TENANT DESIGN MANUAL UPDATED DECEMBER 2018

Similar documents
TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED FEBRUARY 2017

TENANT DESIGN MANUAL UPDATED OCTOBER 2016

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JANUARY 2016

TENANT DESIGN MANUAL UPDATED OCTOBER 2016

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED AUGUST 2016

TENANT DESIGN MANUAL UPDATED MAY 2016

TENANT DESIGN MANUAL UPDATED JULY 2016

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JUNE 2016

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED AUGUST 2015

TENANT DESIGN MANUAL UPDATE JUNE 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED FEBRUARY 2017

TENANT DESIGN MANUAL UPDATED JULY 2015

TENANT DESIGN MANUAL UPDATED JUNE 2015

LOUIS JOLIET MALL TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

SOUTHLAKE MALL. Southlake Mall Tenant Design & Construction Criteria TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

PLAZA WEST COVINA TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

The Promenade at Casa Grande 1005 N Promenade Pkwy Casa Grande, AZ 85294

14400 Bear Valley Road, Victorville, CA 92392

TECHNICAL CRITERIA ARROWHEAD TOWNE CENTER THE PLACE TO SHOP

FRANKLIN PARK MALL TENANT DESIGN & CONSTRUCTION CRITERIA PROPERTY SPECIFIC REQUIREMENTS

San Tan Village 2218 E. Williams Field Rd. #235, Gilbert, AZ 85295

General Information RETAIL AND RESTAURANT

GENERAL INFORMATION. Landlord s Tenant Coordinator

TWELVE OAKS GENERAL INFORMATION (BUILDING E ONLY)

Tenant Design Criteria Section t Technical Criteria Updated: August Wilton Mall at Saratoga 3065 Route 50, Saratoga Springs, NY 12866

Submission Procedures

TWELVE OAKS GENERAL INFORMATION (BUILDINGS A, B, C, and D ONLY)

TECHINICAL CRITERIA DEPTFORD MALL THE PLACE TO SHOP

th Street Boulder CO 80301

E x p a n s i o n P r o j e c t

DESCRIPTION OF LANDLORD'S WORK & TENANT'S WORK

8000 Cooper Avenue, Glendale, NY 11385

LANDLORD WORKLETTER EXHIBIT C-1 CONSTRUCTION REQUIREMENTS AND STANDARDS GREY SHELL ONLY

TECHNICAL CRITERIA THE PLACE TO SHOP THE SHOPS AT ATLAS PARK

3435 MAIN 3435 Main Street Kansas City, MO RESTAURANT SPACE Available for Lease 1. BUILDING LOCATION

TENANT DESIGN CRITERIA V. Technical Criteria 34

FAIR OAKS GENERAL INFORMATION

The Shops at Montebello Montebello Town Center Dr, Montebello, CA 90640

a) Tenant shall require its Contractor to provide and maintain the following insurance coverage:

TECHNICAL CRITERIA THE PLACE TO SHOP LOS CERRITOS CENTER

Exhibit C - Shops 1 & 2

CHARLESTON PLACE TENANT CALCULATION CHECK/DATA TABULATION SHEET(S) Forms must be completed by the Tenant's Mechanical or Electrical Engineer.

FOR LEASE. Capitol Hill Corner Cafe/Restaurant Space th Avenue, Seattle, WA Please call brokers for more information:

Construction Document Criteria

Construction Document Criteria

Construction Document Criteria

Fee Type How Determined Rate Permit Processing Charge Flat Permit or Plan Review Submittal $32.00

CHAPTER 1321 Permit and Inspection Fees

Tenant Design Criteria Section rd Restaurant Design Criteria Updated: June E. Camelback Road, Scottsdale, AZ 85251

CONSTRUCTION CRITERIA

Construction Document Criteria

TENANT MANUAL 5 January 2006

Bangor Mall Bangor, ME

Restaurant Addendum to Tenant Construction and Design Criteria. Restaurant Criteria. Replace Existing Tenant

Design and Construction Document Criteria

OBTAINING A CERTIFICATE OF OCCUPANCY FOR UNAPPROVED DWELLING UNITS

List of Principal Officials

CONSTRUCTION CRITERIA

THE PLACE TO SHOP CHANDLER FASHION CENTER

THE BAY STREET STORY. Page 1 of 32

Shoreview Corporate Center

M001 EAGLECREST LEARNING CENTER CITY & BOROUGH OF JUNEAU. Inc. CBJ CONTRACT No. E SYMBOLS FAN SCHEDULE HEATING COIL SCHEDULE EQUIPMENT SCHEDULE

ARLINGTON S COOLEST SQUARE BLOCK HAS RISEN TO ITS EXPECTATIONS. #HQCOOL

TRIALLIANCE COMMERCIAL REAL ESTATE SERVICES COLUMBIA STATION Route 108, Old Annapolis Road Columbia, MD 21045

City of Oregon City. Community Development Building Division Fee Schedule Effective April 1, 2016 BUILDING DIVISION

DEPARTMENT OF BUILDING AND SAFETY

GENERAL GROWTH PROPERTIES, INC.


GRAND CENTRAL TERMINAL NEW YORK, NY MECHANICAL, ELECTRICAL AND PLUMBING TENANT DESIGN CRITERIA HANDBOOK

BUI L DIN G A ND E L E V A T O R F E ES

1. Project No.: 812 Muslim Commercial Bank, Karachi Mechanical & Electrical System

COLD DARK SHELL LEASE EXHIBIT

EXHIBIT C. Leasehold Improvements Work Letter

GENERAL INFORMATION CRITERIA

RESIDENCE 1A. 1 bedroom, living/dining room plus juliet balcony RESIDENCE 1B JULIET BALCONY BEDROOM LIVING DINING 10'-0" 9'-5" 9'-3" 17'-4"

Tenant Design Criteria Section gi General Information Criteria Updated: January Dale Rd., Modesto, CA 95356

BUILDING DIVISION SIMPLIFIED BUILDING PERMIT FEE SCHEDULE January 01st, 2019 to December 31st, 2019

Tenant Design Criteria Section gi General Information Criteria Updated: June Paradise Valley Mall 4568 E. Cactus Rd., Phoenix, AZ 85032

THE PLACE TO SHOP TOWNE MALL

COUNTY OF FREDERICK INSPECTIONS DEPARTMENT FEE SCHEDULE Approved July 14, COMMERCIAL FEES Minimum Fee $ unless stated otherwise

RENTER'S INSPECTION WORKSHEET Free form provided at

Building Specifications

Theodore Roosevelt High School 3436 W Wilson Ave Chicago, IL 60625

Transcription:

TENANT DESIGN MANUAL UPDATED DECEMBER 2018

PROJECT OVERVIEW South Hills Village is located at US 19 (Washington Road) and Ft. Couch Road, in the Bethel Park suburb of Pittsburgh. 2

PROJECT OVERVIEW Anchored by Macy*s, and Barnes and Noble, South Hills Village features more than 130 national and specialty retailers, restaurants, a Food Court and the Carmike 10 Theater. 3

SITE PLAN 4

TENANT INFORMATION PACKAGE The Tenant Information Package can be accessed from Simon s website simon.com.» Select the business header, search for the property name, click on the Tenant Info Package link on the right side of the page.» If you have any difficulties working with the website, please contact your Tenant Coordinator. *For questions regarding the Landlord s design and construction requirements, please contact your Tenant Coordinator or call 317-636-1600 and ask for Tenant Coordination. 5

MALL BUILDING DATA Occupancy/ Use: Construction Classification: Building Levels: Sprinkler System: Mercantile Type II B One (1) Level Fully Sprinkled 6

MUNICIPAL ZONE PLAN LOWER LEVEL 7

MUNICIPAL ZONE PLAN UPPER LEVEL 8

l14-0 storefront height (verify in field) l14-0 storefront height (verify in field) STOREFRONT ELEVATION LOWER LEVEL Typical storefront height is raised to 14-0 A.F.F (bottom of the 1x located below the mall bulkhead. 2-0 projections are allowed on lower level and 1-6 projections are allowed on upper level in approved areas. 9

14-0 storefront height (verify in field) STOREFRONT ELEVATION UPPER LEVEL (THESE PHOTOS BELOW ARE EXAMPLES OF EXISTING, PER CRITERIA STOREFRONT HEIGHT WILL BE RAISE FOR ALL CONSTRUCTION) Mall Bulkhead Mall Bulkhead l 1x below the bulkhead Raise storefront 24 +/- (V.I.F.) l Raise storefront 24 +/- (V.I.F.) l 1x below the bulkhead l14-0 storefront height (verify in field) Typical storefront height is raised to 14-0 A.F.F (bottom of the 1x located below the mall bulkhead. 2-0 projections are allowed on lower level and 1-6 projections are allowed on upper level in approved areas. 10

NEUTRAL PIER DETAIL FOR PROJECTING STOREFRONT Neutral piers are 3/4 black metal reveals located on the centerline of the lease lines between the two storefront. Tenant s finishes will extend to the edge of the metal reveals. Flushed storefronts are also encouraged and referred to on page 13. 11

STOREFRONT DETAILS NEUTRAL PIERS Old neutral pier condition all sections, all levels. New neutral pier condition all sections, all levels. Neutral Pier - All Sections, All Levels (except Food Court): The Neutral Pier condition for the entire Mall is a ¾ reveal installed at the center line of the demising wall. See the Detail provided in this manual. If the old neutral pier condition still exists, the Tenant is required to remove it during demolition and install the ¾ reveal. Tenants must extend their storefront finishes to the edge of this ¾ reveal. If the reveal did not already exist, Tenant s GC must also finish out the opposite side of the new reveal to the edge of the adjacent Tenant s storefront finishes. The Mall Operations Director or Construction Coordinator will coordinate the finish of this area with the GC on site. 12

NEUTRAL PIER DETAIL - FOR FLUSH STOREFRONTS 13

STOREFRONT SIGNS, AWNINGS & CANOPIES 14

11-0 A.F.F. (Verify in Field) FOOD COURT ELEVATION All signs MUST be mounted to a metal sign grid Blade Signs required in food court (Coordinate with Mall Operations on blade sign criteria) l Neutral Pier 15

HVAC RETAIL TENANTS This is an enclosed chilled water mall. Tenant s design team shall accommodate conditions that may affect the performance of the HVAC system for their store, i.e. zoning for solar gain at the storefront, sensor location (s) and size and quantity of return air outlets. System Landlord supplied chilled water. Supply Water Conditions Landlord has provided adequate chilled water for retail occupancies. (EWT is 42 degrees, LWT is 60 degrees minimum). 2 way modulating control valve by Tenant or reuse existing. 10 WPD maximum for Tenant components. Tenant Equipment Tenant shall utilize only Central Station AHU equipment with electric heat (No fan coil units permitted) and 6 row coils. Reuse existing valved connection or new connection by Tenant. Condensate Route to Code approved receptacle within space through roof curb. HVAC Load Calculation Tenant to submit detailed computer generated load calculation to justify request for chilled water. Outside Air Lower level Tenants will connect to Landlord supplied duct. Upper level Tenants will be required to duct the outside air from the roof through a Tenant supplied gravity ventilator. Return Plenum (Ducted return is for odor producing Tenants only and subject to Landlord approval). Smoke Exhaust/Relief None required. Toilet Exhaust Lower level Tenant supplied fan (150 CFM max) with duct extension to Landlord duct. Interlock with light switch. Tenant to provide for any additional exhaust requirements. Upper level - Tenants will be required to vent their toilet exhaust through the roof. Odor, Thermal & Process Equipment Exhaust Size for application by Tenant. 16

HVAC RETAIL TENANTS, CONT. Temperature Controls Tenant shall install Landlord specification (Andover) controller on each AHU. Landlord designated vendor to install and connect into the system. Test & Balance Tenant shall employ a TAB, NEBB or AABC Certified Air Balance Contractor to perform final testing and balancing. See Criteria Sheet MEP-1 for further information. 17

PLUMBING RETAIL TENANTS Water Redistributed by Landlord via overhead mains, ¾ minimum valved connection at pressure available from public system minus distribution losses. Tenant supplied meter w/remote reader for large water users only. Waste 4 wye connection off Landlord main. Designated connection point within or adjacent to space. Vent Lower level Tenants connect to Landlord provided vent stubs. Upper level Tenants vent to roof. Natural Gas Not available. Toilet Rooms As required by code. See Criteria Sheet MEP-1 for further information. 18

FIRE PROTECTION RETAIL TENANTS Fire Protection Modify existing system to comply with Code and Landlord insurance requirements. Implementation Tenant shall directly employ the Landlord designated contractor. Tenant Flow Switch Not permitted. Valve for Tenant Space Not permitted. See Criteria Sheet MEP-1 for further information. 19

ELECTRICAL RETAIL TENANTS Voltage 277/480V, 3ph, 4-wire Wire Color For all wire sizes install wire colors in accordance with the following: (A) red, (B) black, (C) blue, and (N) gray/white for circuits @ 120/208 volts single or three phase (A) brown, (B) orange, (C) yellow, and (N) gray/white, with one or more colored stripes for circuits @ 277/480 volts single or three phase Landlord Equipment Fusible switches, plug in bus duct in central locations and (2) 1 minimum conduits. One 1 conduit and 60 amp fusible switch for lighting, power and water heating. One 1 conduit and 60 amp switch for HVAC equipment. Power Provided by redistributed electrical system by Landlord. Metering Tenants to utilize existing Landlord check meter or install Landlord specified metering on light and power service. Reuse existing conduit or install new for code required demand load. Verify with Landlord if exceeding existing fused switch size. Submit connected and demand electrical load data to support electric service size requested. Telephone 3/4 minimum conduit with pull wire to designated connection point in central locations or route cable via service corridor. Fire Alarm Existing Landlord system is Simplex 4100. It has no provision for connection to Tenant required devices. See Criteria Sheet MEP-1 for further information. 20

HVAC FOOD COURT TENANTS The Food Court utilizes rooftop units. Engineer is required to accommodate conditions that may affect the performance of the HVAC system for their store. Equipment Downflow rooftop unit on full curb with electric or natural gas heat. Split systems are allowed with Landlord approval. Condensate Drain Route to Code approved receptacle within space through curb. Return Ducted (Plenum return is for non-odor producing Tenants only and subject to Landlord approval). Smoke Exhaust/Relief Tenant to provide Code required smoke exhaust fan or reuse existing. Minimum size shall be 1.5 cfm per square foot of lease space. Tenant space shall remain negative relative to Mall. Toilet Exhaust By Tenant including fan, ductwork and roof cap. Odor, Thermal & Process Equipment Exhaust Size for application by Tenant. Grease Exhaust Per code. Protect roof with Grease Guard containment system. Replacement Air From Tenant outside air and dedicated makeup air units. Temperature Controls Stand-alone digital electric/electronic control system by Tenant. Test & Balance Tenant shall employ a TAB, NEBB or AABC Certified Air Balance Contractor to perform final testing and balancing. See Criteria Sheet MEP-1 for further information. 21

PLUMBING FOOD COURT TENANTS Water Redistributed by Landlord via overhead mains, 1 minimum valved connection at pressure available from public system minus distribution losses. Tenant supplied meter w/remote reader. Waste 4 wye connection off Landlord main. Designated connection point within or adjacent to space. Vent Through roof by Tenant. Grease Waste Tenant to install Code compliant grease trap within premise. Natural Gas Available at exterior meter banks; subject to utility availability. Meter and piping by Tenant if not existing. Provide automatic shut off valve. Toilet Rooms As required by code. See Criteria Sheet MEP-1 for further information. 22

FIRE PROTECTION FOOD COURT TENANTS Fire Protection Modify existing system to comply with Code and Landlord insurance requirements. Implementation Tenant shall directly employ the Landlord designated contractor. Tenant Flow Switch Not permitted. Valve for Tenant Space Not permitted. See Criteria Sheet MEP-1 for further information. 23

ELECTRICAL FOOD COURT TENANTS Voltage 277/480V, 3ph, 4-wire Wire Color For all wire sizes install wire colors in accordance with the following: (A) red, (B) black, (C) blue, and (N) gray/white for circuits @ 120/208 volts single or three phase (A) brown, (B) orange, (C) yellow, and (N) gray/white, with one or more colored stripes for circuits @ 277/480 volts single or three phase Landlord Equipment Metering switchboard at central location. 2 minimum conduit. Power Provided by redistributed electrical system by Landlord. Metering Tenants to utilize existing Landlord check meter or install Landlord specified metering. Reuse existing conduit or install new for code required demand load. Verify with Landlord if exceeding existing main switch size. Submit connected and demand electrical load data to support electric service size requested. Telephone 1 minimum conduit with pull wire to designated connection point in central locations or route cable via service corridor. Fire Alarm Landlord system is a Simplex 4100U. Tenant must connect duct detector and hood extinguishing system to Landlord control and monitor modules to activate Tenant smoke fan. Final connection and programming to be by Landlord s designated vendor. See Criteria Sheet MEP-1 for further information. 24

MEP CALCULATION FORMS Tenant s Engineer shall use their own forms to calculate and comply with Landlord s MEP design criteria: Appliance Heat Gain Electrical Load Summary Kitchen Exhaust Fan Specifications Kitchen Make-up Air Unit Specification VAV Terminal Specification Maintenance 25