RESEARCH PAPER AN AUDIT OF THE EGRESS SYSTEM IN MULTI-STOREY ANNEXES OF FOUR HALLS OF RESIDENCE AT KNUST, KUMASI, GHANA

Similar documents
STAIRS Design & Construction

THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist.

E1-12: Final Decision AS

2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS

CONTENTS. Introduction. Technical Terms. Requirements of good Staircase. Dimensions of step. Types of steps. Classification of Staircase

BUILDING CODE COMMISSION

Natural Light & Ventilation. Sources. Regulation 45 (1) & 45 (2) A Public road with right of way. A Courtyard or Open Space within the site.

2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC.

The New NYC Building Code Chapter 10 Means of Egress. New York City Department of Buildings. Technical Affairs. Fatma M. Amer, P.E.

Presentation By. Chris Poujol. Jeffery Rodriguez. James Rigley

Attic Floor Bedrooms 1 & 2 Family Dwellings

The House Of Stairs Sevnet

Accessible Facilities Report Template

Access to and use of buildings

NOTE: HEIGHT WIDTH OF UNOBSTRUCTED OPENING MUST EQUAL AT LEAST 5.7 SQ. FT.

MSC Guidelines for Review of Means of Escape (Subchapter H)

Spiral staircases. for industrial settings and escape routes

Single Point of Failure and Inter-relationship between Stair Pressurisation System and Evacuation Strategy for Tall Buildings

Arriving and Getting In

STAIRWAY FALL INCIDENT REPORT

Equality and Access Plan The Abbey School, Reading

The House Of Stairs Penguin Readers

DRS RWANDA STANDARD. Code of practice for fire safety. of building. Part 5: Exit requirements and personal hazard.

Evacuation Design Focused on Quality of Flow

DESIGN OF FLOW AND HOLDING CAPACITY OF ESCAPE ROUTES IN BUILDINGS

STANDARDS IN RENTED ACCOMMODATION. Housing Services

Emil Møllers Gade 41 Horsens, Denmark

BUILDING CODE COMMISSION

q/., S Lt _ _.._--.

HIGH-RISE BUILDING INVENTORY FORMS (B.I.F.) PRODUCTION AND APPROVAL

ANALYSIS OF RELATIONSHIP BETWEEN MARKET VALUE OF PROPERTY AND ITS DISTANCE FROM CENTER OF CAPITAL

Codes Checklist Document 3

Arlington County. Smart Choice Homes. Arlington County. Homes for all of us. Homes for a lifetime. Home

ADA/TAS Plan Review & Inspection Worksheet Texas Access

DEPARTMENT OF DEVELOPMENT SERVICES ACCESSIBILITY CHECK LIST FOR MULTI-FAMILY RESIDENTIAL BUILDINGS

BASIC TECHNICAL TERMS ENCOUNTERED IN HOUSE PLANNING. Building or part thereof where motor vehicles are kept.

UNIVERSITY OF HONG KONG LIBRARY. This book was received in accordance with the Books Registration Ordinance Section 4

Depreciation Determination of a D9 Earth Moving Mechanical Plant

NEW ACCESSIBILITY CHANGES

Discuss the history of fires that resulted in much of the development of codes related to means of egress. Review mean of egress terminology

Urban Management Land Information System UMLIS: Facing Urban Challenges through Efficient Revenue Collection

NFPA (2012). In a high-rise building, stairwell pressurization systems typically utilize multiple fans distributed over the height of the stair, a duc

Regional District of Nanaimo Secondary Suite Program

Ontario s 2012 Building Code Barrier-Free Design Amendments Ontario Regulation 332/12 Amended by O. Regs. 368/13 and 191/14

RISK ASSESSMENT Visits By School Parties

ESCAPE ROUTES DESIGN SPECIFICATION ANALYSIS FOR OPTIMUM EVACUATION OF 200 PEOPLE IN HIGH-RISE BUILDING

Mobility Scooter Storage Policy

SMART Access Assessment

Facilities providing accommodation for the public (e.g. Hotels, hostels, guesthouses, self catering apartments).

Copyright 2013, Queen s Printer for Ontario

SPECIFIC GUIDANCE FOR A BEDSIT TYPE HOUSE IN MULTIPLE OCCUPATION (HMO)

Residential Accessible, Type A, and Type B Dwelling Unit Requirements 2012 International Building Code and 2009 ICC/ANSI A117.1

OBTAINING A CERTIFICATE OF OCCUPANCY FOR UNAPPROVED DWELLING UNITS

2012 IBC Means of Egress

Accessible Housing Standards 2015

Compliance Schedules and Building Warrants of Fitness

Accessible drinking fountain does not have a clear 30 wide floor space centered on the drinking fountain (centerline to the counter edge is 12 ).

City of South Portland Office of the City Clerk 25 Cottage Road South Portland, ME Registration of Short-Term Rental Checklist

(2) Determining Occupant Loads for the Operation of a Building (The Alberta Fire Code)

PUBLICATION EFFICIENT EVACUATION METHODS IN TALL BUILDINGS

D DAVID PUBLISHING. Mass Valuation and the Implementation Necessity of GIS (Geographic Information System) in Albania

2.2 72ND STREET STATION ENTRANCE ALTERNATIVES

DAYLIGHT SIMULATION FOR CODE COMPLIANCE: CREATING A DECISION TOOL. Krystle Stewart 1 and Michael Donn 1

Occupants: Behaviour in Response to the High-rise Apartments Fire in Hiroshima City

The Challenge to Implement International Cadastral Models Case Finland 1

Part A Spatial Planning Typology

THINKING OUTSIDE THE TRIANGLE TAKING ADVANTAGE OF MODERN LAND MARKETS. Ian Williamson

2012 IBC Mixed Occupancies

London Accessible Housing Register A good practice guide for social housing landlords

DESIGN, ACCESS & PLANNING STATEMENT

2012 Texas Accessibility Standards Reference Guide for changes to the code

Vestibule Requirement Intent

IDP REPORT EDAN - CHELSEA WARD ECW 0021 STUDENT NUMBER :

ASSESSMENT OF ACCESSIBILITY IN APARTMENT MIXED-USE HOUSING -IN THE CASE OF KABUL

APPLICATION FOR CERTIFICATE OF ACCEPTANCE Section 97 Building Act 2004

The Impact of Balconies on Wind Induced Ventilation of Singlesided Naturally Ventilated Multi-storey Apartment

The House Of Stairs Penguin Readers

2015 IBC Allowable Heights and Areas

Purpose. Scope. Stairway Identification Signs. Emergency Evacuation and Stairwell Signage Requirements

Existing Building Accessibility Quick Checklist (CBC 11B) Job Address Permit

Problems of residential building facilities in the Czech Republic

êéëé~êåü=üáöüäáöüí Code Requirements and Costs of Incorporating Accessory Apartments in Houses

Appendix1,Page1. Urban Design Guidelines. Back to Back and Stacked Townhouses. DRAFT September 2017

Hotel Accessibility Pack

A REPORT FROM THE OFFICE OF INTERNAL AUDIT

ACCESSORY DWELLING UNITS

Examining Local Authority Housing Waiting Lists. A Submission to the Joint Oireachtas Committee on Housing, Planning and Local Government.

Department of Mechanical Engineering, Accra Technical University, Ghana. Department of Building Technology, Accra Technical University, Ghana

Understanding Accessibility Features to Meet Housing Needs

Building and Housing. Te Tari Kaupapa Whare

ALFIX STAIRWAY TOWERS

Multi-Paths of Colleges Performance Appraisal and Comparison Hui PENG 1,a, Lian-Sen WANG 2,3,4,b,*

Understanding Accessibility Features to Meet Housing Needs

General Information. Location Information. Location Use. Colorado VSPC/Drop-off/Drop-box Accessibility Survey Form. For SOS office use only

National Trust Cottages Access Statement/Guide

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

THEATER EVACUATION AND EMERGENCY SITUATION GUIDELINES THEATER EVACUATION

Raven Housing Trust. Fire Risk. Communal Area - Managed Risk Procedure

Information about accessible public transport

APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE NEWNHAM CAMPUS TORONTO, ONTARIO

Transcription:

Journal of Science and Technology, Vol. 32, No. 3 (2012), pp 49-60 49 2012 Kwame Nkrumah University of Science and Technology (KNUST) http://dx.doi.org/10.4314/just.v32i3.6 RESEARCH PAPER AN AUDIT OF THE EGRESS SYSTEM IN MULTI-STOREY ANNEXES OF FOUR HALLS OF RESIDENCE AT KNUST, KUMASI, GHANA E. A. Botchway and A. Boatemaa-Oti Department of Architecture, KNUST, Kumasi ABSTRACT Fire safety construction and fire safety equipment installations are important systems required for occupant safety. A principal consideration in this case is the provision of an effective egress system that could be located at appropriate places to aid people to safety. The absence of these measures in multi-storey blocks leaves occupants at greater risk. This paper presents results of a study carried out in students Halls of Residence at the Kwame Nkrumah University of Science and Technology (KNUST) in Ghana. Past and current statistics show an average of 300% increase in population of the multi-storey blocks on KNUST campus without any consideration of the capacity in the egress system. Documentation of the egress system in the halls of Residence was done by use of measured drawings and photography. A comparative analysis of the existing dimensions and standard dimensions revealed the narrow width, unequal treads and risers of steps and other inaccuracies of stair components. The results of the egress analysis showed the bottlenecks and constrictions that will be created when occupants rush out in an emergency. These lapses can be eliminated when proper circulation is introduced to the existing components and the construction of a suitable fire escape stair to aid occupants to a place of ultimate safety. Keywords: safety, egress, fire protection, vertical circulation INTRODUCTION Apart from providing shelter, essential fire safety systems are required in buildings to ensure the safety of occupants in the event of fire and other emergencies. Buildings have to be designed such that occupants can easily travel to a place of ultimate safety in times of fire (British Standards Institution Group, 2008). To this end, there is the need to provide egress systems such as fire escape elements in the form of stairs to facilitate exiting from buildings. Fire escape stair is a continuous, unobstructed, path of escape used when traversing a building vertically in case of fire (McGraw Hill Dictionary of Architecture and Construction, 1993) There are various students housing on KNUST campus comprising the six traditional main Halls of Residence and other modern Halls of

50 Botchway and Boatemaa-Oti Residence (Table1). Currently, the vertical circulation in the multi-storey blocks of KNUST comprises of non-functional lifts and flights of stairs serving huge numbers of occupants. This study will analyse the egress system of residential Types B (1) and C (1) as shown in Table 1. Multiple occupation structures like the multistorey blocks on KNUST campus have the risk of fires breaking out because of overloaded electrical circuits which is a factor created by increasing student population and occupancy (Renewals Team, 2007; Chalmers Insurance Group, 2010). In the event of fire, evacuation as a first step is necessary as it ensures that occupants of a building reach a place of ultimate safety outside the building (British Standards Institution Group, 2008; Fire Officer, 2009; Richardson, 2009). When there is ignition and fire begins to spread, safe evacuation must be completed within the initial stages of fire growth (C and D) as indicated in Fig.1. Late evacuation (E) has to be done quickly to avoid fatalities. Stairs - Majority of accidents occur on escape routes due to incorrect sizes and differences of stair components, especially, treads and risers. As little as 5mm difference in riser heights can be disastrous (British Standards Institution Group, 2008). The clear width of stair stated as at least 1200mm may be subject to change according to the total number of occupants on each floor (see Fig. 2 and 3). In calculating the width for a number of people, 530mm should be the unit width for each occupant. The product of the unit width, 530mm, and the number of people should dictate the exact width of stair on each floor. However, if the population on each floor is scanty and the product is less than the standard stated above, then 1200mm should be used. On the other hand, if the product of 530mm and the population is more than the standard stated, the result which is greater than 1200mm should be used (British Standards Institution Group, 2000; 2008; Ministry of Works and Housing, 1996). Table 1: Student housing typologies on KNUST campus Typology Type A Type B (1) Type B (2) Type C (1) Type C (2) Description Low rise modern Halls of Residence and all traditional main Halls. Number of floor levels is between 2 and 6. Comprises of SRC hostel, Tek Credit, GUSS Hostels, GRASAG Hostel, Steven Paris Hostel, Spring Hostel and Hall 7. High rise single banking blocks with one stair. Comprises of annexes of the main Halls: Republic Annex, Queens Annex and University Hall Annex. The blocks have 9 floor levels. High rise single banking block with 2 stairs. Comprises of Independence Hall Annex. The block has 9 levels. High rise single banking blocks with one stair. Consists of 2 multi-storey blocks of Africa Hall. The blocks have 9 floor levels. High rise double banking blocks with two stairs. Consists of 2 multi-storey blocks of Unity Hall. Blocks have 10 floor levels.

Egress system in multi-storey annexes... 51 O = Ignition A = Fire Detection B = Alarm C = Occupants aware of Fire/ Evacuation begins D = Evacuation of Life Safety Strategies Complete E = Escalation of Fire/ Danger Zone Fig. 1: Stages of fire growth and evacuation of occupants Source: British Standards Institution Group, 2008, p. 51; Patterson 1993, p11 Fig. 2: Typical floor plan of Halls of Residence showing width of stair and maximum travel distance Source: British Standards Institution Group, 2000, 2008 MATERIALS AND METHODS This study is aimed at auditing the existing condition of the egress system of multi-storey Halls of Residence on KNUST campus for a remedy that will safeguard the safety of occupants. The approach used in this paper involved an analytical and comparative study of selected multi-storey blocks comprising Republic Hall, Independence Hall, Africa Hall Block B and Queen Elizabeth Hall Annexes. Standard egress data were gathered from the British Standard Codes. Data on the egress system was recorded through measured drawings

52 Botchway and Boatemaa-Oti A = Clear width of stair (at least 1200mm) B = Maximum travel distance from remote area (Maximum 14000mm) C = Space between balusters/ rails (Maximum 200mm) D = Height of handrail (1100mm) E = Headroom (At least 2000mm) F= height (100 to 190 mm uniform risers) G= length (250 to 350 mm uniform treads) H= Angle of stair (Pitch) in degrees (Maximum 38 degrees) Fig. 3: Typical elevation showing components of stairs Source: British Standards Institution Group, 2000, p.3 conducted at each Hall of Residence to obtain the floor plans and stair components dimensions. Type B (1) and C (1) Residences studied have similar configurations thus, similar floor plan and section (Fig. 4 and Fig. 5). On a typical floor of each block, there are twelve (12) rooms, each with four (4) occupants (Fig. 4). The existing stair on the floor serves all the occupants on the floor and will also double as an escape stair in times of fire. Apart from (Fig. 4 and Fig. 5), the following stair components dimensions were also recorded for further discussion; width of stair, maximum travel distance to stair, space between balusters, height of handrail, headroom, riser height, tread length and pitch of stair. The recorded stair data were documented and each component s dimension compared with standard measurements (see Fig. 2 and 3). RESULTS AND DISCUSSIONS The chosen study areas comprise the following Halls of Residence and data about their past and current population (Table 2). Before the analysis, the occupancy growth of the study areas was computed to determine whether the existing stair qualities are appropriate for the current population as shown in Table 2. From Table 2, the number of rooms has not increased since their establishment but there has been a 300% increase in mean occupancy. This would put the circulation and egress system of the Halls in a critical condition. From Table 3, each Hall of Residence has one (1) stair on which all occupants commute and also doubles as an escape stair implying that there is basically one stair case provided for the entire block. The dangers associated with this condition have to be critically considered. Documentation and Analysis of Stairs of Study Areas The Annex blocks of the Main Halls have similar designs and spatial arrangements but different egress qualities. The auditing of the blocks is based on standard requirements for fire escape stairs which have been detailed in Fig. 2

Egress system in multi-storey annexes... 53 Fig. 4 Typical floor plan of type B (1) and Type C (1) annex blocks Fig. 5: Typical cross-section of Type B(1) and Type C(1) annex blocks and 3. Each floor has 12 rooms housing 48 occupants. The resulting dimensions of the existing stair components have been recorded in Tables 4 to 11. Analysis of stair components Using a comparative analysis approach, each stair component recorded was compared with the standard value as seen from Table 4 to Ta- ble 11. Any existing dimension that was not consistent with the standard was then classified inadequate or unacceptable indicating that the particular component is not safe enough to guard occupants to safety. However, measured values that corresponded with the standard values are safe components for egress thus acceptable. Clear Width of Stair - From Table 4, the

54 Botchway and Boatemaa-Oti Table 2: Occupancy growth of multi-storey blocks of Study Areas [Type B (1) and C (1)] Typology Type B (1) Residential Block Number of Rooms Year Occupied by Students Initial Occupancy Current Occupancy (2012) Queens Hall Annex 96 1959 96 384 300 Republic Hall Annex 96 1961 96 384 300 Average% Increase Over the Years University Hall Annex 96 1961 96 384 300 Type C (1) Africa Hall (Block B) 96 1967 96 384 300 Source: (KNUST Estate Office, 2012) Table 3: Standard required escape routes versus existing stairs in the Halls of Residence (For population between 200 and 400) Standard No. of Escape Routes Typology Residence Existing Population (2012) Existing Number of Stairs Comment at least 2 B (1) Queens Hall Annex 384 1 Inadequate Republic Hall Annex 384 1 Inadequate University Hall Annex 384 1 Inadequate at least 2 C (1) Africa Hall Block B 384 1 Inadequate Source: British Standards Institution Group, 2008, p.70; Patterson, 1999, p.195 Table 4: Clear Width of Stair (mm) Standard clear width ( 1200mm) Hall Existing width of stair Comments Queens 946.8 Inadequate Republic 918.8 Inadequate University 954.6 Inadequate Africa (Block B) 934.2 Inadequate

Egress system in multi-storey annexes... 55 Table 5: Maximum travel distance from remote area (Dimensions in millimetres) Standard distance ( 14000mm) Hall Travel Distance (mm) Comments Queens 21783 Unacceptable Republic 19720 Unacceptable University 19720 Unacceptable Africa (Block B) 14420 Unacceptable Table 6: Space between Rails (mm) Standard space between rails ( 200mm) Hall Existing space between rails Comments Queens 465.8 Unacceptable Republic 445.8 Unacceptable University 390.6 Unacceptable Africa (Block B) 480 Unacceptable Table 7: Height of handrail (mm) Standard height of handrail ( 1100mm) Hall Existing handrail height Comments Queens 978 Inadequate Republic 831.2 Inadequate University 923.8 Inadequate Africa (Block B) 954.8 Inadequate Table 8: Headroom (mm) Standard headroom ( 2000mm) Hall Existing space between rails Comments Queens 2286.5 Acceptable Republic 2363 Acceptable University 2288.3 Acceptable Africa (Block B) 2346.7 Acceptable

56 Botchway and Boatemaa-Oti Table 9: Existing riser heights on fifth flight in each Hall (mm) Standard size (100 to 190 mm uniform risers) Hall 1 2 3 4 5 6 7 8 Comments Queens 203 174 170 176 168 168 177 167 Unacceptable Republic 168 159 180 168 168 177 169 177 Unacceptable University 169 168 174 173 174 174 169 160 Unacceptable Africa (Block B) 178 166 173 175 173 172 172 125 Unacceptable Table 10: Existing treads dimensions on fifth flight in each Hall (mm) Standard size (250 to 350 mm uniform tread) Hall 1 2 3 4 5 6 7 Comments Queens 275 274 269 269 270 268 268 Unacceptable Republic 270 268 270 270 274 276 277 Unacceptable University 284 280 281 284 282 280 282 Unacceptable Africa (Block B) 276 278 279 275 274 274 269 Unacceptable Table 11: Pitch of stair (degrees) Standard Pitch ( 38 degrees) Hall Existing pitch of stair Comments Queens 32.7 Acceptable Republic 31.6 Acceptable University 30.9 Acceptable Africa (Block B) 33.2 Acceptable

existing value of each Hall when compared to the standard clear width as seen (Fig. 2 and 3) are inadequate. This indicates the inadequate widths will be an ingredient for bottlenecks on each flight as depicted in Fig. 6 and Fig. 7 (indicated in dotted circles). The bottlenecks that will occur due to the narrow width of the stair will extend to the landings and could finally cause an obstruction. As can be seen in Fig. 6 and Fig. 7, constrictions will be complicated on the ground floor as people moving from the sub-basement will meet the cumulative total number of occupants descending the stairs. As seen in dotted circle in Fig. 6, there will be a confluence of people at the threshold of the tunnel. Travel Distance - All the Annex blocks do not meet the standard travel distance as seen in Table 5. Occupants from remote parts of each floor will have to travel more than 14000mm to reach the stair. In Fig. 7, occupants in rooms 1 to 4 will travel beyond 14000mm to access the stair in order to evacuate. This could cause a lot of harm to occupants as they will spend a lot more time travelling to the exit point in the building with fire and smoke. Egress system in multi-storey annexes... On the other hand, when an escape stair is provided at the extreme end of the block as indicated in Fig. 8 (in dotted circle), occupants will be ushered out in two directions and this will prevent bottlenecks on the stairs (Fig. 6 and 7) and reduce travel time for evacuation. Space between Rails - From Table 6, the existing rail spacing as recorded are greater than the standard 200mm, thus unacceptable to aid occupants to safety. As depicted in Fig. 9, introducing guardrail 2 (shown as continuous line) will reduce the wide gap between the rails to prevent casualties. Handrails and guards are very important in egress as they provide support and guide for users of the stair. Circular handrails with a diameter between 32 and 50mm are most comfortable to grasp (British Standards Institution Group, 2000). Handrail height - All the existing handrail heights in the Halls of Residence (Table 7) are lower than the standard height (1100mm). This makes their heights inadequate to aid occupants during evacuation. The existing 57 Fig 6: Typical section through multi-storey annex blocks (Section A-A)

58 Botchway and Boatemaa-Oti Fig. 7: Typical floor plan of type B (1) and Type C (1) blocks showing existing stair (All dimensions in millimetres) Fig. 8: Typical plan showing fire escape stair attached to existing blocks handrail heights can be increased by a 130mm additional to provide total support for occupants as depicted in Fig. 9. Headroom - From Table 8, 2000mm is the least height for headroom as suggested by British Standards Institution Group. The existing average headroom of each Hall is higher than the minimum value (2000 mm). This means that all existing headroom of the Annex blocks are safe for occupants as accidents will not occur from collision into the under parts of other flights of stairs. s and s - Uneven risers and treads are major causes of accidents on stairs. Apart from risers and treads falling within the standard range as recorded in Tables 9 and 10, it is also important for their dimensions to be uniform throughout the flight as indicated in Fig. 9. The inconsistency of the treads and risers in the Halls of Residence makes them unacceptable. Pitch - From Table 11, all recorded measured values of the pitch of each Hall of Residence is acceptable. Each of the pitch is not steep

Egress system in multi-storey annexes... 59 Fig. 9: Typical section B-B through stairs showing existing and proposed components CONCLUSIONS AND RECOMMENDA- TIONS Safety measures in the multi-storey blocks have been undermined looking at the inadequacy of fire preventive measures such as the absence of fire equipment and the non-provision of a fire escape stair. The only means of circulation, which is the stair, is over utilized due to the increasing number of occupants in the multistorey Halls of Residence. The principal remedy is the provision of a fire escape stair at the extreme end of the blocks to aid easy movement and smooth egress out in times of emergencies as has been illustrated. The addition of an extra stair will facilitate egress from the blocks and this is a prime factor that will improve the safety conditions in the multi- storey Annex blocks of all the Halls of Residence. The construction inaccuracies of the existing stair can be corrected by using screed. This will make the existing stair functional; acting as an alternative fire escape stair and a means of ver- tical circulation. Though the stairs are made of concrete, non-slip aggregate treatment should be further introduced on the individual treads as well as the landings to prevent possible slipping. The University in addition to this bears the responsibility of conducting periodic checks on fire safety conditions in the Halls of Residence as the occupancy situation changes. This will have to be carried out by the Fire Safety Department of the University to ensure total safety of occupants and that of properties as well. ACKNOWLEDGEMENTS The Authors are grateful to the staff of Kwame Nkrumah University of Science and Technology (KNUST) Development Office for their assistance in the acquisition of the layout of the Halls of Residence. The Authors also acknowledge with appreciation the assistance of KNUST Fire Department and Ghana National Fire Service, Kumasi for the fire safety knowledge shared with them.

60 Botchway and Boatemaa-Oti REFERENCES British Standards Institution Group (2000). British Standard codes 5395. [E-book] London: British Standards Institution. Available at: http://www.4shared.com [Accessed 3rd July, 2010]. British Standards Institution Group (2008). British Standard codes 9999. [E-book] London: British Standards Institution. Available at: http://www.4shared.com [Accessed 3rd July, 2010]. Chalmers Insurance Group (2010). A report on Electrical Current. [pdf] Maine: MMG Ins u r a n c e A v a i l a b l e a t : h t t p : / / www.chalmersinsurancegroup.com/assets [Accessed 18 th July, 2010]. Fire Officer (2009). Disability Emergency Egress and Evacuation Issues or Policy, Fire Safety Technical Guide. [pdf] London: University College of London. Available at <http://www.ucl.ac.uk/efd/maintenance/ fire/.../uclfire_tn_008.pdf>. [Accessed 29 th July, 2010]. Kwame Nkrumah University of Science and Technology Estate Office (2012). Students Halls of Residence. [online] K.N.U.S.T., Kuma si. Available at <http:// www.knust.edu.gh>. [Accessed 2 nd July, 2010] McGraw Hill Dictionary of Architecture and Construction (1993). Available at <http:// www.answers.com/topic/fire-escape>. [Accessed 23 rd August, 2012] Ministry of Works and Housing (1996).Ghana National Building Regulations (L.I.1630). Accra, Assembly Press. National Institute of Standards and Technology (2010).E-handbook of Statistical Methods. [E-book] Gaithersburg: U.S. Commerce D e p a r t m e n t. A v a i l a b l e a t http:www.itl.nist.gov/div 898/handbook>. [Accessed 11 th August, 2010]. Patterson, J. (1993). Simplified Design for fire safety, New York: John Wiley and Sons Inc. Renewals Team (2007). Fire precautions for houses in multiple occupation. [pdf] Bideford: Torridge District Council. Available at < h t t p : / / w w w. t o r r i d g e. g o v. u k / CHttpHandler.ashx?>. [Accessed 2 nd July, 2010] Richardson, K. (2009). Fire Safety in High Rise Apartment Buildings. [E-book] Atlanta: ASHRAE Publication. Available at <http:// www.cmhc.ca/fire-safety-in-high-rise- Apartment-Buildings. [Accessed 2 nd August, 2010].