TENANT DESIGN MANUAL UPDATED FEBRUARY 2017

Similar documents
TENANT DESIGN MANUAL UPDATED OCTOBER 2016

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED FEBRUARY 2017

TENANT DESIGN MANUAL UPDATED JANUARY 2016

TENANT DESIGN MANUAL UPDATED OCTOBER 2016

TENANT DESIGN MANUAL UPDATED MAY 2016

TENANT DESIGN MANUAL UPDATED JUNE 2016

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JULY 2016

TENANT DESIGN MANUAL UPDATED AUGUST 2016

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED AUGUST 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED DECEMBER 2018

TENANT DESIGN MANUAL UPDATE JUNE 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

PLAZA WEST COVINA TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

LOUIS JOLIET MALL TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

SOUTHLAKE MALL. Southlake Mall Tenant Design & Construction Criteria TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

The Promenade at Casa Grande 1005 N Promenade Pkwy Casa Grande, AZ 85294

14400 Bear Valley Road, Victorville, CA 92392

FRANKLIN PARK MALL TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

San Tan Village 2218 E. Williams Field Rd. #235, Gilbert, AZ 85295

TECHNICAL CRITERIA ARROWHEAD TOWNE CENTER THE PLACE TO SHOP

Tenant Design Criteria Section t Technical Criteria Updated: August Wilton Mall at Saratoga 3065 Route 50, Saratoga Springs, NY 12866

TECHINICAL CRITERIA DEPTFORD MALL THE PLACE TO SHOP

a) Tenant shall require its Contractor to provide and maintain the following insurance coverage:

TENANT DESIGN CRITERIA V. Technical Criteria 34

General Information RETAIL AND RESTAURANT

GENERAL INFORMATION. Landlord s Tenant Coordinator

th Street Boulder CO 80301

FOR LEASE. Capitol Hill Corner Cafe/Restaurant Space th Avenue, Seattle, WA Please call brokers for more information:

TECHNICAL CRITERIA THE PLACE TO SHOP THE SHOPS AT ATLAS PARK

8000 Cooper Avenue, Glendale, NY 11385

Construction Document Criteria

TWELVE OAKS GENERAL INFORMATION (BUILDING E ONLY)

DESCRIPTION OF LANDLORD'S WORK & TENANT'S WORK

3435 MAIN 3435 Main Street Kansas City, MO RESTAURANT SPACE Available for Lease 1. BUILDING LOCATION

TWELVE OAKS GENERAL INFORMATION (BUILDINGS A, B, C, and D ONLY)

Tenant Design Criteria Section rd Restaurant Design Criteria Updated: June E. Camelback Road, Scottsdale, AZ 85251

The Shops at Montebello Montebello Town Center Dr, Montebello, CA 90640

Submission Procedures

E x p a n s i o n P r o j e c t

Restaurant Addendum to Tenant Construction and Design Criteria. Restaurant Criteria. Replace Existing Tenant

CHARLESTON PLACE TENANT CALCULATION CHECK/DATA TABULATION SHEET(S) Forms must be completed by the Tenant's Mechanical or Electrical Engineer.

CHAPTER 1321 Permit and Inspection Fees

Bangor Mall Bangor, ME

LANDLORD WORKLETTER EXHIBIT C-1 CONSTRUCTION REQUIREMENTS AND STANDARDS GREY SHELL ONLY

Construction Document Criteria

Construction Document Criteria

Fee Type How Determined Rate Permit Processing Charge Flat Permit or Plan Review Submittal $32.00

TECHNICAL CRITERIA THE PLACE TO SHOP LOS CERRITOS CENTER

Construction Document Criteria

FAIR OAKS GENERAL INFORMATION

TENANT MANUAL 5 January 2006

RENTER'S INSPECTION WORKSHEET Free form provided at

EXHIBIT C. Leasehold Improvements Work Letter

CONSTRUCTION CRITERIA

COLD DARK SHELL LEASE EXHIBIT

CONSTRUCTION CRITERIA

Coconut Point (Community Center) Estero/Bonita Springs, Florida

THE BAY STREET STORY. Page 1 of 32

Design and Construction Document Criteria

Exhibit C - Shops 1 & 2

TENANT DESIGN MANUAL. February 27, 2015

TENANT DESIGN MANUAL JANUARY, 2018

THE PLACE TO SHOP CHANDLER FASHION CENTER

M001 EAGLECREST LEARNING CENTER CITY & BOROUGH OF JUNEAU. Inc. CBJ CONTRACT No. E SYMBOLS FAN SCHEDULE HEATING COIL SCHEDULE EQUIPMENT SCHEDULE

OBTAINING A CERTIFICATE OF OCCUPANCY FOR UNAPPROVED DWELLING UNITS

GRAND CENTRAL TERMINAL NEW YORK, NY MECHANICAL, ELECTRICAL AND PLUMBING TENANT DESIGN CRITERIA HANDBOOK

City of Oregon City. Community Development Building Division Fee Schedule Effective April 1, 2016 BUILDING DIVISION

Procedures on Maintenance Services and. Required Inspections for the ADR Tenants. Seattle Tacoma International Airport.

AIRPORT DINING & RETAIL PREVENTIVE MAINTENANCE PROGRAM MANUAL

THE PLACE TO SHOP TOWNE MALL

Theodore Roosevelt High School 3436 W Wilson Ave Chicago, IL 60625

GREATER HARTFORD TRANSIT DISTRICT GHTD RFP # LEASE OF RETAIL SPACE, UNION STATION. ADDENDUM #2 Issued November

Summary of Oregon Home Inspector Certification Law (ORS 701) and Standards of Practice for Home Inspections

No Surprises: What You Need to Know About the TPRs and Cost Segregation. Trent Baeckl, CPA Tax Senior Manager

MERRILLVILLE CORPORATE CENTER BUILDING FACTS & AMENITIES

BUI L DIN G A ND E L E V A T O R F E ES

APPENDIX A BUILDING PERMIT AND RELATED FEES

ANCHOR SPACE FOR LEASE Civic Square Shopping Center W. El Camino Real Sunnyvale, CA 94087

CHAPTER 4 LIGHT, VENTILATION & OCCUPANCY LIMITATIONS

TRIALLIANCE COMMERCIAL REAL ESTATE SERVICES COLUMBIA STATION Route 108, Old Annapolis Road Columbia, MD 21045

Fort Myers, FL USA. Client Name Client Test

Herriman & Associates, Inc. Website Various service forms mentioned in this letter are available on our website,

Transcription:

TENANT DESIGN MANUAL UPDATED FEBRUARY 2017

PROJECT OVERVIEW Pier Park is an approximately 1.1 million square feet combination town/ community/lifestyle center located in the heart of Panama City Beach between US 98 and Front Beach Road at Powell Adams Road and Pier Park Drive. 2

PROJECT OVERVIEW Pier Park is a Simon Mall and is the premier shopping destination for the Panama City market and the entire Emerald Coast. Pier Park features over 1 million square feet of open-air regional lifestyle shopping, providing unique retailers, tourist attractions, and dining options. Pier Park is anchored by Dillard s, JCPenney, Target, Grand Theatres, Ron Jon Surf Shop, Margaritaville, Marshalls, Forever 21, and Dave & Buster s. 3

TENANT INFORMATION PACKAGE The Tenant Information Package (TIP) is intended to provide you with the project s design and construction criteria and consists of several parts: COMPONENT TIP Index Tenant Design Manual Kiosk Design Manual Architectural Criteria MEP/FP Criteria Bulletins DESCRIPTION Will provide a comprehensive list of topics to help locate information Provide mall specific architectural, sign and engineering design criteria Outline submission requirements and will provide necessary guidelines to design your store. (same as Architectural Criteria) 4

TENANT INFORMATION PACKAGE The Tenant Information Package can be accessed from Simon s website simon.com.» Select the business header, search for the property name, click on the Tenant Info Package link on the right side of the page.» If you have any difficulties working with the website, please contact your Tenant Coordinator. *For questions regarding the Landlord s design and construction requirements, please contact your Tenant Coordinator or call 317-636-1600 and ask for Tenant Coordination. 5

MALL BUILDING DATA Occupancy/ Use: Construction Classification: Building Levels: Sprinkler System: Mixed Use M, A2, B Type IIB One (1) Level Fully Sprinkled *Site Plan and Leasing Plan available for Tenant s to use on Simon.com. Select the business header, search for the property name, click on links on right side of page. 6

STOREFRONT ZONE PLAN 7

LIFESTYLE ELEVATION Tenant sign type and location is subject to approval of Landlord s Tenant Coordinator Modification of storefront glass and mullions must be approved by Landlord s Tenant Coordinator 8

BUILDING A-2 9

BUILDING A-2 ELEVATIONS A-B 10

BUILDING A-2 ELEVATIONS C-D 11

BUILDING A-2 ELEVATIONS E 12

BUILDING B 13

BUILDING B ELEVATION A 14

BUILDING B ELEVATION B-D 15

BUILDING B ELEVATION E-G 16

BUILDING B ELEVATION H & J 17

BUILDING C 18

BUILDING C ELEVATION A 19

BUILDING C ELEVATION A (CONTINUED) 20

BUILDING C ELEVATION B 21

BUILDING D 22

BUILDING D ELEVATION A 23

BUILDING D ELEVATION A (CONTINUED) 24

BUILDING D ELEVATION B-C 25

BUILDING E 26

BUILDING E ELEVATION A 27

BUILDING E ELEVATION B-C 28

BUILDING E ELEVATION D-E 29

BUILDING F-1/ F-2 30

BUILDING F-2 ELEVATIONS 31

BUILDING F-2 ELEVATIONS 32

BUILDING G-1 33

BUILDING G-1 34

BUILDING G-2 35

BUILDING G-2 36

BUILDING G-3 37

BUILDING H-1 38

BUILDING H-3 39

BUILDING J 40

BUILDING J 41

BUILDING K 42

BUILDING K ELEVATION C ELEVATION B B A E C D ELEVATION A 43

BUILDING K ELEVATION C (CONTINUED) ELEVATION D 44

BUILDING K ELEVATION E 45

ADJACENT MARINE ENVIRONMENT The Center is adjacent to the Gulf of Mexico, and, as such, is subject to certain regulations and permits that protect the adjacent marine environment, including without limitation a development permit issued to The St. Joe Company, as predecessor in interest to Landlord, by the City of Panama City Beach under Permit Number 199900907 (IP- KDO), as recorded in the books of the Office of Recorder, County of Bay, State of Florida and Florida s Marine Turtle Protection Act [Section 370-12(1), Fla. Stat (2001)] and the Model Lighting Ordinance for Marine Turtle Protection (Rule 62B-55.006.F.A.C). In addition to local authorities, the Florida Fish and Wildlife Conservation Commission (FWCC), Office of Protected Species Management (OPSM), and the U.S. Fish and Wildlife Service (FWS) have jurisdiction over the development. Of primary concern is lighting of Tenant s storefront signage, light emanating from the Premises and the overall night sky glow of the Center. To reduce the overall night sky glow, Landlord requires the following: (1) all storefront signs to be goose-neck lighted, with lamps facing downward using bulbs specified by Landlord; (2) Tenant may not operate with its doors standing open between dusk to dawn each night; and (3) the use of turtle glass, which is glass with a visible light transmittance of 45% or less in the visible spectrum (400 to 700 nanometers). Specifications of both the sign lighting and turtle glass will be included in the Tenant Information Package. Landlord makes no representations or warranties that Tenant s conformance to the above standards will cause Tenant s Plans to be approved by the authorities having jurisdiction over the Center and the Premises, and Landlord assumes no responsibility for the conformity with applicable laws and regulations. Tenant shall indemnify and hold Landlord harmless from and against any and all losses, costs, damages or claims of whatever nature (including without limitation reasonable attorney s fees and costs of any kind) arising out of or in connection with such compliance. 46

STOREFRONT SIGNS, AWNINGS & CANOPIES 47

BLADE SIGNS 48

HVAC RETAIL TENANTS This is an open air mall. Engineer is required to accommodate conditions that may affect the performance of the HVAC system for their store. Equipment Individual packaged rooftop units shall be designed in accordance with ASHRAE requirements and the criteria set forth in the Landlord s MEP Criteria Drawings included in the Tenant Information Package. Condensate Drain Condensate to be piped from rooftop unit through curb to approved sanitary connection within space. Drains and trap should be copper. Condense trap should be at a depth sufficient to overcome positive/negative static pressure of fan (3 minimum) Outside/Relief Air Economizer and barometric or fan powered relief through Tenant installed components. Return Plenum (Ducted return is for odor producing Tenants only and subject to Landlord approval). Exhaust/Relief None required. Toilet Exhaust By Tenant including fan, ductwork and roof cap. Odor, Thermal & Process Equipment Exhaust Size for application by Tenant. Temperature Controls Stand-alone digital electric/electronic control system by Tenant. Test & Balance Tenant shall employ a TAB, NEBB or AABC Certified Air Balance Contractor to perform final testing and balancing. See Criteria Sheet MEP-1 for further information. 49

PLUMBING RETAIL TENANTS Water Domestic water shall be available either directly from the local utility company or Landlord redistributed system. The Tenant shall be responsible for coordinating available capacity, pressure, service connection, utility meter instillation, etc., with the utility. Waste 4 wye connection off Landlord main. Designated connection point within or adjacent to space. Vent Utilize existing connection or Tenant to install new. Grease Waste Code-approved grease interceptors must be installed to prevent grease-laden waster from entering the sanitary waste system. Interceptors located within a space must be surface-mounted above the floor (if permitted by code or jurisdiction.) Larger interceptors may be located outside the building. Coordinate with the Landlord to determine the allocated area for interceptor, routing or piping and the extent, if any, of existing provisions. Natural Gas Utility service available at central meter locations. All work by Tenant including meter if not existing. Toilet Rooms As required by code. Drinking Fountain Per code and ADA requirements. Service Sink As required by code. See Criteria Sheet MEP-1 for further information. 50

FIRE PROTECTION RETAIL TENANTS Implementation Tenant shall directly employ the Landlord designated contractor to install and/or modify existing grid or utilize connection provided. Tenant Flow Switch Not permitted. Valve for Tenant Space Not permitted. See Criteria Sheet MEP-1 for further information. 51

ELECTRICAL RETAIL TENANTS Voltage 120/208 and 277/480, 3ph, 4-wire Landlord Equipment Exterior cable busway with meters and fusible switches or interior metering boards. Minimum 2 empty conduit. Power Provided by Landlord redistribution system. Tenant to provide disconnect, fusing, meter and conductors and connect to Landlord distribution board (if not existing). Metering Reuse existing or provide new per Landlord specification. Capacity TENANT MAXIMUM ALLOTMENT IS 20 WATTS PER SQUARE FOOT. Submit connected and demand electrical load data to support electric service size requested. Telephone 3/4 minimum conduit with pull wire to designated connection point in central locations. Fire Alarm Interface with Landlord system is only permitted when the Tenant occupancy requires a system to meet Code. If required by Code, Tenant to provide required panel and devices compatible with Simplex 4100 system. Duct detectors to shut down RTU equipment to be annunciated within Tenant space only. See Criteria Sheet MEP-1 for further information. 52

HVAC FOOD TENANTS This is an open air mall. Engineer is required to accommodate conditions that may affect the performance of the HVAC system for their store. Condensate Drain Condensate to be piped from rooftop unit through curb to approved sanitary connection within space. Return Ducted (Plenum return is for non-odor producing Tenants only and subject to Landlord approval). Smoke Exhaust/Relief None required. Odor, Thermal & Process Equipment Exhaust Size for application by Tenant. Grease Exhaust Per code. Protect roof with Grease Guard containment system. Exhaust Replacement Air Draw from Common Area for thermal exhaust (3,000 SCFM) and process exhaust (up to 5,000 SCFM). Thermal Exhaust 3,000 SCFM MAX through thermostatically controlled damper registers, duct extension and sensor installation by Tenant. Kitchen and Process Equipment Exhaust Size for application by Tenant. Utilize exhaust only system up to 5,000 SCFM. Toilet Exhaust By Tenant including fan, ductwork and roof cap. Temperature Controls Stand-alone digital electric/electronic control system by Tenant. Thermal exhaust sensor installation by Tenant. Test & Balance Tenant shall employ a TAB, NEBB or AABC Certified Air Balance Contractor to perform final testing and balancing. See Criteria Sheet MEP-1 for further information. 53

PLUMBING FOOD TENANTS Water Redistributed by Landlord via overhead mains. Minimum 1 1/2 valved connection. Tenant supplied check meter w/remote reader. Waste 4 connection off Landlord main. Designated connection point within or adjacent to space. Vent Through roof by Tenant or connect to existing. Grease Waste Landlord has provided central grease interceptor with 4 wye connection to each Food Court Tenant. Natural Gas Gas is available from the utility at exterior pipe and regulator connection if not existing. Provide automatic gas shut off valve. Toilet Rooms Per code. Drinking Fountain Per code. Service Sink Consult with Health Department for specific requirements. See Criteria Sheet MEP-1 for further information. 54

FIRE PROTECTION FOOD TENANTS Implementation Tenant shall directly employ the Landlord designated contractor to install and/or modify existing grid or utilize connection provided. Tenant Flow Switch Not permitted. Valve for Tenant Space Not permitted. See Criteria Sheet MEP-1 for further information. 55

FIRE PROTECTION FOOD TENANTS Voltage 277/480, 3ph, 4-wire Landlord Equipment Distribution metering switchboards with switches and meters. 4 conduit minimum. Power Provided by Landlord redistribution system. Tenant to provide fusing, meter (if not existing), conductors and connect to Landlord distribution board. Metering Reuse existing or provide new per Landlord specification. Capacity FOOD COURT TENANT MAXIMUM ALLOTMENT IS 100 WATTS PER SQUARE FOOT. Submit connected and demand electrical load data to support electric service size requested. Telephone 3/4 conduit to designated connection point in central locations. Fire Alarm Connect hood extinguishing system to Landlord s Simplex 4100 system. Connection to system to be by Landlords designated vendor. Duct detectors to shut down RTU equipment and be annunciated within Tenant space. See Criteria Sheet MEP-1 for further information. 56

MEP CALCULATION FORMS Tenant s Engineer shall use their own form for HVAC Load Calculations: Appliance Heat Gain Electrical Load Summary Kitchen Exhaust Fan Specifications Kitchen Make-up Air Unit Specification RTU/Split System Specification Maintenance 57