Available online at ScienceDirect. Energy Procedia 78 (2015 )

Similar documents
Available online at ScienceDirect. Energy Procedia 78 (2015 )

Measuring Air Change Rates using the PFT Technique in Residential Buildings in Northern Portugal

Energy consumption in an old residential building before and after deep energy renovation

Energy variations in apartment buildings due to different shape factors and relative size of common areas

The effect of atrium façade design on daylighting in atrium and its adjoining spaces

Assessing of thermal comfort in multi-stories old and new residential buildings in China

Indoor climate of an unheated apartment and its impact on the heat consumption of adjacent apartments

Indoor climate and energy consumption in residential buildings in Estonian climatic conditions

ELECTRICAL LOAD CHARACTERISTICS OF SUPERINSULATED MULTIFAMILY HOUSING: A CASE STUDY

measures of apartment buildings

Study of the energy performance of Korean apartment buildings with alternative balcony configurations

MONITORED RESULTS FROM AN INNOVATIVE SOLAR RENOVATION OF MULTI STOREY HOUSING - EU SHINE ENGELSBY, FLENSBURG

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 6 Heiselberg, Per Kvols. Publication date: 2016

Passive Cooling Measures for Multi-Unit Residential Buildings

Daylight availability in courtyards of urban dwellings in Athens

Impacts of Maximum Allowable Building Footprint on Natural Ventilation in Apartment Building

NFPA (2012). In a high-rise building, stairwell pressurization systems typically utilize multiple fans distributed over the height of the stair, a duc

Published in: NSB 2014: 10th Nordic Symposium on Building Physics June 2014 Lund, Sweden

The relationships between the extent of mould problems and physical building characteristics in high-rise apartment buildings

World Renewable Energy Congress (WRECX) Editor A. Sayigh 2008 WREC. All rights reserved. 822

COMFORT WITH COURTYARDS IN DHAKA APARTMENTS

Assessing the effect of new control and payment methods on heating energy consumption and occupant behaviour in Chinese dwellings

The Carpenter Center for Visual Arts, Harvard University Analysis 4 th and 5 th Floor Studio Spaces

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 7 Heiselberg, Per Kvols. Publication date: 2016

Available online at ScienceDirect. Energy Procedia 96 (2016 )

ABSTRACT. Keywords: Adaptive behavior, Wind flow, Energy-saving, Energy consumption, Coastal areas

Atrium in residential buildings a design to enhance social interaction in urban areas in Nordic climates

Balanced ventilation in apartment buildings

GLAZED BALCONIES AND SUN SPACES ENERGY SAVERS OR ENERGY WASTERS?

DAYLIGHT SIMULATION FOR CODE COMPLIANCE: CREATING A DECISION TOOL. Krystle Stewart 1 and Michael Donn 1

Plan for acquisition of historical consumption data and household typology for each dwelling

Figure 1. The chart showing how the effort and cost of the design changes are affected as the project progresses (Anon.) Simulation tools are a key co

Apartment Building in Brogården, Alingsås SE

Is there a conspicuous consumption effect in Bucharest housing market?

Keywords: criteria of economic efficiency, governance, land stock, land payment, land tax, leasehold payment, leasehold

Fundamental Study on Thermal Surface Analysis

Influence of occupants behavior on indoor CO 2 concentration of a naturally ventilated multifamily building in Porto, Portugal.

Robustness of multi-objective optimization of building refurbishment to suboptimal weather data

Energy Efficient and Passive House Building Design Guidelines

THE CURRENT RESULTS OF URB.ENERGY PROJECT IN THE TARGET AREA JUGLA (Riga)

INRODUCTION STATISTIC DATE OF DWELLINGS STOCKS IN POLAND.

DEMAND FR HOUSING IN PROVINCE OF SINDH (PAKISTAN)

Analyzing Ventilation Effects of Different Apartment Styles by CFD

COMPARISON OF SAMPLING METHODS FOR AIR TIGHTNESS

Energy Efficiency and Urban Renewal of a UNESCO-listed historical centre: The case of Porto. Álvaro Santos Paulo Valença José Pacheco Sequeira

Maratonvägen 36. Project summary. Energy concept: To achieve a substantial reduction of the energy losses.

Learning in Architecture Design Studio

INDOOR ENVIRONMENT IN MULTI-STOREY RESIDENTIAL BUILDINGS Thermal and Visual Comfort Using IV20 MASTER THESIS

Indoor climate and ventilation performance on top floors of typical old-type apartment buildings

Washington Department of Revenue Property Tax Division. Valid Sales Study Kitsap County 2015 Sales for 2016 Ratio Year.

RETROFIT OF BUILDINGS BY DUBLIN CITY COUNCIL. Matt Carroll, City Architects Division DUBLIN CITY COUNCIL

RESOLUTION NO ( R)

On the Relationship between Track Geometry Defects and Development of Internal Rail Defects

The Effects of Housing Price Changes on the Distribution of Housing Wealth in Singapore

The Impact of Balconies on Wind Induced Ventilation of Singlesided Naturally Ventilated Multi-storey Apartment

ASSESSMENT OF ACCESSIBILITY IN APARTMENT MIXED-USE HOUSING -IN THE CASE OF KABUL

Urban Planning and Architectural Standards for Social Housing Architectural Design

PUBLISHED VERSION. 2014, The Architectural Science Association & Genova University Press.

Wijk van Morgen, Kerkrade

Elements for an acoustic classification of dwellings and apartment buildings in France C. Guigou-Carter, R. Wetta, R. Foret, J.-B.

IREDELL COUNTY 2015 APPRAISAL MANUAL

Energy efficient renovation of building stock of Jugla

Report of the RIBA visiting board to the University of Hong Kong

Utilizing 3D Building and 3D Cadastre Geometries for Better Valuation of Existing Real Estate

Journal of Babylon University/Engineering Sciences/ No.(5)/ Vol.(25): 2017

Course Residential Modeling Concepts

Attic Floor Bedrooms 1 & 2 Family Dwellings

Study of Environmental Cognition and Life Domains of Residents of Super High-rise Condominiums

LITHUANIAN HOUSING MODERNIZATION PROGRAM. valius serbenta housing energy efficiency agency

Buy a passive house in a micro residential area, modern, comfortable, all houses are very efficient with a very low energy consumption (90% less than

[BUILDING STATISTICS PART I]

Evacuation Design Focused on Quality of Flow

A STUDY ON ZONING REGULATIONS IMPACT ON VENTILATION RATE IN NON-CONDITIONED APARTMENT BUILDINGS IN DHAKA CITY

Illinois Farmland Sales Database

Sustainable retrofitting of blocks of flats: environmental, economic and social aspects

Registration of the Premises in 2D Cadastral System in Poland

LOCATION ORIENTATION ARCHITECTURAL UNIQUENESS STATE OF CONSERVATION RETURN ON INVESTMENT

Dense housing and urban sustainable development

Improving the Social Dialogue for Energy Efficient Social Housing

UCSD Revelle College Apartments

Evaluation of Vertical Equity in Residential Property Assessments in the Lake Oswego and West Linn Areas

DIRECTIVE # This Directive Supersedes Directive # and #92-003

Tenants Acceptance or Rejection of Major Energy Renovation of Block of Flats IEA Annex 56

REPEATABILITY & REPRODUCIBILITY (R&R) STUDY

Trends in Affordable Home Ownership in Calgary

Ventilation and climate control

Small Lot Housing Code (June 2013):

Everything's Fine at home

MOLDOVA: STUDY INTO IMPROVING THE ENERGY EFFICIENCY OF RESIDENTIAL BUILDINGS

House prices up by 7.6% on a year before

ANALYSIS OF RELATIONSHIP BETWEEN MARKET VALUE OF PROPERTY AND ITS DISTANCE FROM CENTER OF CAPITAL

The accounting treatment of goodwill as stipulated by IFRS 3

86 years in the making Caspar G Haas 1922 Sales Prices as a Basis for Estimating Farmland Value

PROPERTY FACTS. Your Green Office In The Heart of The City

Exposure assessment of magnetic field in dwellings with built-in transformers in Bulgaria

Greening up your Apartment?

ARCH - ARCHITECTURE. ARCH - Architecture 1. ARCH406 Graduate Architecture Design Studio III (6 Credits)

LITTLE MOUNTAIN ADJACENT AREA REZONING POLICY

SUNSPACE DESIGN SOLUTIONS BASED ON DAYLIGHT PERFORMANCE IN A MULTI-STOREY RESIDENTIAL BUILDING

Rockwall CAD. Basics of. Appraising Property. For. Property Taxation

Transcription:

Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2790 2795 6th International Building Physics Conference, IBPC 2015 Variability assessment of thermal comfort in a retrofitted social housing neighborhood based on in situ measurements António Curado a,b, *,Vasco Peixoto de Freitas a, Nuno M. M. Ramos a a CONSTRUCT-LFC, Faculty of Engineering (FEUP), University of Porto, Rua Dr. Roberto Frias s/n, 4200-465 Porto, Portugal b Polytechnic Institute of Viana do Castelo, School of Technology and Management, Department of Engineering Sciences and Technology, Avenida do Atlântico, 4900-348 Viana do Castelo, Portugal. Abstract The current socio-economic conditions of social housing neighborhoods in Portugal, where people generally don t have heating or cooling habits, determines the adoption of passive retrofitting strategies. A social housing neighborhood in Porto, Portugal, named Bairro de Lordelo, with 4 blocks, 179 dwellings and more than 400 inhabitants was recently retrofitted. The retrofitting investment was strictly limited to a maximum value per dwelling and involved the inclusion of thermal insulation in roofs, replacement of windows, and renovation of the ventilation systems. It s main goal was to increase thermal comfort, in a context of inexistence of any heating or cooling systems installed. An indoor climate measurement program was developed for the months of July, August and September of 2012, and the months of December 2012, January and February 2013, in order to evaluate, respectively, summer and winter thermal comfort of the dwellings. The experimental measurements were carried out in 24 dwellings 4 of the dwellings were measured during the 3 months and the other 20 in periods of 2 and 3 weeks-. The study is focused on the importance of the variability of the vertical and horizontal alignment of an apartment and its occupation, for a certain measurement period, on the indoor air temperature and in the thermal comfort of the occupants, according to adaptive models presented in EN15251 and using some descriptive statistics. As a final result it is expected that its influence can be up to 4ºC on the indoor air temperature. 2015 The Authors. Published by by Elsevier Elsevier Ltd. Ltd. This is an open access article under the CC BY-NC-ND license Peer-review (http://creativecommons.org/licenses/by-nc-nd/4.0/). under responsibility of the CENTRO CONGRESSI INTERNAZIONALE SRL. Peer-review under responsibility of the CENTRO CONGRESSI INTERNAZIONALE SRL Keywords: Variability; thermal comfort; retrofitting; in situ measurements * Corresponding author. Tel.: +351 258 819700. E-mail address: acurado@estg.ipvc.pt 1876-6102 2015 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/). Peer-review under responsibility of the CENTRO CONGRESSI INTERNAZIONALE SRL doi:10.1016/j.egypro.2015.11.627

António Curado et al. / Energy Procedia 78 ( 2015 ) 2790 2795 2791 1. Introduction The aim of this paper is to study both the summer and winter thermal comfort of a retrofitted social neighborhood in Porto, Portugal, and evaluate the variability of indoor temperature in a set of similar dwellings [1,2] To assess indoor air temperature and relative humidity of the several rooms, a monitoring campaign was carried out for the summer months of 2012 and winter months of 2012 and 2013. Data loggers were installed in a set of 24 occupied dwellings to collect data every 10 minutes. The instrumented rooms (living rooms and bedrooms) were measured in operation conditions, with the residents doing the regular activities in their houses. The study of thermal comfort of the dwellings is set using an adaptive analysis presented in EN15251:2007 [3, 4, 5]. This approach is valid for the analyzed dwellings, since they don t have mechanical cooling systems in operation, and the thermal conditions in the rooms are regulated by the occupants through opening and closing of windows. There have been some similar studies regarding the study of the variability on indoor air temperature in situ measurements: from Sept. 2009 to March 2011, Kalamees et al. [6], measured in one-hour intervals over one-year period in bedrooms, the indoor air temperature and relative humidity in 41 apartments in 29 apartment buildings in Estonia. The average indoor temperature during summer, from all measured houses was +24.6ºC (hourly values varied between +14.6ºC and +34.1ºC and standard deviation was 2.6ºC), and during winter varies from +20ºC (at T out-25ºc) to +22ºC (at T out+15ºc). According to Sung-Hyon H. [7], 3 to 4 week fuel consumption and temperature data were collected from some 1500 dwellings, over two successive winters in 2001/2002 an 2002/2003, under the government-funded British project named Warm Front. The results show that the Warm Front Scheme resulted in a mean increase of 1.6ºC in indoor temperature. There are, however, few studies of the variability on indoor air temperature in climates with warm summers and mild winters, with particular focus on residential multi storey buildings in which the dwellings have very similar characteristics. 2. Case Study The selected case study is a social housing neighborhood located in Porto, Portugal, that is part of a large social housing retrofitting program that is being conducted by local authorities. The program involves the intervention in a considerable number of social housing neighborhoods, in order to improve the quality of life of 35.000 persons living in 13.000 houses, owned by the city. The neighborhood was originally built in 1978. It consists in 4 multi-storey housing blocks, with a total of 179 dwellings with typologies that vary from T1 to T5, in which live about 450 inhabitants. The retrofitting works were concluded in 2011 [1]. The buildings were subjected to an envelope retrofitting (façades, roofs and windows) that could preserve the original appearance of the façade, and at the same time could increase the building s energy efficiency and the thermal comfort of the residents. The original solution before retrofitting included cavity walls without thermal insulation, pitched roofs covered with asbestos plaques without thermal insulation, and windows in wood frame with single glazing (the solar factor is 0.85). After retrofitting, the façade walls were kept cavity walls without thermal insulation (U-value=1.3 W/m 2 ºC); pitched roofs were covered with insulated aluminum panel sandwiches and insulated at the ceiling level with 80 mm of MW (U-value=0.45 W/m 2 ºC). The windows were replaced by aluminum frames with double glazing (U- value=2.8 W/m 2 ºC) [1]. Collective residential mechanical ventilation fans were applied in the kitchens, Bathrooms were equipped with extractor s fans operated manually by the user, and self-regulating air vents were applied in the roller blind boxes of living rooms and bedrooms [1]. This type of dwellings, due to climate and socio-economic context, are not operated with continuous heating or cooling systems. 3. Thermal comfort analysis The graphics presented in Figure 2 illustrate the study of thermal comfort for the 3 apartments placed in a vertical alignment throughout the 3 months of winter and summer measurements. The apartments are located in the same vertical alignment, have the same geometry, room orientation and occupation (Figure 1).

2792 António Curado et al. / Energy Procedia 78 ( 2015 ) 2790 2795 Fig. 1. Location of the apartments in the same vertical alignment Each point on the graphic corresponds to a experimental measurement, obtained for the period between December 1st and February 28th for winter measurements, and between June 1st and September 30th for the summer measurements. Fig.2. (a) Thermal comfort according to EN15251 - Winter; (b) Thermal Comfort according to EN15251 - Summer. According to the graphics in Figure 2, the thermal comfort in the 3 apartments located in the same vertical alignment is quite reduced for the winter season and very high for the summer season. The fact that the percentage of discomfort for the summer season is very low for the 3 locations is due to the roof insulation. The upper floor apartment reveals a similar thermal behavior as the others. 4. Indoor air temperature variability analysis 4.1. Methodology The continuous indoor air temperature measurements, in 2 different periods of the year, of a set of 24 representative dwellings of a social housing neighborhood, measured with the residents doing their regular activities, provided a wide range of results which can be used to develop a study of the variability of the indoor air temperature. The measurement results allowed us to establish the following study of variability: Influence of the location of the apartments in a vertical and horizontal alignment in its thermal performance, referred in a simplified way as height and room location, respectively, and influence of the occupation of the apartments in its thermal performance, referred as occupation ; For the height analysis the study is done for 3 similar apartments with the same occupation and room orientation, placed in a vertical alignment, over a period of 3 months, both for summer and winter conditions (Section 4.2). For the room location analysis the study is done for 3 similar apartments with the same occupation and height, placed in the same horizontal alignment over different periods of 2 weeks, both in summer and winter conditions (Section 4.3). And finally for the occupation analysis, the study is done for 6

António Curado et al. / Energy Procedia 78 ( 2015 ) 2790 2795 2793 similar apartments with the same height and orientation but different occupation over different periods of 2 weeks, both in the summer and winter conditions (Section 4.4). 4.2. Influence of the location in a vertical alignment on variability To study the influence of the location of the apartments in a vertical alignment on the indoor air temperature, it was selected 3 apartments measured for three months (summer and winter) and compared the results. The apartments are located in the same vertical alignment, have the same geometry, room orientation and occupation (Figure 1). The graphics in Figure 3 represent the curve of cumulative frequencies of variability of the parameter T i-t out ( C) in a bedroom facing southwest for a period of 3 months, both for winter and summer measurements. By the analysis of the curves, it s possible to identify a higher temperature variation for summer measurements. Fig. 3. (a) Percentiles T i-t out(ºc) - Winter; (b) Percentiles T i-t out(ºc) - Summer. The results presented in Figure 3 highlight the percentiles of cumulative frequency of the parameter T i - T out ( C), for the 3 apartments located in the same vertical alignment, called Roof floor apartment (ROOF), Middle floor apartment (MID) and Ground floor apartment (GRD). For the winter season, the percentile 50 (median) of the parameter T i - T out ( C) records for 3 apartments, a difference of only 0.2ºC. This difference is slightly more pronounced in percentiles 10 and 90, but does not exceed 0.4ºC. In the summer season the difference in percentile 50 (median) is 1.0ºC (0.2ºC for the winter). This difference is generally maintained for the remaining percentile analysis results. From the analysis of the presented results it seems to exist, for the summer measurement period, a higher variability of Ti - T out ( C) compared to the winter period. 4.3. Influence of the location in a horizontal alignment on variability To study the influence of the location of the apartments in a horizontal alignment on the variation of indoor air temperature, it was selected 3 apartments measured in small periods of two weeks both for summer and winter season, and compared the results for the indoor air temperature measurements. The apartments are located on the roof floor of the building and placed in a current zone (apartment referred to be as "center") and in two opposite gables (apartments called "Gable NW" and "Gable SE"). The study evaluated the variability on the parameter T i - T out ( C), according to the graphics presented in Figure 4.

2794 António Curado et al. / Energy Procedia 78 ( 2015 ) 2790 2795 Fig. 4. (a) Percentiles T i-t out(ºc) - Winter; (b) Percentiles T i-t out(ºc) - Summer. The analysis of the results presented in Figure 4 allows the detection of a considerable dispersion in the value of the parameter T i - T out ( C). For the winter season this dispersion reaches a 2.6ºC value for the median, a value close to 3 C to the percentile 90, and a value of 2.5ºC for the percentile 10. The study of the results shows that the effect of the location of the apartments in a horizontal alignment is considerable. As expected the apartment called "center", with smaller shape factor, is the warmest in the considered measurement period. The variation is also notorious for the summer season, with the percentile 50 values achieving a difference between apartments of 3.0 C. In the other percentiles the difference reaches values near 5 C (4.8 C for the percentile 10). The study of the results for the summer season is in line with that recorded for the winter period; it appears that there is a pronounced effect on the location of the room in a horizontal alignment, on the variation of the indoor air temperature. The apartment called "Center", located in current zone, with smaller shape factor, is less warm during the measurement period considered for analysis. 4.4. Influence of the occupation on variability To study the influence of the occupation on the variation of indoor air temperature, it was selected 6 apartments measured in small periods of two weeks both in the summer and winter season, and compared the measurement results of the parameter T i-t out ( C). The apartments are located on the roof floor of the building (apartments referred to be as "A", "B", "C", "D", "E" and "F"), according to the graphic presented in Figure 5. Fig. 5. (a) Percentiles T i-t out(ºc) - Winter; (b) Percentiles T i-t out(ºc) - Summer. For the winter season, the results presented in Figure 5 show a marked variation of the parameter T i-t out ( C) for the studied percentiles. Apartments "A" and "C" are, respectively, the warmest apartment and the coldest during the analysis period. For the apartments "A" and "C", the median shows a variation of 2.6ºC, a variation of 2.9ºC for the percentile 90, and a variation of 2.5 C for the percentile 10. The results are consistent with the level of occupancy of the apartments. According to the graphics in Figure 4, the apartment "A" is the most occupied of the sample (5 pax.), and the apartment "C" the least one (only1 pax.). In summer season the apartments "A" and "F" are respectively, the

António Curado et al. / Energy Procedia 78 ( 2015 ) 2790 2795 2795 warmest apartment and the coldest for the analysis period. The median and the percentile 90 have, for the apartments "A" and "F", a variation of 2.9ºC, and the percentile 10, a variation of 4.3 C. Like the results obtained for the winter season, in summer the results are consistent with the level of occupancy of the apartments. The warmest apartment is the most occupied of the sample (Apartment "A"), and the coldest apartment is one of the least occupied of the sample (Apartment "F"). 5. Conclusions The experimental campaign that took place in Bairro de Lordelo produced a very wide range of measurement results, which allowed the study of the thermal comfort and the variability of the indoor air temperature, for a set of occupied apartments, during summer and winter season, in a free floating system. The study allowed the following conclusions: In buildings without heating systems installed, the occupation seems to be the most important variable on the indoor air temperature variation. A set of apartments with the same geometry, similar location and solar orientation, but with different people occupation, can have an indoor air temperature variation that exceeds 4.0 ºC, both in winter and in summer time. This variable reveals to be more important on thermal comfort analysis than the shape factor of the apartments, studied for a vertical and a horizontal alignment of the apartments.. The influence of the location of the apartments in a vertical alignment reveals very small differences, not exceeding 1.0 ºC, and in a horizontal alignment shows differences close to 2.5ºC. T i T out indoor air temperature (ºC) outdoor air temperature (ºC) U-value heat transfer coefficient (W/m 2 ºC) T oc indoor operative temperature (ºC) exponentially-weighted running mean of the outdoor temperature (ºC) References [1] Freitas, V.P.. Projeto de Reabilitação do Bairro de Lordelo do Ouro. Porto, Portugal. 2007-2009. [2] Curado, A.. Conforto Térmico e Eficiência Energética nos Edifícios de Habitação Social Reabilitados. A Thesis submitted for the Degree of Doctor of Philosophy to the University of Porto. Porto, Portugal; 2014. [3] CEN - COMITÉ EUROPÉEN DE NORMALISATION. EN 15251:2007 Indoor environmental input parameters for design and assessment of energy performance of buildings-addressing indoor air quality, thermal environment, lighting and acoustics. CEN, Brussels, Belgium; 2011. [4] BOERSTRA A.. The adaptive thermal comfort criterion in the new EPBD IEQ standard. In: Proceedings of NCEUB Windsor conference 2006, Comfort and Energy Use in Buildings. Getting them Right. Windsor, UK; 2006. [5] BRAGER, G.; DE DEAR, R.. Thermal adaptation in the built environment: a literature review. In: Energy and Buildings, 27 (1), pp. 83-96; 1998. [6] Kalamees T.; Arumagi E.;.Ilomets S.. The Analysis of Indoor hygrothermal conditions in multi-storey wooden apartments buildings. In: Annex 55 Working Meeting. Porto, Portugal; 2011. [7] Hong, Sung-Hyon. Changes in Space Heating Energy Consumption Following Energy Efficient Refurbishment in Low-Income Dwelling in England. A Thesis submitted for the Degree of Doctor of Philosophy to the Bartlet School of Graduate Studies, University College London. London, England; 2011.