ADA STANDARD: PARKS SERVICE CENTER GARAGE 4.15.5(1), Figs. 4(e) and 27(b) Accessible drinking fountain does not have a clear 30 wide floor space centered on the drinking fountain (centerline to the counter edge is 12 ). Shorten the counter width by 3 (min.) to provide clear 30 wide floor space centered on the drinking fountain. Photo of drinking fountain
PARKS SERVICE CENTER GARAGE ADA STANDARD: 4.23.7, 4.27.2, 4.27.3, 4.2.5 and Fig. 5, 4.2.6 and Fig. 6 Height to operating latch on first aid cabinet is more than 48 above the floor (measured at 59-1/2 ). Adjust height of first aid cabinet so highest closed operable latch is not more than 48 above the floor. Photo of Parks Service Center
PARKS SERVICE CENTER GARAGE ADA STANDARD: 4.35.2, 4.35.4 Insufficient maneuvering clearance is provided between the edges of the benches and the lockers (measured at 54 ). A 24 x 48 bench is not provided for handicapped users (measured at 9-1/2 x 36 ). Adjust the benches so that a minimum of 60 turning diameter is provided within the locker room. Install a 24 x 48 bench for handicapped users to replace one or both of the existing two benches. Photo of Parks Service Center
ROBERT E. BURKE MEMORIAL PARK Photo of Robert E. Burke Memorial Park
ITEM: ADA GUIDELINE: ROBERT E. BURKE MEMORIAL PARK N/A N/A N/A N/A Photo of park
SHERIDAN PARK Photo of Sheridan Park
ITEM: SHERIDAN PARK ACCESSIBLE ROUTE ADA GUIDELINE: 4.1.2(1), 4.3 An accessible path is not provided to the picnic tables in the park. Add an accessible path to the picnic tables in the park. Photo of Picnic Tables in south portion of park
ITEM: SHERIDAN PARK PICNIC TABLE ADA GUIDELINE: 5.5, 306, 902.2, 902.3 An accessible space is not provided in the picnic table grouping that permits a wheelchair to pull under the end of one of the table sides. Remove one of the seat and horizontal arm assemblies to provide an accessible wheelchair space. Photo of Picnic Tables in south portion of park
A.C. NIELSEN TENNIS CENTER Photo of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.1.3(1), 4.3.8 Second floor to Tennis Center has no lift or elevator (square footage is approximately 5115 sq. ft. on second floor). Install lift or elevator to second floor. Photo of second floor of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.13.9 Door knob on first floor boiler room door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor boiler room door of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.13.9 Door knob on first floor manager s office door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor manager s office door of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.13.9 Door knob on first floor storage room door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor storage room door of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.13.9 Door knob on first floor AED closet room door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor AED closet room door of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.13.9 Door knob on second floor closet in southeast corner is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of storage room door on southeast corner of second floor of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.13.9 Door knob on top of second floor stairwell in northwest corner is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door at top of stairwell at northwest corner of second floor of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.13.9 Door knob on second floor hallway at southeast corner is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on hallway second floor in southeast corner of A.C. Nielsen Tennis Center
ADA STANDARD: A.C. NIELSEN TENNIS CENTER 4.15.5(1), Figs. 4(e) and 27(b) Drinking fountain inside east side of the center of the building entrance is not accessible since the unit does not allow 27 of wheelchair access under the unit. Install new drinking fountain that has 27 of wheelchair access under the unit. Photo of drinking fountain inside the east side of the center of A.C. Nielsen Tennis Center
ADA STANDARD: A.C. NIELSEN TENNIS CENTER 4.15.5(1), Figs. 4(e) and 27(b) Drinking fountain in aisle between the tennis courts is not accessible since the unit does not allow 27 of wheelchair access under the unit and the spout is higher than 36 above floor (measured at 46 to spout). Install new drinking fountain that has 27 of wheelchair access under the unit and a spout no higher than 36 above the floor. Photo of drinking fountain in the aisle between the tennis courts of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.4.1 Boxes over thermostats in southeast corner of second floor project out more than 4 and are above 27 high. Replace covers with models that do not project out more than 4 from wall. Photo of thermostat boxes in second floor southeast corner of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.4.1 Five fire extinguishers on throughout building project out more than 4 and are higher than 27 above the floor (measured at 43 above floor). Lower 5 fire extinguishers so the bottom edges are no more than 27 above the floor. Photo of fire extinguisher on second floor of A.C. Nielsen Tennis Center
A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.19.6 Mirrors in restrooms are mounted higher than 40 to bottom reflecting surface (measured at 45 to ground). Lower bottom edges of mirrors to 40 above ground. Photo of mirror in restrooms of A.C. Nielsen Tennis Center
ADMINISTRATIVE OFFICE Photo of Administrative Office
ADMINISTRATIVE OFFICE ADA STANDARD: 4.19.2 West women s single user restroom sink exceeds 34 height above floor (measured at 35 ). Lower sink to 34 height above floor. Photo of west women s single user restroom
ADMINISTRATIVE OFFICE ADA STANDARD: 4.19.6 All four (4) single user restroom mirrors exceed 40 height above floor (measured at 41 ). Lower mirrors to 40 height above floor. Photo of east women s single user restroom
ADMINISTRATIVE OFFICE ADA STANDARD: 4.19.4, 4.17.6 Horizontal grab bars in two (2) west single user restrooms are less than 36 long (measured at 30 ). Install 36 long horizontal grab bars. Photo of west men s single user restroom
ADMINISTRATIVE OFFICE ADA STANDARD: 4.25.3 Coat hooks in all four (4) single user restrooms exceed 54 height above floor (measured at 63 ). Either lower existing coat hooks to 54 height above floor or add new hooks at 54 height above floor. Photo of east men s single user restroom
BALLFIELD STORAGE - SHELTER Photo of Ballfield Storage - Shelter
BALLFIELD STORAGE - SHELTER ADA STANDARD: 4.1.6(3)(d)(ii), 4.13.8 Threshold at building entrance exceeds ¾ height (measured at 3 high). Install gravel, concrete or asphalt ramp to top of threshold and into the building. Photo of double door entry
BALLFIELD STORAGE - SHELTER ADA STANDARD: 4.3.8 Elevation change between concrete pad and adjacent gravel exceeds ½ height. Install gravel to meet height of concrete pad. Photo of north side
BALLFIELD STORAGE- -SHELTER ADA STANDARD: 4.4.1 Building logs project out greater than 4 into accessible pathways above 27 from floor (measured at 29 and 37 ). Install barriers so the top of the barricade is at 27 or below underneath building projections. Photo of south side
CART BARN Photo of Cart Barn
CART BARN ADA STANDARD: 4.13.5, 4.13.6 Hose hook located inside door inside southwest corner of Cart Barn does not allow 32 clear passage and maneuvering room. Relocate hose hook location away from the door to allow 32 clear passage. Photo of southwest corner of interior
CART BARN ADA STANDARD: 4.13.9 Southwest and northeast pedestrian doors have round handles which are difficult for the disabled to grasp. Replace door handles with lever-style handles. Photo of southwest door
CART BARN ADA STANDARD: 4.4.1 Hose reel projects out more than 4 and has bottom edge higher than 27 above the floor. Lower hose reel so bottom edge is below 27 above the floor. Photo of hose reel
CART BARN ADA STANDARD: 4.4.1 Fire extinguisher next to southwest door projects out more than 4 and has bottom edge higher than 27 above the floor (measured at 30 ). Lower fire extinguisher so bottom edge is below 27 above the floor. Photo of southwest fire extinguisher
CART BARN ADA STANDARD: 4.4.2 Double vent on west wall of building projects out more than 4 and is below 80 above the floor. Install barrier below double vent with bottom edge below 27 above the floor (i.e. panels on sides of vent or bumpers or bollards on floor. Photo of double wall vent
CART BARN ADA STANDARD: 4.4.1 Hose hook projects out more than 4 with bottom edge higher than 27 above the floor. Relocate hose hook to a new location with bottom edge below 27 above the floor. Photo of hose hook
CELL PHONE BUILDING - NORTH Photo of Cell Phone Building - North
CELL PHONE BUILDING - NORTH ADA STANDARD: 4.1.2(1), 4.3, 4.3.8, 4.1.3(1) Stairs to door at south side of building are not accessible (5 risers at 8 each are more than the ½ maximums required). Add a ramp to north cell phone building (and south cell phone building) to berm and top of stairs. Photo of stairs
CELL PHONE BUILDING - NORTH ADA STANDARD: 4.13.6, Fig. 25 On latch pull side of door, there is not 18 of clearance to edge of stair tread (measured at 6 ). Rebuild railings and stairs to provide a full clearance of 18 from edge of latch pull side of door to edge of stair tread and 48 clearance from building to railings. An alternative is to flip door hinge/latch sides and add concrete extension on uphill side of landing to 18 from latch side of door. Photo of stairs
CELL PHONE BUILDING - SOUTH Photo of Cell Phone Building - South
CELL PHONE BUILDING - SOUTH ADA STANDARD: 4.1.2(1), 4.3, 4.3.8, 4.1.3(1) Stairs to door at south side of building are not accessible (5 risers at 8 each are more than the ½ maximums required). Add a ramp to south cell phone building (and north cell phone building) to berm and top of stairs. Photo of stairs
CELL PHONE BUILDING - SOUTH ADA STANDARD: 4.13.6, Fig. 25 On latch pull side of door, there is not 18 of maneuvering clearance to edge of landing (measured at 6 ). Also, there is a hole in concrete landing. Add paving to 18 from edge of latch pull side of door. Fill in hole. Photo of stairs
CLUBHOUSE Photo of Clubhouse
CLUBHOUSE ADA STANDARD: 4.4.2 Overhanging trees on the path to the clubhouse from the parking lot have branches below 80 height. Cut any branches overhanging the path to above 80 height. Photo of path looking west from the parking lot to the Clubhouse
CLUBHOUSE ADA STANDARD: 4.3.8 Pavement adjacent to the driving range ball dispenser is uneven and not level with adjacent concrete pad. Add asphalt to bring surface level with adjacent concrete pad to permit user to get closer to dispenser. Photo of driving range ball dispenser on east side
CLUBHOUSE ADA STANDARD: 4.4, 4.2.1(3), 4.1.3(2) Exterior light fixtures and hanging flower baskets project into accessible routes over 4 and are located between 27 and 80 above the ground (measured at 8 projection and 65 high to the bottom of the light fixtures and 28 projection and 72 high to the bottom of the flower baskets). Replace light fixtures with style that does not project more than 4 into an accessible route. Raise hanging baskets to above 80 ground or relocate to other locations where at least 80 exists. Photo of exterior column on front porch
CLUBHOUSE ADA STANDARD: 4.1.3(1), 4.1.6(3)(d)(ii), 4.13.8 West entrance to the Clubhouse is not accessible (threshold to doors exceeds ¾ height; measured at 6 risers) and has no sign directing user to the accessible entrance (main south entrance). Install a permanent sign directing disabled users to the main south entrance. Photo of west entrance
CLUBHOUSE ADA STANDARD: 4.1.3(1), 4.13.6, Fig. 25 North entrance to the Clubhouse is not accessible (insufficient clearance of 18 on latch side of the door; measured at 6 ) and has no sign directing user to the accessible entrance (main south entrance). Install a permanent sign directing disabled users to the main south entrance or add pavement to latch side of door to provide a minimum of 18 clearance. Photo of north entrance
CLUBHOUSE ADA STANDARD: 4.1.3(1), 4.1.6(3)(d)(ii), 4.13.8 North entrance to the Clubhouse pro s office is not accessible (threshold exceeds ¾ due to settled asphalt outside the door) and has no sign directing user to the accessible entrance (main south entrance). Install a permanent sign directing disabled users to the main south entrance or add asphalt to top lip of concrete floor. Photo of north entrance to the pro s office
CLUBHOUSE ADA STANDARD: 4.13.6 Clearance space on the pull side of the latch side of the north office door is less than 18 (measured at 4 ) due to drawer unit and shelf unit. Relocate drawer and shelf unit to provide a minimum of 18 clearance on the latch side of the door. Photo of north office
CLUBHOUSE ADA STANDARD: 4.13.6 Clearance space on the pull side of the latch side of the door is less than 18 (measured at 5 ) due to metal shelving unit. Relocate shelving unit to provide a minimum of 18 clearance on the latch side of the door. Photo of kitchen storage room
CLUBHOUSE ADA STANDARD: 4.13.6 Clearance space on the pull side of the latch side of the door from the hallway into the kitchen area is less than 18 (measured at 2 ) due to pop boxes. Relocate pop boxes to provide a minimum of 18 clearance on the latch side of the door. Photo of door from hallway to kitchen area
CLUBHOUSE ADA STANDARD: 4.13.6 Clearance space on the pull side of the latch side of the door from the pro s office into the driving range machine room is less than 18 (measured at 3 ) due to lockers. Relocate double height locker to provide a minimum of 18 clearance on the latch side of the door. Photo of pro s office driving range machine door
CLUBHOUSE ADA STANDARD: 4.13.9 The round knob on the door into the driving range machine room is hard to grasp for the disabled. Replace the door knob with a lever type to match the other door knobs in the Clubhouse. Photo of pro s office driving range machine door
CLUBHOUSE ADA STANDARD: 4.13.6 Clearance space on the pull side of the latch side of the pro s office storage door is less than 18 (measured at 6 ) due to display units. Relocate display units to provide a minimum of 18 clearance on the latch side of the door. Photo of pro s office storage room
CLUBHOUSE ADA STANDARD: 4.4.1 Interior wall lights (total of 3) in rear hallways project out further than 4 with the bottom edge of the fixture between 27 and 80 above the floor (measured at 10-1/2 projection and 62-1/2 above the floor). Replace fixtures with units that do not project more than 4 from the wall or install with the bottom of the light above 80 from the floor. Photo of rear hallway
CLUBHOUSE ADA STANDARD: 4.4.1 Interior wall lights (total of 4) in the classroom project out further than 4 with the bottom edge of the fixture between 27 and 80 above the floor (measured at 7 projection and 79 above the floor). Replace fixtures with units that do not project more than 4 from the wall or install with the bottom of the light above 80 from the floor. Photo of classroom
CLUBHOUSE ADA STANDARD: 4.4.1 Fire extinguisher in rear hallway projects out further than 4 with the bottom edge of the fixture between 27 and 80 above the floor (measured at 5 projection and 33 above the floor). Reset fire extinguisher with the bottom edge at 27 above the floor. Photo of north hallway fire extinguisher