons/5minuts] Effective opening area of entrance doors [m] 3 4 3 1 14 total entrance entrance 1 total entrance entrance 1 Table 4 Coefficients in approximation equations of outdoor airflow rate through entrance doors β1r βr Q = B B1e Be [ R < R] Q = C R+ C [ R R ] 1 Q:Air exchange rate of outdoor air through entrance doors (relative to the space volume on typical floor [ACH] R:Total opening area of the entrance doors [m] B,B1,B,β1,β,R,C1,C: Coefficients in the approximation equations B B 1 B β 1 β R C 1 C Type-S1 16. 13.9..4.77 - - - Type-O1. 16.4 3.55.31.63 - - - Type-C 7.5.38 5.1.5 1.37 - - - Type-O 11. 9.9 1..43.81 - - - Type-S 11.5 8.9 3.1.46 1.4 - - - Type-N.35.51 1.84.77 4. 5..38.45 Air exchange rate of outdoor airflow rate through entrance doors (relative to the space volume on a typical floor) [ACH] 1 8 6 4 type-o type-c building type-o1 type-s1 type-s type-n 8 1 14 16 18 Time Figure Changes in effective opening area of entrance doors and outdoor airflow rate through them on a winter day building type S, the outdoor airflow rate was found to be about four times higher, and for building types C and O about three times higher. When the effective opening area is larger than 5 square meters for building type N, the height of the s neutral pressure level is lower than the height of the entrance door, causing the outdoor flow rate into the entrance hall to increase. The relationship between the entrance door effective opening area and the outdoor airflow rate was approximated using the equations shown in Table 4. The outdoor airflow rate through the entrance doors can be easily estimated using the approximation equations for the six types of buildings. EXAMINATION WITH PROPOSED METHOD Using the data obtained by observing the entrance traffic in an existing office building, the proposed method was used to make changes to the effective opening area and the outdoor airflow on a winter weekday. The results of these calculations are shown in Figure. Throughout the day, the effective opening area of the entrance doors fluctuates between 1 and 3.5 square meters. Although the outdoor airflow rate for building type N is almost a constant ACH, the rates for the other building types widely fluctuate. These values can reach three to six times as high as those for building type N. In fact, the outdoor airflow rate for building types O1 and S1 just before work and during lunchtime is over ACH CONCLUSION 1) The effective opening area estimation method for entrance doors at a given traffic level was expanded to be applicable to 36 different types of doors. ) An estimation method for calculating the winter outdoor airflow rate through entrance doors was presented for six different types of buildings. 3) An example calculated the changes in the outdoor flow rate through the entrance doors on a winter day using the proposed method. Although the - 663 671 -

outdoor airflow rate is an almost constant low value for building type N, the rates for buildings wildly fluctuate and reach values three to six times as high as those for building type N. REFERENCES ASHRAE 1. ASHRAE Handbook Fundamentals, ASHRAE, Inc., Atlanta Hayakawa, M., Togari, T. 1989. Air tightness of main doors and exterior walls, Journal of Architecture, Planning and Environmental Engineering (Transactions of AIJ), No.4 Kohri, K. 1. A Simulation Analysis of the Opening Area of Entrance Doors and Winter Airflow into the Entrance Hall of a High-Rise Office Building, Seventh International IBPSA Conference, Rio de Janeiro Kohri, K., Ishino, H. 3. A Study on Characteristics of Automatically Operated Doors and Outdoor Air flow Rate Coming into Buildings, Journals of Architecture, Planning and Environmental Engineering (Transactions of AIJ), No.564-664 67 -