Secondary Suites Changes between the 2006 ABC and the 2014 ABC Requirements

Size: px
Start display at page:

Download "Secondary Suites Changes between the 2006 ABC and the 2014 ABC Requirements"

Transcription

1 Secondary Suites Changes between the 2006 ABC and the 2014 ABC Requirements Alberta Building Code 2006 Alberta Building Code 2014 Change Construction Height of Rooms and Spaces 1) The height of rooms or spaces in a secondary suite over the required minimum area in accordance with Table shall be not less than 1.95 m Ceiling Heights of Rooms or Spaces 1) Except as provided in Sentences (2) and (3), the ceiling heights and clear heights in rooms or spaces in residential occupancies shall conform to Table ) Ceiling heights in secondary suites shall be not less than 1.95 m. 3) Clear heights under beams and ducting in secondary suites shall be not less than 1.85 m. 4) Areas in rooms or spaces over which ceiling height and clear height are not less than the minimum specified in Table or Sentence (2) or (3) shall be contiguous with the entry or entries to those rooms or spaces. Reduction of ceiling height from 1.95m to 1.85m under beams and ductwork Door Heights 1) Except where the height of rooms or spaces in a secondary suite is less than the minimum height listed in Table , doors within dwelling units shall conform to subsection Bedroom Windows 1) Except as permitted in Sentence (1), each bedroom within a secondary suite shall have at least one outside window that meets the requirements of Articles and Doorway Opening Sizes 1) Except as provided in Sentence (2) and Articles , and , doorway openings within dwelling units and within houses with a secondary suite including their common spaces shall be designed to accommodate at least the door sizes given in Table for swing-type and folding doors.in Division B 2) Doorway openings within secondary suites shall be designed to accommodate swing-type and folding doors not less than mm high where the ceiling height complies with Sentence (2) Egress From Bedrooms Egress Windows or Doors for Bedrooms 1) Except where the suite is sprinklered, each bedroom or combination bedroom shall have at least one outside window or exterior door openable from the inside without the use of keys, tools or special knowledge and without the removal of sashes or hardware. (See Article and Appendix A.) Reduction of door height from 1980 to 1890 when door is located under a beam or ductwork Landings 1) Landings for stairs shall be at least as wide as the stairs and not less than 900 mm in length Dimensions of Landings (See Articles and regarding landings in exits.) 1) Except as provided in Sentences (2) to (6), the width and length of landings shall comply with Table (See Appendix A.) 2) Widths and lengths of landings serving a house with a secondary suite including their common spaces shall comply with the requirements in Table that apply to dwelling units. Reduced from 900 to 860 in length. 1

2 Handrails and Guards 1) Handrails and guards shall conform to the requirements of Subsections and Handrails Guards Public and Exit Corridor Width 1) The clear width of every public corridor and exit corridor shall be not less than 860 mm Hallways Hallway Width 1) The unobstructed width of a hallway within a dwelling unit shall be not less than 860 mm, except that the hallway width is permitted to be 710 mm where a) there are only bedrooms and bathrooms at the end of the hallway furthest from the living area, and b) a second exit is provided i) in the hallway near the end farthest from the living area, or ii) in each bedroom served by the hallway. 2) The unobstructed width of a hallway within a common space of a house with a secondary suite shall be not less than 860 mm Unenclosed Exterior Stair or Ramp 1) Where an unenclosed exterior exit stair or ramp provides the only means of egress from a secondary suite and is exposed to the hazards of fire from unprotected openings in the exterior wall of the primary dwelling unit, the openings shall be protected in conformance with Articles and Openings Near Unenclosed Exterior Exit Stairs and Ramps 1) Unprotected openings in exterior walls of the building shall be protected with wired glass in fixed steel frames or glass block conforming to Articles and , where a) an unenclosed exterior exit stair or ramp provides the only means of egress from a suite and is exposed to fire from unprotected openings in the exterior walls of i) another fire compartment, or ii) another dwelling unit, ancillary space or common space in a house with a secondary suite, and b) unprotected openings in the exterior walls of the building are within 3 m horizontally and less than 10 m below or less than 5 m above the exit stair No change Exit Doors 1) Every exit door or door that provides access to exit from a secondary suite shall be a) not less than mm high, b) not less than 810 mm wide, and c) permitted to swing inward Doorway Opening Sizes 1) Except as provided in Sentence (2) and Articles , and , doorway openings within dwelling units and within houses with a secondary suite including their common spaces shall be designed to accommodate at least the door sizes given in Table for swing-type and folding doors Division B 2) Doorway openings within secondary suites shall be designed to accommodate swing-type and folding doors not less than mm high where the ceiling height complies with Sentence (2). 2

3 Travel Limit 1) The travel limit from a floor level in a dwelling unit to an exit or egress door may exceed 1 storey where that floor level is served by an openable window conforming to Sentence (2) Travel Limit to Exits or Egress Doors 4) The travel limit from a floor level in a house with a secondary suite to an exit or egress door may exceed 1 storey where that floor level is served by an openable window conforming to Sentence (2) Means of Egress 1) Except as permitted in Sentence (2), each dwelling unit shall be provided with at least one exit that leads directly to the outside. 2) Dwelling units may share a common exit meeting the requirements of Article Two Separate Exits 1) Except as provided in Sentence (1) and except for dwelling units in a house with a secondary suite, where an egress door from a dwelling unit opens onto a public corridor or exterior passageway it shall be possible from the location where the egress door opens onto the corridor or exterior passageway to go in opposite directions to 2 separate exits unless the dwelling unit has a second and separate means of egress Shared Egress Facilities 1) A dwelling unit need not be provided with a second and separate means of egress referred to in Article where the dwelling unit is provided with not less than one exit as required by Article Shared Egress Facilities 1) Except for dwelling units in a house with a secondary suite, a dwelling unit shall be provided with a second and separate means of egress where an egress door from the dwelling unit opens onto a) an exit stairway serving more than one suite, b) a public corridor i) serving more than one suite, and ii) served by a single exit, c) an exterior passageway i) serving more than one suite, ii) served by a single exit stairway or ramp, and iii) more than 1.5 m above adjacent ground level, or d) a balcony i) serving more than one suite, ii) served by a single exit stairway or ramp, and iii) more than 1.5 m above adjacent ground level. 2) Where a dwelling unit is located above another dwelling unit or common space in a house with a secondary suite, the upper dwelling unit shall be provided with a second and separate means of egress where an egress door from that dwelling unit opens onto an exterior passageway that a) has a floor assembly with a fire-resistance rating less than 45 min, b) is served by a single exit stairway or ramp, and c) is located more than 1.5 m above adjacent ground level. Sentence 2 is new 3

4 Protection of Exits 1) Every exit, other than an exit doorway, shall be separated from adjacent floor areas by not less than one layer of 12.7 mm thick gypsum wallboard or equivalent material on each side of the walls. (See Appendix A.) Fire Separations for Exits 2) Where an exit is located in a house with a secondary suite including their common spaces, the exit shall be protected by a continuous smoke-tight barrier of not less than 12.7 mm thick gypsum board installed on a) both sides of walls separating the exit from the remainder of the building, b) the underside of floor-ceiling framing separating the exit from the remainder of the building. Clarifies that the barrier between the dwelling units has to be smoke tight and that drywall has to be used. The word equivalent has been deleted Exit Signs 1) Exit signs referred to in Subsection are not required within a building that contains a secondary suite Signs Application 1) This Subsection applies to all exits except those serving not more than one dwelling unit or a house with a secondary suite Emergency Lighting 1) Emergency lighting referred to in Subsection is not required within a building that contains a secondary suite Lighting Application 1) This Subsection applies to the lighting of all means of egress except those within dwelling units or a house with a secondary suite Dwelling Unit Separations 1) Dwelling units shall be separated from each other by not less than one layer of 12.7 mm thick gypsum wallboard or equivalent material on the ceiling and on each side of the walls. (See A (1) in Appendix A.) 2) Table does not apply to a dwelling unit within a building that contains a secondary suite Separation of Residential Suites 4) Walls and floor-ceiling framing in a house with a secondary suite that separate dwelling units from each other or dwelling units from ancillary spaces and common spaces need not comply with Sentence (1), where the walls and floor-ceiling framing are protected by a continuous smoke-tight barrier of not less than 12.7 mm thick gypsum board installed on a) both sides of walls, and b) the underside of floor-ceiling framing. (See Sentence (2) for closures.) Clarification that the barrier is to be smoketight Protection of Public Corridors 1) A public corridor shall be separated from the remainder of the building by not less than one layer of 12.7 mm thick gypsum wallboard or equivalent material on each side of the walls. (See A (1) in Appendix A.) Separation of Public Corridors 4) Where a public corridor is located in a house with a secondary suite, a continuous smoke-tight barrier of not less than 12.7 mm thick gypsum board shall be installed on a) both sides of walls separating the corridor from the remainder of the building, and b) the underside of floor-ceiling framing separating the corridor from the remainder of the building. (See Sentence (2) for closures.) Clarification that the barrier is to be smoketight. 4

5 Heating and Ventilation Systems 1) Each dwelling unit shall have an independent heating and ventilation system complying with Sections and (See Appendix A.) Required Ventilation 1) Every residential occupancy shall incorporate a) provisions for non-heating-season ventilation in accordance with Subsection , and b) except as required by Sentences (2) and (3), if supplied with electrical power and a heating system, provisions for heating-season ventilation in accordance with Part 6. 2) A self-contained heating-season ventilation system serving a single dwelling unit shall comply with Subsection (See Appendix A.) 3) In houses that contain a secondary suite, heating-season ventilation need not be provided for a) exits, b) public corridors, and c) ancillary spaces that are not within a dwelling unit, except as provided in Sentence (4). (See A (2) in Appendix A.) 4) Where ancillary spaces described in Clause (3)(c) contain exhaust devices, these spaces shall be provided with make-up air in accordance with Article Clarification of heating and ventilation requirements Solid Blocking 1) Solid blocking may be omitted for doors described in Sentence (1), where the interior wall finish adjacent to the door is in place prior to the construction of the secondary suite Resistance to Forced Entry for Doors 9) Solid blocking shall be provided on both sides at the lock height between the jambs for doors described in Sentence (1) and the structural framing so that the jambs will resist spreading by force. 10) Solid blocking may be omitted for doors described in Sentence (9), where the interior wall finish adjacent to the door is in place prior to the construction of a secondary suite. No changes Sound Control 1) Section does not apply to a building that contains a secondary suite Minimum Sound Transmission Class Ratings 2) This Section does not apply to the construction separating dwelling units within a house with a secondary suite. 3) Where a dwelling unit is adjacent to an elevator shaft or a refuse chute, the separating construction shall have a sound transmission class rating of at least 55, measured in accordance with Subsection or as listed in A in Appendix A. No changes Garages and Carports 1) Section applies to garages and carports serving a building that contains a secondary suite. 2) The requirements regarding fire resistance rating, type of construction and type of cladding shall not apply to the exposing building face of a building that contains a secondary suite facing a Application 1) This Section applies to garages and carports serving not more than one dwelling unit or a house with a secondary suite 5) Except as provided in Sentence (6), combustible projections on the exterior of a wall that are more than 1 m above ground level and that could expose an adjacent building to fire spread shall not be permitted within Clarification that the article applies to one dwelling unit or a house with a secondary suite. 5

6 detached garage or accessory building, where a) the detached garage or accessory building is located on the same property as that building, and b) the building served by the detached garage or accessory building is the only other building on the property a) 1.2 m of a property line or the centre line of a public way, or b) 2.4 m of a combustible projection on another building on the same property. 6) Except as provided in Sentences (8) to (10), Sentence (5) shall not apply to a) buildings containing 1 or 2 dwelling units only, and b) detached garages or accessory buildings, where i) the detached garage or accessory building serves only one dwelling unit or a primary dwelling unit with a secondary suite, ii) the detached garage or accessory building is located on the same property as that dwelling unit, and iii) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property. (See A (7) in Appendix A.) 6

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 08-03-1177 Application No. 2007-26 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Articles 3.4.4.1.,

More information

Regional District of Nanaimo Secondary Suite Program

Regional District of Nanaimo Secondary Suite Program Regional District of Nanaimo Secondary Suite Program Secondary suites are recognized for the important role they play in providing affordable housing in the region. They also provide many benefits to homeowners,

More information

CITY OF MOUNT PLEASANT ORDINANCE NO. 1017

CITY OF MOUNT PLEASANT ORDINANCE NO. 1017 CITY OF MOUNT PLEASANT ORDINANCE NO. 1017 AN ORDINANCE TO AMEND SECTIONS 152.004 AND 152.007 OF THE CODE OF ORDINANCES FOR THE CITY OF MOUNT PLEASANT TO ADOPT PROVISIONS OF THE 2012 INTERNATIONAL PROPERTY

More information

2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS

2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS 2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS Section 1001 ADMINISTRATIVE 1001.1 General 1001.2 Alterations to existing means of egress 1001.3 Maintenance 1001.4 Fire safety and evacuation plans

More information

Section 9.5. Design of Areas, Spaces and Doorways

Section 9.5. Design of Areas, Spaces and Doorways f):.-"> ~Ontario 2012 Building Code Compendium 9.5.1.5. 9.4.4.5. Reserved 9.4.4.6. Walls Supporting Drained Earth (See Appendix A.) Except where constructed in accordance with Section 9.15., walls supporting

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 09-03-1215 Application No. B-2009-01 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Sentences 3.3.1.3.(9)

More information

2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC.

2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC. 2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC. October 23, 2018 Section 1001. Administration. See Section 107.2.3 for Egress Drawing

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No.: 10-29-1265 Application No.: B-2010-24 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Clause 3.4.4.2.(2)(f)

More information

Presentation By. Chris Poujol. Jeffery Rodriguez. James Rigley

Presentation By. Chris Poujol. Jeffery Rodriguez. James Rigley Means of Egress Presentation By Chris Poujol Jeffery Rodriguez James Rigley Table of Contents I. Means of Egress Definition II. History III. NYC Building Code IV. General Requirements IX. Exit Signs X.

More information

The New NYC Building Code Chapter 10 Means of Egress. New York City Department of Buildings. Technical Affairs. Fatma M. Amer, P.E.

The New NYC Building Code Chapter 10 Means of Egress. New York City Department of Buildings. Technical Affairs. Fatma M. Amer, P.E. The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International

More information

Discuss the history of fires that resulted in much of the development of codes related to means of egress. Review mean of egress terminology

Discuss the history of fires that resulted in much of the development of codes related to means of egress. Review mean of egress terminology Discuss the history of fires that resulted in much of the development of codes related to means of egress Review mean of egress terminology Discuss 8 Elements to an Effective Means of Egress. Modern code

More information

E1-12: Final Decision AS

E1-12: Final Decision AS BCAC COMPILATION OF GROUP A E1-12: Final Decision AS 202, 1006 (New), 1007 (New), 1014.3, 1015, 1020.1, 1021 (IFC [B] 1006 (New), 1007 (New), 1014.3, 1015, 1020.1, 1021) Proponent: Charles S. Bajnai, Chesterfield

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 08-04-1178 Application No. B-2007-47 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND AND IN THE MATTER OF Sentence 3.2.9.2.(1)

More information

CHAPTER 4 LIGHT, VENTILATION & OCCUPANCY LIMITATIONS

CHAPTER 4 LIGHT, VENTILATION & OCCUPANCY LIMITATIONS CHAPTER 4 LIGHT, VENTILATION & OCCUPANCY LIMITATIONS Chapter 4 establishes the minimum criteria for light and ventilation and identifies occupancy limitations. * Indicates code is still under review for

More information

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS Prepared by: Community Development Standards Branch Town of Innisfil www.innisfil.ca June 2016 Contents 1. Introduction... 1 2. Ontario Building

More information

Vestibule Requirement Intent

Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration into a space

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 04-33-988 Application No. 2004-28 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.4.6.3.(2)

More information

ACCESSORY DWELLING UNITS

ACCESSORY DWELLING UNITS ACCESSORY DWELLING UNITS Category: Residential Construction Revised: [Paul L. Scarlett], Director Responsible Bureau Sections: Development Services Center 1900 SW Fourth Avenue Portland, OR 97201 503-823-7310

More information

(2) Determining Occupant Loads for the Operation of a Building (The Alberta Fire Code)

(2) Determining Occupant Loads for the Operation of a Building (The Alberta Fire Code) (d) (e) (f) (g) (h) if emergency lighting is required if exit signs are required if additional requirements apply for high buildings the type of hardware required on exit and access to exit doors the required

More information

UNIVERSITY OF HONG KONG LIBRARY. This book was received in accordance with the Books Registration Ordinance Section 4

UNIVERSITY OF HONG KONG LIBRARY. This book was received in accordance with the Books Registration Ordinance Section 4 UNIVERSITY OF HONG KONG LIBRARY This book was received in accordance with the Books Registration Ordinance Section 4 CODE OF PRACTICE ON PROVISION OF MEANS OF ESCAPE IN CASE OF FIRE AND ALLIED REQUIREMENTS

More information

Attic Floor Bedrooms 1 & 2 Family Dwellings

Attic Floor Bedrooms 1 & 2 Family Dwellings Habitable Room Definition (2015 MN Residential Code R202) A space in a building for living, sleeping, eating or cooking is considered a habitable space. Bathrooms, toilet rooms, closets, halls, storage

More information

Suite Permission. Suites complying with shall be permitted to be used to meet the corridor access requirements of

Suite Permission. Suites complying with shall be permitted to be used to meet the corridor access requirements of Categorical Waiver Available: 5. Suites Sections 18/19.2.5 of the 2000 LSC requires every habitable room to have an exit access door leading directly to an exit access corridor; allows for exit access

More information

The Secondary Suite Program

The Secondary Suite Program The Secondary Suite Program Recent surveys have shown that secondary suites provide up to 20% of all rental accommodation in the Lower Mainland. They provide many benefits to homeowners, tenants and the

More information

The Secondary Suite Program

The Secondary Suite Program The Secondary Suite Program Recent surveys have shown that secondary suites provide up to 25% of all rental accommodation in the Lower Mainland. They provide many benefits to homeowners, tenants and the

More information

A Guide to Secondary Suites

A Guide to Secondary Suites A Guide to Secondary Suites Introduction Building on the Saanich Official Community Plan (OCP) that supported secondary suites as a form of affordable housing, studies were undertaken in 2009 and in 2014.

More information

HOUSING CODE CHECKLIST FOR RENTAL INSPECTIONS

HOUSING CODE CHECKLIST FOR RENTAL INSPECTIONS HOUSING CODE CHECKLIST FOR RENTAL INSPECTIONS GENERAL 410.200 Heating facilities must be fully operational and well maintained with facilities capable of heating every room (including bathroom and kitchen).

More information

THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist.

THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist. Nova Scotia Building Accessibility Checklist Note OTE THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist.

More information

ACCESSORY DWELLING UNITS

ACCESSORY DWELLING UNITS ACCESSORY DWELLING UNITS Category: Residential Construction Revised: [Paul L. Scarlett], Director Responsible Bureau Sections: Development Services Center 1900 SW Fourth Avenue Portland, OR 97201 503-823-7310

More information

CHAPTER 10 ARTICLE II DIVISION 2: MINIMUM STANDARDS

CHAPTER 10 ARTICLE II DIVISION 2: MINIMUM STANDARDS CHAPTER 10 ARTICLE II DIVISION 2: MINIMUM STANDARDS Sec. 10-56. Fitness for dwelling, dwelling units. Every dwelling and dwelling unit intended for use as a human habitation, occupancy or use, or held

More information

DRS RWANDA STANDARD. Code of practice for fire safety. of building. Part 5: Exit requirements and personal hazard.

DRS RWANDA STANDARD. Code of practice for fire safety. of building. Part 5: Exit requirements and personal hazard. RWANDA STANDARD DRS 186-5 Seconde dition Code of practice for fire safety of building Part 5: Exit requirements and personal hazard Reference number DRS 186-5: 2018 RBS yyyy CD RS 186-5:2013 ii Error!

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-43-898 Application No. 2002-46 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.2.1.1.(4),

More information

NEW ACCESSIBILITY CHANGES

NEW ACCESSIBILITY CHANGES NEW ACCESSIBILITY CHANGES TO THE ONTARIO BUILDING CODE An outline of the accessibility changes made to the Ontario Building Code by Ontario Regulation 368/13. May 9, 2014 OAA CONFERENCE Continuing Education

More information

ADAPTABLE DESIGN GUIDELINES

ADAPTABLE DESIGN GUIDELINES ADAPTABLE DESIGN GUIDELINES Adaptable design creates liveable residences for a wider range of persons than current building codes require. By considering design features that can be easily and inexpensively

More information

RM-7, RM-7N and RM-7AN Districts Schedules

RM-7, RM-7N and RM-7AN Districts Schedules 1 Intent Districts Schedules The intent of this schedule is to encourage development of ground-oriented stacked townhouses or rowhouses, while continuing to permit lower intensity development. In RM-7AN,

More information

Rebuilding at a Zero Lot Line after the Wildfire Information Package

Rebuilding at a Zero Lot Line after the Wildfire Information Package Rebuilding at a Zero Lot Line after the Wildfire Information Package Background Issued: April 2017 A zero lot line is a residential development approach in which buildings are permitted to be located immediately

More information

Codes Checklist Document 3

Codes Checklist Document 3 Ohio University Interior Architecture Codes Check p1 of 7 atthew Ziff,.Arch, Associate Professor Codes Checklist Document 3 General Construction Code Requirements Construction type of Building (Table 601)

More information

RM-8 and RM-8N Districts Schedule

RM-8 and RM-8N Districts Schedule Districts Schedule 1 Intent The intent of this schedule is to encourage development of ground-oriented stacked townhouses or rowhouses, including courtyard rowhouses, while continuing to permit lower intensity

More information

2012 IBC Means of Egress

2012 IBC Means of Egress 12/11/2017 Introductions 2012 IBC Means of Egress Based on the 2012 International Building Code (IBC ) Instructor introduction Exits Cell phones & pagers Schedule & breaks Student introductions 2 Goal

More information

RT-11 and RT-11N Districts Schedules

RT-11 and RT-11N Districts Schedules Districts Schedules 1 Intent The intent of this schedule is to allow a variety of housing options by encouraging development of multiple small houses and duplexes on larger lots and assembled sites, while

More information

Copyright 2013, Queen s Printer for Ontario

Copyright 2013, Queen s Printer for Ontario Contact Information Building Code Information Officer, George Brown College BuildingCode@GeorgeBrown.ca 416-415-5000x6725 http://ce.georgebrown.ca/buildingcodeinformation This course is based on the Building

More information

Schedule C Barrier-Free Design

Schedule C Barrier-Free Design 1 Schedule C Barrier-Free Design As amended by Article 3.1.1.5. of these regulations Section 3.8 Barrier- Free Design of the Code is replaced with the following: Section 3.8 Barrier-Free Design 3.8.1.

More information

A By-law to amend Zoning and Development By-law No regarding Laneway Houses

A By-law to amend Zoning and Development By-law No regarding Laneway Houses Zoning & Development By-law Amendments regarding Laneway Houses Draft for Public Hearing A By-law to amend Zoning and Development By-law No. 3575 regarding Laneway Houses 1. This By-law amends or adds

More information

Tiny House on Wheels A Tiny House

Tiny House on Wheels A Tiny House TINY HOUSES November 2018 The term Tiny House means different things to different people. Some people use the term to refer to a Tiny House on Wheels while others refer to a smaller version of a detached

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 09-05-1217 Application No. 2009-03 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Article 3.3.1.15. and

More information

PROPERTY CONDITION CHECK LIST FOR A LICENCED HMO

PROPERTY CONDITION CHECK LIST FOR A LICENCED HMO PROPERTY CONDITION CHECK LIST FOR A LICENCED HMO Address of property:... Inspection date:... No of bedrooms desired:... 1. Minimum Bedroom Sizes Depending On Communal Space Bedrooms If the property has

More information

COUNCIL ORDER No

COUNCIL ORDER No SAFETY CODES COUNCIL #000, 0665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780430099 I 888430099 Fax: 78044534 I 88844534 www.safetycodes.ab.ca COUNCIL ORDER No. 005443 BEFORE THE BUILDINGTECHNICALCOUNCIL

More information

ERRATA AND REVISIONS MEASURES FOR FIRE SAFETY IN HIGH BUILDINGS

ERRATA AND REVISIONS MEASURES FOR FIRE SAFETY IN HIGH BUILDINGS National Research Council Canada Conseil national de recherches Canada Associate Committee on the NATIONAL BUILDING CODE of Canada Comite associe du CODE NATIONAL DU BATIMENT du Canada Ottawa ERRATA AND

More information

2.1 Alarm Source How was the alarm reported? UCT 911/ Phone, ERS, Class-3, BARS, Verbal.

2.1 Alarm Source How was the alarm reported? UCT 911/ Phone, ERS, Class-3, BARS, Verbal. SIZE-UP CHAPTER 2 December 7, 2013 1. INTRODUCTION Size-up begins with the receipt of the alarm and continues until the fire is under control. It is an ongoing process that may require modification as

More information

c 211 Hotel Fire Safety Act

c 211 Hotel Fire Safety Act Ontario: Revised Statutes 1970 c 211 Hotel Fire Safety Act Ontario Queen's Printer for Ontario, 1970 Follow this and additional works at: http://digitalcommons.osgoode.yorku.ca/rso Bibliographic Citation

More information

MANDATORY BUILDING STANDARDS FOR ADAPTABLE HOUSING

MANDATORY BUILDING STANDARDS FOR ADAPTABLE HOUSING MANDATORY BUILDING STANDARDS FOR ADAPTABLE HOUSING Effective June 1, 2004 Planning Department BASIC ADAPTABLE HOUSING SCHEDULE "F" TO ZONING BYLAW 8200 BASIC ADAPTABLE HOUSING The following Basic Adaptable

More information

WHEA Lunch & Learn Series JAN Lauzon Life Safety Consulting. Suites

WHEA Lunch & Learn Series JAN Lauzon Life Safety Consulting. Suites WHEA Lunch & Learn Series JAN-2017 Lauzon Life Safety Consulting Suites WHEA Lunch & Learn Series JAN-2017 Presenter Member: WHEA Code Committee WHEA Education Committee Lauzon Life Safety Consulting,

More information

Renovation Progress. May 5 11, Week 31

Renovation Progress. May 5 11, Week 31 Renovation Progress May 5 11, 2012 Week 31 May 5 A Saturday work day for these men tying rebar and building wood framing for the north porch slab May 5 New Infirmary hallway on 1 st Ottilia with most of

More information

West Pender Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law)

West Pender Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law) City of Vancouver Zoning and Development By-law Community Services, 453 W. 12th Ave Vancouver, BC V5Y 1V4 F 604.873.7344 fax 604.873.7060 planning@vancouver.ca CD-1 (468) 1409-1477 West Pender Street By-law

More information

Regulation Outline. Under section 59 of the Community Planning Act, the Lieutenant-Governor in Council makes the following Regulation:

Regulation Outline. Under section 59 of the Community Planning Act, the Lieutenant-Governor in Council makes the following Regulation: 1 Regulation Outline Citation....1 Definitions....2 Act Loi Code Code tourist establishment établissement touristique tourist home maison pour touristes Approval of building code....3 Interpretation....4

More information

RM-1 and RM-1N Districts Schedule

RM-1 and RM-1N Districts Schedule Districts Schedule 1 Intent The intent of this Schedule is to encourage development of courtyard rowhouses on larger sites while continuing to permit lower intensity development on smaller sites. Siting

More information

Emil Møllers Gade 41 Horsens, Denmark

Emil Møllers Gade 41 Horsens, Denmark STUDY OF DANISH MULTI-STORY HOUSES DATA: 2015 03 09 Emil Møllers Gade 41 Horsens, Denmark GROUP MEMBERS: VIDMANTAS GLINSKAS 204756 EDGAR MORA 235414 JAVIER GUTIERREZ 236330 EGLE MECIUTE 215430 META DATA

More information

APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE NEWNHAM CAMPUS TORONTO, ONTARIO

APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE NEWNHAM CAMPUS TORONTO, ONTARIO APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE NEWNHAM CAMPUS TORONTO, ONTARIO Prepared by: Rita Cherniavskaya & Elias Frechette Technical Consultants

More information

Background: 5 th Edition (2014) Florida Building Code, Building

Background: 5 th Edition (2014) Florida Building Code, Building Issue DS 2017-019. The petitioner Robert C Shumake of Shumake Architecture is seeking a declaratory statement on whether FBC 1029.1 require an emergency escape and rescue opening from sleeping units located

More information

SPECIFIC GUIDANCE FOR A BEDSIT TYPE HOUSE IN MULTIPLE OCCUPATION (HMO)

SPECIFIC GUIDANCE FOR A BEDSIT TYPE HOUSE IN MULTIPLE OCCUPATION (HMO) Document A SPECIFIC GUIDANCE FOR A BEDSIT TYPE HOUSE IN MULTIPLE OCCUPATION (HMO) This document is intended as a specific guide for persons who own, manage or control Bedsit type - houses in multiple occupations

More information

RM 4 and RM 4N Districts Schedule

RM 4 and RM 4N Districts Schedule Districts Schedule 1 Intent The intent of this Schedule is to permit medium density residential development, including a variety of multiple dwelling types, to encourage the retention of existing buildings

More information

2014 Vancouver Building By-Law

2014 Vancouver Building By-Law 2014 Vancouver Building By-Law GoToWebinar - Webinar on Policy Development for VisitAble Housing October, 21, 2014 Presented by Jason Watt P.Eng, CP Overview New Look, Websites, Stakeholders, By-law Structure,

More information

West 1st Avenue By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law)

West 1st Avenue By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law) City of Vancouver Zoning and Development By-law Community Services, 453 W. 12th Ave Vancouver, BC V5Y 1V4 F 604.873.7000 fax 604.873.7060 planning@vancouver.ca CD-1 (483) 236-298 West 1st Avenue By-law

More information

Ontario s 2012 Building Code Barrier-Free Design Amendments Ontario Regulation 332/12 Amended by O. Regs. 368/13 and 191/14

Ontario s 2012 Building Code Barrier-Free Design Amendments Ontario Regulation 332/12 Amended by O. Regs. 368/13 and 191/14 Ontario s 2012 Building Code Barrier-Free Design Amendments Ontario Regulation 332/12 Amended by O. Regs. 368/13 and 191/14 Notice: This E Learning module is intended for general information purposes only.

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No.03-10-908 Application No. 2003-06 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentences 3.3.1.8.(1)

More information

NJAA Guidance on Child Protective Window Guards

NJAA Guidance on Child Protective Window Guards NJAA Guidance on Child Protective Window Guards DCA FINALIZES LATEST WINDOW GUARD REGULATIONS On February 5, 2007, the DCA adopted regulations implementing PL 2006, c. 55 this summer s revised window guard

More information

PLANNING APPLICATION (REVISION 2.1)

PLANNING APPLICATION (REVISION 2.1) (REVISION ) RT DF SCHEMATIC SITE GRADING PLAN SCHEMATIC SITE GRADING PLAN 1" = 10' 1 C1 RT DF SCHEMATIC SITE UTILITY PLAN SCHEMATIC SITE UTILITY PLAN 1" = 10' 1 C2 RT DF SCHEMATIC SITE STORM WATER QUALITY

More information

RT-5 and RT-5N Districts Schedule

RT-5 and RT-5N Districts Schedule Districts Schedule 1 Intent The intent of this District Schedule is to strongly encourage the retention and renovation of existing character houses by providing incentives such as increased floor area,

More information

1133 West Georgia Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law)

1133 West Georgia Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law) City of Vancouver Zoning and Development By-law Community Services, 453 W. 12th Ave Vancouver, BC V5Y 1V4 F 604.873.7000 fax 604.873.7060 planning@vancouver.ca CD-1 (446) 1133 West Georgia Street By-law

More information

West Hastings Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law)

West Hastings Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law) Zoning and Development By-law Community Services, 453 W. 12th Ave Vancouver, BC V5Y 1V4 F 604.873.7344 fax 873.7060 planning@city.vancouver.bc.ca CD-1 (316) 526-528 West Hastings Street By-law No. 7209

More information

Small Lot Housing Code (June 2013):

Small Lot Housing Code (June 2013): Small Lot Housing Code (June 2013): Standards that establish a building envelope for a single Class 1a building and associated Class 10 buildings on an allotment. If an adjoining allotment is not subject

More information

RM-11 and RM-11N Districts Schedule

RM-11 and RM-11N Districts Schedule Districts Schedule 1 Intent The intent of this Schedule is to permit medium density residential development primarily in the form of four-storey T -shaped apartments, and to foster compact, sustainable,

More information

1200 Alberni Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law)

1200 Alberni Street By-law No (Being a By-law to Amend By-law 3575, being the Zoning and Development By-law) Zoning and Development By-law Community Services, 453 W. 12th Ave Vancouver, BC V5Y 1V4 F 604.873.7344 fax 873.7060 planning@city.vancouver.bc.ca CD-1 (319) 1200 Alberni Street By-law No. 7224 (Being a

More information

êéëé~êåü=üáöüäáöüí Code Requirements and Costs of Incorporating Accessory Apartments in Houses

êéëé~êåü=üáöüäáöüí Code Requirements and Costs of Incorporating Accessory Apartments in Houses êéëé~êåü=üáöüäáöüí May 2009 Technical Series 09-102 Code Requirements and Costs of Incorporating Accessory Apartments in Houses áåíêççìåíáçå Canada Mortgage and Housing Corporation commissioned a study

More information

City of Vancouver Zoning and Development By-law Planning, Urban Design and Sustainability Department

City of Vancouver Zoning and Development By-law Planning, Urban Design and Sustainability Department Zoning and Development By-law Planning, Urban Design and Sustainability Department 453 West 12th Avenue, Vancouver, BC V5Y 1V4 tel: 3-1-1, outside Vancouver 604.873.7000 fax: 604.873.7100 website: vancouver.ca

More information

The New NYC Building Code Chapter 11 Accessibility. New York City Department of Buildings. Technical Affairs. Keith Wen, R.A. Copyright Materials

The New NYC Building Code Chapter 11 Accessibility. New York City Department of Buildings. Technical Affairs. Keith Wen, R.A. Copyright Materials The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright

More information

Homeowners Guide to Accessory Dwelling Units

Homeowners Guide to Accessory Dwelling Units Homeowners Guide to Accessory Dwelling Units Applicable to Buildings in existence AFTER July 14, 1994 In accordance with Zoning By law 2010 050 and the Ontario Building Code 2012 Town of Bradford West

More information

BUILDING CODE INTERPRETATION

BUILDING CODE INTERPRETATION BUILDING CODE INTERPRETATION March 2008 06-BCI-010 Page 1 of 9 ADAPTABLE DWELLING UNITS DISCUSSION This STANDATA has been developed to clarify the requirements for adaptable dwelling units in residential

More information

Small Lot Housing Code

Small Lot Housing Code Small Lot Housing Code AUGUST 2014 SMALL LOT HOUSING CODE Level 29, 35 Collins Street Melbourne Victoria 3000 Telephone: 03 9651 9600 Facsimile: 03 9651 9623 Email: Info@mpa.vic.gov.au www.mpa.vic.gov.au

More information

Building Code Extracts from the National Building Code of Canada 2010

Building Code Extracts from the National Building Code of Canada 2010 3.2.6. Additional Requirements for High Buildings (See Appendix B.) Building Code 3.2.6.1. Application This Subsection applies to a building a) of Group A, D, E or F major occupancy classification that

More information

DEVELOPMENT PERMIT APPLICATION BED & BREAKFAST

DEVELOPMENT PERMIT APPLICATION BED & BREAKFAST DEVELOPMENT PERMIT APPLICATION BED & BREAKFAST How did we do today? Visit www.canmore.ca/feedback and let us know! OFFICE USE ONLY Fee Required: $ Date Paid: Application #: Tax roll #: Required documents:

More information

Andraus high-rise, Sao Paulo, Brazil, February 1972

Andraus high-rise, Sao Paulo, Brazil, February 1972 Andraus high-rise, Sao Paulo, Brazil, February 1972 Of the 450 rescued, 350 were lifted off the roof by a fleet of 11 helicopters over a period of 4 hours 100 were saved at the 14th storey level using

More information

RM-10 and RM-10N Districts Schedule

RM-10 and RM-10N Districts Schedule Districts Schedule 1 Intent The intent of this Schedule is to permit medium density residential development primarily in the form of 6-storey apartments, and to foster compact, sustainable, multi-family

More information

RM-5, RM-5A, RM-5B, RM-5C and RM-5D Districts Schedule

RM-5, RM-5A, RM-5B, RM-5C and RM-5D Districts Schedule Districts Schedule 1 Intent The intent of this Schedule is to permit a variety of residential developments and some compatible retail, office, service and institutional uses. Emphasis is placed on achieving

More information

DEPARTMENT OF DEVELOPMENT SERVICES ACCESSIBILITY CHECK LIST FOR MULTI-FAMILY RESIDENTIAL BUILDINGS

DEPARTMENT OF DEVELOPMENT SERVICES ACCESSIBILITY CHECK LIST FOR MULTI-FAMILY RESIDENTIAL BUILDINGS DEPARTMENT OF DEVELOPMENT SERVICES ACCESSIBILITY CHECK LIST FOR MULTI-FAMILY RESIDENTIAL BUILDINGS City staff has compiled this partial checklist to assist developers with designing buildings in conformance

More information

OBTAINING A CERTIFICATE OF OCCUPANCY FOR UNAPPROVED DWELLING UNITS

OBTAINING A CERTIFICATE OF OCCUPANCY FOR UNAPPROVED DWELLING UNITS OBTAINING A CERTIFICATE OF OCCUPANCY FOR UNAPPROVED DWELLING UNITS A 2008 City Code amendment requires the owners of all rental dwelling units in the city to have a certificate of occupancy (CO) before

More information

The UBBL Applications of Fire Safety Provisions

The UBBL Applications of Fire Safety Provisions The UBBL Applications of Fire Safety Provisions Atriums Open Structures and Corridors Fire Appliance Access Ar Chong Lee Siong APAM MIFireE MIArbs PAM-IFEM SEMINAR 2016 ATRIUMS UBBL clause 137 UBBL clause

More information

HUDSON COUNTY NEW CONSTRUCTION MULTI-FAMILY RESIDENTIAL: NEWARK AVE JERSEY CITY, NJ BLOCK:11010, LOT:4. Design:

HUDSON COUNTY NEW CONSTRUCTION MULTI-FAMILY RESIDENTIAL: NEWARK AVE JERSEY CITY, NJ BLOCK:11010, LOT:4. Design: BLOCK:00, LOT:4 ZONING TABULATION CHART ITEM REQUIRED EXISTING PROPOSED NOTE VARIANCE MIN. LOT SIZE*,500 SF,93.35 SF,93.35 SF CONFORMING NO MAX. STRUCTURE HEIGHT 5 STORIES 3 5 CONFORMING NO MIN. LOT WIDTH

More information

Arriving and Getting In

Arriving and Getting In Waldorf St Martins Apartment Hotel Accessibility Report - 8/6/18 Waldorf St Martins offers 4 x One Bedroom Accessible Apartments for short term accommodation, in Auckland CBD, close to all central attractions

More information

PP Course # Instructor Information. Patrick Vandergriff 35 Cottonwood Canyon Road La Luz, NM

PP Course # Instructor Information. Patrick Vandergriff 35 Cottonwood Canyon Road La Luz, NM Instructor Information PP Course #15788 Patrick Vandergriff 35 Cottonwood Canyon Road La Luz, NM 88337 1-575-430-8752 pvandergriff@codeconsult.org 1 Detailing of Mixed Occupancy Structures within the 2018

More information

A Contemporary Arts & Culture Neighbourhood

A Contemporary Arts & Culture Neighbourhood A Contemporary Arts & Culture Neighbourhood THE PROJECT The Bkheir development is a gated community located in Antelias- Nabay, next to Fouar Antelias and 2 minutes away from the coastal highway. Overlooking

More information

CITY OF TORONTO BY-LAW NO. ~-20~

CITY OF TORONTO BY-LAW NO. ~-20~ Authority: Toronto and East York Community Council Item ~ as adopted by City of Toronto Council on ~, 20~ Enacted by Council: ~, 20~ CITY OF TORONTO BY-LAW NO. ~-20~ To amend the former City of Toronto

More information

Sample Questions for Paper 1 Statutory Controls in Building Works

Sample Questions for Paper 1 Statutory Controls in Building Works 1. One of the purposes of usable floor space in building plan submissions is for determining Ans. : A A. the area of the refuse chamber. B. the provision of sanitary fitments. C. the area within a flat,

More information

Secondary Suites Pre-application Workshop. It could be your first step to a secondary suite.

Secondary Suites Pre-application Workshop. It could be your first step to a secondary suite. Secondary Suites Pre-application Workshop It could be your first step to a secondary suite. Agenda 1. Introductions 2. Overview 3. What is a Secondary Suite? 4. DP/BP Application Process 5. Design Considerations

More information

1. PRESENTATION OF THE PROJECT

1. PRESENTATION OF THE PROJECT 1. PRESENTATION OF THE PROJECT Luxury chalets - Alpe d Huez LOCATION The project is located at the highest point of the Alpe d Huez resort, beside the ski slopes and opposite the Grandes Rousses mountain

More information

Access to and use of buildings

Access to and use of buildings The Building Regulations 2010 Access to and use of buildings APPROVED DOCUMENT M Volume 1: Dwellings M4(1) Category 1: Visitable dwellings M4(2) Category 2: Accessible and adaptable dwellings M4(3) Category

More information

3. Miscellaneous Instructions and Definitions.

3. Miscellaneous Instructions and Definitions. Last page revision- March 31st, 1999 TEXAS ACCESSIBILITY STANDARDS (TAS) TAS Table of Contents 3. Miscellaneous Instructions and Definitions. 3.1 Graphic Conventions. Graphic conventions are shown in Table

More information

NOTE: HEIGHT WIDTH OF UNOBSTRUCTED OPENING MUST EQUAL AT LEAST 5.7 SQ. FT.

NOTE: HEIGHT WIDTH OF UNOBSTRUCTED OPENING MUST EQUAL AT LEAST 5.7 SQ. FT. Egress Windows Few of us think of windows as lifesaving equipment but they are! When you need to escape a house fire or other disaster, or when rescue personnel need to enter the right-sized egress window

More information

STATE OF NEW JERSEY. ASSEMBLY, No th LEGISLATURE. Sponsored by: Assemblywoman L. GRACE SPENCER District 29 (Essex)

STATE OF NEW JERSEY. ASSEMBLY, No th LEGISLATURE. Sponsored by: Assemblywoman L. GRACE SPENCER District 29 (Essex) ASSEMBLY, No. STATE OF NEW JERSEY th LEGISLATURE INTRODUCED MAY, 0 Sponsored by: Assemblywoman L. GRACE SPENCER District (Essex) SYNOPSIS Requires DCA to issue regulations and conduct inspections for bed

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 99-300 AN ORDINANCE OF THE CITY OF BIG BEAR LAKE, COUNTY OF SAN BERNARDINO, STATE OF CALIFORNIA, REPEALING ORDINANCE NO. 90-187 AND AMENDING THE DEVELOPMENT CODE TO REVISE SECTION 86.0201

More information

ASSEMBLY, No STATE OF NEW JERSEY. 212th LEGISLATURE INTRODUCED JUNE 8, 2006

ASSEMBLY, No STATE OF NEW JERSEY. 212th LEGISLATURE INTRODUCED JUNE 8, 2006 ASSEMBLY, No. STATE OF NEW JERSEY th LEGISLATURE INTRODUCED JUNE, 00 Sponsored by: Assemblyman WILLIAM D. PAYNE District (Essex and Union) Assemblyman CRAIG A. STANLEY District (Essex) Assemblywoman OADLINE

More information