Student Residential Accommodation Standard Design Guidelines August 2017

Similar documents
Student Residential Accommodation Standard Design Guidelines July 2016

MINIMUM HMO & HOSTEL STANDARDS

Common Areas and Building Finishes

Contents: Notes: Application:

Common Areas and Building Finishes

Contents: Notes: Application:

Apartment , Ver A

Access Statement The Hollies Ingram Road Bamburgh NE69 7BT

Common Areas and Building Finishes

Artist impression. 2 & 3 Bedroom Penthouses. 20 Galore St, CRACE, ACT 2911

HMO LICENSING STANDARDS FOR FACILITIES PROVIDED FOR SHARED AND EXCLUSIVE USE

TOURIST TRAFFIC ACTS Registration and Renewal of Registration Regulations for Hotels 2016

Property. Introduction

Common Areas and Building Finishes

LAKESIDE URBAN HOUSES

Welcome and Minimum Requirements Pages 3-4 Recommended Furniture Page 5 General Information Pages 6-7 Contact Information Page 8 Data Protection

Brighton & Hove City Council. Standards for Licensable Houses in Multiple Occupation

PROPERTY CONDITION CHECK LIST FOR A LICENCED HMO

Artist impression. 2 Bedroom Apartments. 20 Galore St, CRACE, ACT 2911

Facilities providing accommodation for the public (e.g. Hotels, hostels, guesthouses, self catering apartments).

Access Statement Henderson House 19 Henderson Street Amble NE65 0AE

Property. Introduction

Parking. Access Statement Summerhouse Cottage Beadnell. Pre Arrival. Chathill-3.5 miles/ Alnmouth-15 miles/ Berwick upon Tweed-25 miles

ACCESS STATEMENT FOR the Byre AT BIRLING NORTH COTTAGE. Pre-Arrival. Parking. the East Coast Main Line is approximately 4km to the north.

National Trust Cottages Access

Give the name and distance of the nearest railway station. Describe the floor surface e.g. tile/wood/rugs/carpet (thick/short pile).

Access Statement for Helios, 3 The Spinnakers, Valley Road, Carbis Bay

Access Statement Seaton 22 St Aidan s Seahouses NE68 7SS

1 Star Hotel Classification Assessment Form

Proposed Variation No. 5 (Student Accommodation) to the Cork City Development Plan April 16 th 2018

Kitchen 5m² 6m² 7m² 9m² 11m² Total communal living space** 13.5m² 17m² 18m² 20m² 27.5m²

SPECIFIC GUIDANCE FOR A BEDSIT TYPE HOUSE IN MULTIPLE OCCUPATION (HMO)

Access Statement for Bryn Barn Bed and Breakfast

Give the name and distance of the nearest railway station. Describe the type of surface from the car park to the main entrance.

Access Statement Aidanfield Fenwick Berwick upon Tweed TD15 2PJ

Lauder, Scottish Borders

Jurys Inn Nottingham. Property. Introduction. Pre-Arrival

Lantern House - holiday cottage in the Cotswolds UK Access Statement

ACCESS STATEMENT FOR THE HEMMEL

Access Statement for Stoney Steps Flat 5 Ullswater Court Inn on the Lake Glenridding

TOURIST TRAFFIC ACTS Registration and Renewal of Registration Regulations for Hotels 2003

172 Railway Parade, WEST LEEDERVILLE. Marketing Plans for VIP clients only

For more information contact Ian Turner

Give the name and distance of the nearest railway station. Describe the streets in the area surrounding the property

Access Statement for Lorne House Bed & Breakfast

LEGEND. A Apartments. T Townhouses

National Trust Cottages Access Statement

Access Statement for Primrose Farm

National Trust Cottages Access Statement

Oakdale, Sully Road Penarth CF64 2TQ. 665,000 Freehold

Harmony Row Dublin 2. Dublin 2

Plasterboard and paint finish to Architect s detailed design Common areas and car parking levels as required by Building Code of Australia (BCA)

GUIDELINES TOURIST RESIDENCE

HOUSES IN MULTIPLE OCCUPATION Standard Guidance. Houses in Multiple Occupation Standards Guidance

National Trust Cottages Access Statement

Lynwood Church Street St. Mary's Isles of Scilly TR21 0JT

Utopia Gymnastics Accessibility Guidance. Utopia Gymnastics

TOURIST TRAFFIC ACTS REGISTRATION AND RENEWAL OF REGISTRATION REGULATIONS FOR HOLIDAY COTTAGES 2007

National Trust Cottages Access Statement

National Trust Cottages Access Statement

Spacious 4 Bedroom Detached Family Home

Student Accommodation Services (SAS) is a joint venture between Residential Services

The Lodge Guest House

National Trust Cottages Access Statement

National Trust Cottages Access Statement

National Trust Cottages Access Statement

1. Budget Only you can decide. 2. Shop Around. 3. Design Leave that to us! Thank you for enquiring with In House Granny Flats!

RESIDENCES EFFORTLESS LUXURY IN ONE OF CANBERRA S MOST PRESTIGIOUS SUBURBS BY VILLAGE BUILDING CO. 15 CURLEWIS CRESCENT GARRAN

Penthouses. Apartment 8

Hotel Accessibility Pack

Sophia 6mx10m (60m2) Prefabricated 2BR + Bathroom & Kitchenette, 3 STAR Model $ 59,999

ACCESS STATEMENT FOR THE APARTMENT ALEXANDER S

SOPHISTICATED, RELAXED LIVING.

NEWBATTLE TERRACE MORNINGSIDE FLOORPLANS

Meticulously crafted finishes come as standard at Jade

FLAT ONE 2 bedrooms / 2 bathrooms First floor 748 sqft / sqm

FLOOR PLANS. One & two bedroom waterfront apartments & Penthouses, BRISTOL BRIDGE, BS1

10 Holm Village, Isle of Lewis, HS2 0AZ Offers over 210,000 are invited

Access Statement for Willow Nook Cottages

DESCRIPTION OF ACCOMMODATION. All the accommodation is either in the Main College Buildings or in the immediate neighbourhood.

McMillan Student Village Accommodation Information (2018/19)

q/., S Lt _ _.._--.

or FOR SALE

Offers around 325, Schomberg Avenue Belmont Belfast BT4 2JR. The Owner s Perspective:

2 Clifton Clifton, St Peter Port

Access Statement for Dellfield Self-Catering unit

Access Statement for the Cruik Barn cottage, in the grounds of Hause Hall farm, Martindale

Key Features Statement. Glades Bay Gardens OVERVIEW

Access Statement for Denzel 13 The Village, Watergate Bay, TR8 4AA, CORNWALL

40 GILLINGGATE, KENDAL, CUMBRIA Asking Price 395,000

Arriving and Getting In

6 CONTEMPORARY APARTMENTS IN AN ELEGANT VICTORIAN HOUSE

Access Statement for Cuckoo Croft Barn

La Bouverie Route de Cobo, Castel

YHA Oxford Access Statement

For more information contact Ian Turner

FREE ESTIMATE. How to: to complete these forms simply click the grey box and type your response.

Access Statement for Quality Guest Accommodation

A stunning range of 3 & 4 bedroom homes with stylish turnkey finish

Flat 5, Streets, Northgate, Louth, LN11 0LY 64,950

Transcription:

Student Residential Accommodation Standard Design Guidelines August 2017 Revision 05

1. Introduction 1.1. Objective The University s objective is to provide residential undergraduate student accommodation which enhances the student experience by delivering high quality living, social and amenity space: improving the living and learning experience when in residence. 1.2. Document Scope This document sets out the University of Chichester s design guidelines relating to student residential accommodation. These guidelines will be used as a benchmark against which to measure all new, and wherever practically possible, refurbishment and/or conversion schemes either on or off campus. The design guidelines apply to both internally and third party developed schemes. 1.3. General Requirements All rooms and layouts shall be of a workable design and comply with the express and implied terms and spirit of all legislation and/or regulations relating to these types of development. Where any conflict between these guidelines and any other relevant legislation and/or regulations occurs the provision shall comply with the higher standard. The University generally requires that developments shall include a minimum of 25% shared facility accommodation in order to offer choice to students. 1.4. University Approval For student accommodation schemes whereby the University has a direct or indirect contractual relationship, any and all deviations from the guidelines set out in this document must be approved by the University. For schemes where there is no contractual relationship, specific University approval would not be necessary, or appropriate, and this document only serves as a guide to the standards that the University seek to meet. The University actively encourages innovation and these guidelines shall be used as a benchmark in which to assess a proposed residential development scheme. 2. Regulations / Legislation 2.1. Building Regulations Designs must comply with all relevant sections of the current Building Regulations and associated Approved Codes of Practice. Any developments should also comply with any anticipated changes to all statutory regulations particularly in reference to fire safety including building cladding materials. Student Accommodation Standard Design Guidelines Rev05.docx Page 2 of 15

All development may be used for vacation accommodation to include conferences and summer schools etc. therefore specific consideration should be given to fire strategy (including travel distances) so that the accommodation is legally compliant for such residents. 2.2. HMO Regulations All developments which fall within the HMO standards criteria must comply with the guidelines and requirements stipulated by the local authority under whose jurisdiction the development falls. 2.3. ANUK/Unipol Code of Standards for Larger Residential Developments The University of Chichester manages its residential accommodation in accordance with the ANUK/Unipol Code of Standards for Larger Residential Developments 1 and therefore the requirements of this code, where appropriate, should be applied to all residential scheme designs. 2.4. Fire and Safety Fire detection and alarm systems should comply with BS 5839 to a category L1 standard and utilise multi use detector heads. A simultaneous evacuation strategy will be required such that should the fire alarm system activate, the whole block will evacuate. A phased/stay put strategy will not be acceptable. It is anticipated therefore that a secondary means of escape for all residents will be required. In line with British Standards manual call points will be required in each cluster flat and at each final point of exit from the building. The fire alarm system will be required to be linked to an approved 24 hour monitoring system such as RedCare. 2.5. Equality The design should fully comply with the requirements of the Equality Act 2010 and associated legislation. 2.6. Acoustics All floors and walls are to comply with the requirements set out in the latest Building Regulations. The performance levels for walls (party and bedroom) and floors should be agreed with the Local Authority Building Control or Approved Inspector but should not be of a lower standard than the values in Table 1 below. Airborne Sound insulation DnT,w + Ctr db (Minimum values) Impact Sound Insulation L nt,w db (Maximum values) Walls 45 n/a Floors & Stairs 45 62 Table 1. Acoustic Criteria 1 http://www.nationalcode.org/upload/file/nationalcode_edu.pdf Student Accommodation Standard Design Guidelines Rev05.docx Page 3 of 15

3. Development Size, Location and Proximity to Facilities 3.1. Size Where the University is providing operational management of the development it is expected that a minimum number of bedrooms will be needed to ensure efficiency and viability. Where the development is proposed to be off campus, and wholly independent of the campus, the minimum number which it is deemed viable is 200 bedrooms. However, clusters of smaller scale developments in close proximity to each other, that create a critical mass of 200 beds, or developments very close (within a 5 minute walk) to campus may have fewer beds. 3.2. Location Developments off campus should ideally be a maximum of fifteen twenty minutes walking time from the closest University campus. The walking route must be via a well lit populated area. Where developments are proposed at a further distance from campus, fully integrated transport options, reflecting the varying needs of the student population, must be proposed. This must include frequent day and night time bus services. A safe cycle route is also deemed essential. Locations where students have to cross very busy major roads are not likely to be favoured. 3.3. Proximity to Facilities Developments off campus must be in close proximity to facilities such as food shops, cafes and options for refreshment and entertainment etc. These facilities should be within a safe short walking distance if not immediately adjacent to or part of the development. 4. Accommodation Requirements This document covers four types of accommodation, en suite bedrooms in cluster flats, non en suite bedrooms in cluster flats Townhouses and Studio Rooms. Details of the requirements per type are set out in sections 4.1 to 4.5 below. Accessible laundry facilities should be provided on the basis of 1 washing machine and dryer to every 75 students. Facilities may be split across buildings or in a separate building and should ideally be located adjacent to entrances. A single wheelchair accessible staff and visitor WC should be provided in each building close to the principle entrance. Cleaner s cupboards are to be provided on each floor. Each should be approximately 3m 2 and provide a Belfast sink, hot and cold water and shelving. Linen stores are to be provided with a capacity commensurate with the size of development. Student Accommodation Standard Design Guidelines Rev05.docx Page 4 of 15

Comms rooms, minimum dimension 2m x 2m, are required to suit the building layout to meet the maximum Cat 6 cable length of 90m from patch panel to RJ45 outlet. However, provision should not be less than one per alternate floor. Secure and covered bin stores are to be provided externally for general waste and recycling. The facility can be shared between buildings if considered appropriate by the University. Covered secure cycle storage is to be provided at each residential building or group of buildings. Lifts should be provided as necessary to ensure all rooms are accessible to ambulant disabled. Car size should provide a minimum capacity of 8 persons and be equipped with CCTV, alarm and voice connection to an approved 24 hour monitoring service. Internal and external social space shall be provided. E.g Common room/s and external seating and socialising areas. Limited parking shall be provided for staff and visitors as well as a dedicated parking space for each disabled resident. 4.1. Facilities for disabled residents 4.1.1. Generally, purpose built adapted and adaptable facilities for disabled residents should be provided at an overall ratio of approximately 1:40 in any development. It is unnecessary, and undesirable, to group adapted rooms in a single block or flat. It is preferable for adapted rooms to be located on the ground floor. 4.1.2. Where adapted bedrooms are provided suitable en suite washing, showering and toilet facilities shall also be provided. 4.1.3. Access to and full use of kitchen facilities and social areas shall also be provided. 4.1.4. All rooms within a residential development shall be accessible by a wheelchair user. i.e not just the flat containing an adapted room. 4.1.5. Due to design constraints and viability, townhouse developments may not always be fully accessible on all floors. However, all ground floor accommodation, including WC and kitchen/dining facilities shall be designed to meet the needs of disabled occupiers and visitors. 4.2. Cluster Flats with en suite Bedrooms 4.2.1. Flat Size Each flat should comprise 5 or 6 bedrooms together with a kitchen diner. Although not preferred the bedrooms per flat could be increased to a maximum of 8 if necessary in some instances if this achieves a more efficient layout. Student Accommodation Standard Design Guidelines Rev05.docx Page 5 of 15

4.2.2. Bedroom Size Each bedroom should be a minimum of 11.5 m 2 excluding the en suite. 4.2.3. En suite Size Each en suite should be c2.5m 2. 4.2.4. Bedroom Facilities Each bedroom should provide as a minimum: Standard 900mm single bed complete with bedhead Bedside table Desk area at least 1500mm wide x 600mm deep 2 drawer fixed pedestal unit below desk Task lighting shall be provided Double Wardrobe with two drawers under at least 1000mm wide x 590mm deep x 1800mm high Desk chair Minimum of 1500mm of bookshelves Full length mirror to be provided either within wardrobe or wall fixed. Double coat hook to be provided on back of bedroom door and within bathroom/shower room. 4.2.5. En suite Facilities Each en suite should provide: WC Wash hand basin (typically 500mm x 420mm) with cupboard under Minimum 800mm x 800mm shower enclosure, with shower tray, soap dish and shower curtain. Mirror and shaver light/point over wash hand basin Heated towel rail with timed booster Shelf Toilet roll holder Ceramic wall tiling to any wall surface subject to frequent wetting is preferred 4.2.6. Kitchen Diner The kitchen diner should provide: Lockable (by use of small padlock) cupboard space to allow each flat occupant to have one cupboard in addition to storage for general cookware etc. Sufficient sinks and cooking facilities to meet the various legislative and Code requirements Surfaces to be heat resistant and with splashbacks Table and chairs to enable all flat occupants to eat together Sufficient space for fridge/freezers such that each flat occupant has one shelf in each Space for waste and recycling bins Tall cupboard for ironing board, vacuum cleaner and cleaning materials A lounge/soft seating area with sufficient seats for all occupants to sit together A typical en suite bedroom layout can be found at Appendix A. Student Accommodation Standard Design Guidelines Rev05.docx Page 6 of 15

4.3. Cluster Flats with non en suite bedrooms 4.3.1. Flat Size Each flat should comprise 6 bedrooms together with a kitchen diner. Although not preferred the bedrooms per flat could be increased to a maximum of 8 if necessary in some instances if this achieves a more efficient layout. 4.3.2. Bedroom Size Each bedroom should be a minimum of 11.5 m 2. 4.3.3. Bedroom Facilities Each bedroom should provide as a minimum: Standard 900mm single bed complete with bedhead Bedside table Desk area at least 1500mm wide x 600mm deep 2 drawer fixed pedestal unit below desk Double Wardrobe with two drawers under at least 1000mm wide x 590mm deep x 1800mm high Wash hand basin (typically 500mm x 420mm) with cupboard under Mirror and shaver light/point over wash hand basin Desk chair Minimum of 1500mm of bookshelves Full length mirror to be provided either within wardrobe or wall fixed Double coat hook to be provided on back of bedroom door 4.3.4. WCs Each flat with up to and including 6 bedrooms should provide one separate WC with small wash hand basin, shelf and toilet roll holder. Flats with more than 6 bedrooms should be provided with two separate WCs. 4.3.5. Shower Rooms Each flat should provide two separate shower rooms each comprising minimum 800mm x 800mm shower enclosure with tray and shower curtain, wash hand basin with mirror over, WC, shelf, robe hook and toilet roll holder. Ceramic wall tiling to any wall surface subject to frequent wetting is preferred. 4.3.6. Kitchen Diner The kitchen diner should provide: Lockable (by use of small padlock) cupboard space to allow each flat occupant to have one cupboard in addition to storage for general cookware etc. Sufficient sinks and cooking facilities to meet the various legislative and Code requirements Table and chairs to enable all flat occupants to eat together Sufficient space for fridge/freezers such that each flat occupant has one shelf. Space for waste and recycling bins A lounge/soft seating area with sufficient seats for all occupants to sit together A typical non en suite bedroom layout can be found at Appendix B. Student Accommodation Standard Design Guidelines Rev05.docx Page 7 of 15

4.4. Townhouses 4.4.1. Townhouse Size Each townhouse should typically comprise two or three storeys of accommodation providing between six and eight bedrooms and a kitchen diner. 4.4.2. Bedroom Size Each bedroom should be a minimum of 11.5m 2. 4.4.3. Bedroom Facilities Each bedroom should provide as a minimum: Standard 900mm single bed complete with bedhead Bedside table Desk area at least 1500mm wide x 600mm deep 2 drawer fixed pedestal unit below desk Double Wardrobe with two drawers under at least 1000mm wide x 590mm deep x 1800mm high Desk chair Minimum of 1500mm of bookshelves Full length mirror to be provided either within wardrobe or wall fixed Double coat hook to be provided on back of bedroom door 4.4.4. WCs Each townhouse should be provided with one separate WC, located on the ground floor, with small wash hand basin, shelf, mirror and toilet roll holder. Ceramic wall tiling to any wall surface subject to frequent wetting is preferred 4.4.5. Shower Rooms Each townhouse should provide two separate shower rooms per four bedrooms each of which should provide: WC Wash hand basin (typically 500mm x 420mm) with cupboard under Minimum 800mm x 800mm shower enclosure with tray, soap dish and shower curtain. Mirror and shaver light/point over wash hand basin Heated towel rail with timed booster Shelf Toilet roll holder 4.4.6. Kitchen Diner The kitchen diner should provide: Lockable (by use of small padlock) cupboard space to allow each townhouse occupant to have one cupboard in addition to storage for general cookware etc. Sufficient sinks and cooking facilities to meet the various legislative and Code requirements Table and chairs to enable at least eight occupants to eat together Sufficient space for fridge/freezers such that each occupant has one shelf. Space for waste and recycling bins Student Accommodation Standard Design Guidelines Rev05.docx Page 8 of 15

A lounge area with sufficient seats for all occupants to sit together A typical townhouse layout can be found at Appendix C. 4.5. Studio Rooms The University would consider developments incorporating a percentage of studio rooms suitable for accommodating up to 2 residents. 4.5.1. Studio Room Size Each Studio Room will be between 20m 2 and 25m 2 and will consist of the following 4.5.2. Living area Each living area should provide as a minimum: Standard 4 6 double bed complete with bedhead Bedside tables Desk area at least 1500mm wide x 600mm deep 2 drawer fixed pedestal unit below desk Double Wardrobe with two drawers under at least 1000mm wide x 590mm deep x 1800mm high Desk chair Minimum of 1500mm of bookshelves Full length mirror to be provided either within wardrobe or wall fixed Double coat hook to be provided on back of bedroom door 2 easy chairs A lounge area with sufficient seats for all occupants to sit together 4.5.3. Ensuite Facilities Each en suite should provide: WC Wash hand basin (typically 500mm x 420mm) with cupboard under Minimum 800mm x 800mm shower enclosure, with shower tray, soap dish and shower curtain. Mirror and shaver light/point over wash hand basin Heated towel rail with timed booster Shelf Toilet roll holder Ceramic wall tiling to any wall surface subject to frequent wetting is preferred 4.5.4. Kitchen facilities The kitchen diner should provide: Suitable cupboard space for up to 2 residents to allow for both food and storage for general cookware etc. Sufficient sinks and cooking facilities to meet the various legislative and Code requirements Table and chairs to enable at least the occupants to eat together Sufficient space for fridge/freezer. Space for waste and recycling bins Student Accommodation Standard Design Guidelines Rev05.docx Page 9 of 15

5. Building Elements 5.1. Building Fabric 5.1.1. Suspended ceilings to be avoided wherever possible. 5.1.2. Door locking should be either centrally programmable electronic or mechanical keyed cylinder on a master suite. For on campus developments the locking system should be compatible with existing University of Chichester systems. 5.1.3. Curtains rather than blinds to be provided where necessary except in kitchens and bathrooms where blinds should be provided. 5.1.4. Consider use of reflective glass/film for security purposes where rooms are overlooked and/or are likely to experience high levels of solar gain. 5.1.5. Tamper proof window restrictors to be fitted to all opening windows, to allow a maximum opening of 100mm. 5.1.6. Suitable protection to be provided to exposed/vulnerable corners to reduce effect of impact damage. 5.1.7. Hardwearing cleanable wall finishes to be provided. 5.1.8. Accent wall colours to be incorporated into the interior design in entrances, communal and circulation spaces, and bedrooms. 5.1.9. Floor finishes should reflect the use of the space, i.e. carpet tiles to bedrooms and lounges, vinyl to bathrooms and kitchens and entrance matting to all entrances and exits. 5.1.10. Vandal resistant door numbers and/or room designations to be provided. Where appropriate door stops and kick plates should be fitted to avoid impact damage. 5.2. Building Services 5.2.1. The design and specification of heating and hot water installations should take into consideration the ongoing maintenance and energy costs and not simply capital cost. 5.2.2. Main plant spaces should be accessible from communal areas. 5.2.3. Push fittings on all pipework should not be used. 5.2.4. Isolation valves should be installed on all branches and on a per flat/townhouse and per floor basis. 5.2.5. Variable speed pumps to be used on all pumped systems. Student Accommodation Standard Design Guidelines Rev05.docx Page 10 of 15

5.2.6. Pipework materials should be commensurate with use and location and adequate supports provided wherever necessary. 5.2.7. Kitchen ventilation to be ducted to open air rather than re circulating within room. 5.2.8. Shower room / en suites should be individually ventilated at a rate of at least 15 litres/second to open air with a 20 minute overrun. 5.2.9. Lifts should be provided to all multi storey buildings except townhouses and should have independent control gear for each lift to reduce the risk of all lifts being out of action at once. Lifts should be sized to accommodate a minimum 8 persons or; a wheelchair user with attendant or; furniture and belongings. 5.2.10. Disabled Refuge points to be provided at each level equipped with 24 hour voice connection to an approved monitoring service. 5.2.11. Each flat/townhouse should have a separate distribution board for isolation purposes and be housed in a locked cupboard to avoid misuse. 5.2.12. As a minimum each bedroom should include at least two double power sockets above the desk and two double power sockets elsewhere in the room. 5.2.13. Each study bedroom should include at least one twin RJ45 data socket above the desk. 5.2.14. Dedicated cleaning sockets to be provided on each floor/flat/stairwell. 5.2.15. A permanent connection point for an emergency generator should be provided, together with identification of a location for an emergency generator in the event of power failure etc. 5.2.16. Motion sensor lighting should be installed in all common/circulation areas which should have a 10% background light level and a normal level when motion sensor is activated. 5.2.17. CCTV to be installed to monitor all entrances and exits together with primary circulation routes. System to be compatible with University security systems and images fed back to University Security unless the development is an off campus direct let scheme. 5.2.18. All alarms (lift, fire and intruder etc.) should be compatible with University security systems and fed back to the University Security unless the development is an off campus direct let scheme. In the event that the latter applies all systems should be monitored on a 24/7 basis by an approved monitoring service. Student Accommodation Standard Design Guidelines Rev05.docx Page 11 of 15

5.2.19. Temperature control shall be as set out in Table 2 below. Area Summer Winter WCs/Circulation No specific temp control 18 o C db +/ 1 o C Bathroom No specific temp control 23 o C db +/ 1 o C Bedroom/Kitchen Diner No specific temp control 20 o C db +/ 1 o C Table 2. Temperature Control Criteria 5.2.20. Data network to be Cat 6 star wired back to comms room. 5.2.21. Comms rooms to be ventilated, preferably mechanically, and have 2No. 16 Amp commando sockets. 5.2.22. Hub Racks/Cabinets should be 800mm x 800mm x 42u high. 5.2.23. All areas to be provided with full WiFi coverage with twin RJ45 data points to be provided at each WAP location. 6. Sustainability 6.1. BREEAM The University has stated that all new developments should obtain a BREEAM Excellent rating as a minimum. Refurbishment/conversion schemes should achieve at least BREEAM Very Good. 6.2. Passive Design The aim of all designs should be to optimise the passive building elements where possible and hence reduce the energy consumption associated with the mechanical and electrical systems. 7. Management/Security Office For any off campus development there shall be a management/security office included in the building. The office will be of sufficient size to comfortably accommodate at least two members of staff. The office should be equipped with desks, office chairs and sufficient storage facilities. The management office should be situated adjacent to the main entrance to the development. There may be occasions where a management/security office will be required for on campus developments. Student Accommodation Standard Design Guidelines Rev05.docx Page 12 of 15

Student Accommodation Standard Design Guidelines Rev05.docx Page 13 of 15 Appendix A

Student Accommodation Standard Design Guidelines Rev05.docx Page 14 of 15 Appendix B

Student Accommodation Standard Design Guidelines Rev05.docx Page 15 of 15 Appendix C