Accessible drinking fountain does not have a clear 30 wide floor space centered on the drinking fountain (centerline to the counter edge is 12 ).

Size: px
Start display at page:

Download "Accessible drinking fountain does not have a clear 30 wide floor space centered on the drinking fountain (centerline to the counter edge is 12 )."

Transcription

1 ADA STANDARD: PARKS SERVICE CENTER GARAGE (1), Figs. 4(e) and 27(b) Accessible drinking fountain does not have a clear 30 wide floor space centered on the drinking fountain (centerline to the counter edge is 12 ). Shorten the counter width by 3 (min.) to provide clear 30 wide floor space centered on the drinking fountain. Photo of drinking fountain

2 PARKS SERVICE CENTER GARAGE ADA STANDARD: , , , and Fig. 5, and Fig. 6 Height to operating latch on first aid cabinet is more than 48 above the floor (measured at 59-1/2 ). Adjust height of first aid cabinet so highest closed operable latch is not more than 48 above the floor. Photo of Parks Service Center

3 PARKS SERVICE CENTER GARAGE ADA STANDARD: , Insufficient maneuvering clearance is provided between the edges of the benches and the lockers (measured at 54 ). A 24 x 48 bench is not provided for handicapped users (measured at 9-1/2 x 36 ). Adjust the benches so that a minimum of 60 turning diameter is provided within the locker room. Install a 24 x 48 bench for handicapped users to replace one or both of the existing two benches. Photo of Parks Service Center

4 ROBERT E. BURKE MEMORIAL PARK Photo of Robert E. Burke Memorial Park

5 ITEM: ADA GUIDELINE: ROBERT E. BURKE MEMORIAL PARK N/A N/A N/A N/A Photo of park

6 SHERIDAN PARK Photo of Sheridan Park

7 ITEM: SHERIDAN PARK ACCESSIBLE ROUTE ADA GUIDELINE: 4.1.2(1), 4.3 An accessible path is not provided to the picnic tables in the park. Add an accessible path to the picnic tables in the park. Photo of Picnic Tables in south portion of park

8 ITEM: SHERIDAN PARK PICNIC TABLE ADA GUIDELINE: 5.5, 306, 902.2, An accessible space is not provided in the picnic table grouping that permits a wheelchair to pull under the end of one of the table sides. Remove one of the seat and horizontal arm assemblies to provide an accessible wheelchair space. Photo of Picnic Tables in south portion of park

9 A.C. NIELSEN TENNIS CENTER Photo of A.C. Nielsen Tennis Center

10 A.C. NIELSEN TENNIS CENTER ADA STANDARD: 4.1.3(1), Second floor to Tennis Center has no lift or elevator (square footage is approximately 5115 sq. ft. on second floor). Install lift or elevator to second floor. Photo of second floor of A.C. Nielsen Tennis Center

11 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Door knob on first floor boiler room door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor boiler room door of A.C. Nielsen Tennis Center

12 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Door knob on first floor manager s office door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor manager s office door of A.C. Nielsen Tennis Center

13 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Door knob on first floor storage room door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor storage room door of A.C. Nielsen Tennis Center

14 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Door knob on first floor AED closet room door is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on first floor AED closet room door of A.C. Nielsen Tennis Center

15 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Door knob on second floor closet in southeast corner is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of storage room door on southeast corner of second floor of A.C. Nielsen Tennis Center

16 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Door knob on top of second floor stairwell in northwest corner is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door at top of stairwell at northwest corner of second floor of A.C. Nielsen Tennis Center

17 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Door knob on second floor hallway at southeast corner is round and hard to grasp. Replace round door knob with lever knob that is accessible. Photo of door on hallway second floor in southeast corner of A.C. Nielsen Tennis Center

18 ADA STANDARD: A.C. NIELSEN TENNIS CENTER (1), Figs. 4(e) and 27(b) Drinking fountain inside east side of the center of the building entrance is not accessible since the unit does not allow 27 of wheelchair access under the unit. Install new drinking fountain that has 27 of wheelchair access under the unit. Photo of drinking fountain inside the east side of the center of A.C. Nielsen Tennis Center

19 ADA STANDARD: A.C. NIELSEN TENNIS CENTER (1), Figs. 4(e) and 27(b) Drinking fountain in aisle between the tennis courts is not accessible since the unit does not allow 27 of wheelchair access under the unit and the spout is higher than 36 above floor (measured at 46 to spout). Install new drinking fountain that has 27 of wheelchair access under the unit and a spout no higher than 36 above the floor. Photo of drinking fountain in the aisle between the tennis courts of A.C. Nielsen Tennis Center

20 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Boxes over thermostats in southeast corner of second floor project out more than 4 and are above 27 high. Replace covers with models that do not project out more than 4 from wall. Photo of thermostat boxes in second floor southeast corner of A.C. Nielsen Tennis Center

21 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Five fire extinguishers on throughout building project out more than 4 and are higher than 27 above the floor (measured at 43 above floor). Lower 5 fire extinguishers so the bottom edges are no more than 27 above the floor. Photo of fire extinguisher on second floor of A.C. Nielsen Tennis Center

22 A.C. NIELSEN TENNIS CENTER ADA STANDARD: Mirrors in restrooms are mounted higher than 40 to bottom reflecting surface (measured at 45 to ground). Lower bottom edges of mirrors to 40 above ground. Photo of mirror in restrooms of A.C. Nielsen Tennis Center

23 ADMINISTRATIVE OFFICE Photo of Administrative Office

24 ADMINISTRATIVE OFFICE ADA STANDARD: West women s single user restroom sink exceeds 34 height above floor (measured at 35 ). Lower sink to 34 height above floor. Photo of west women s single user restroom

25 ADMINISTRATIVE OFFICE ADA STANDARD: All four (4) single user restroom mirrors exceed 40 height above floor (measured at 41 ). Lower mirrors to 40 height above floor. Photo of east women s single user restroom

26 ADMINISTRATIVE OFFICE ADA STANDARD: , Horizontal grab bars in two (2) west single user restrooms are less than 36 long (measured at 30 ). Install 36 long horizontal grab bars. Photo of west men s single user restroom

27 ADMINISTRATIVE OFFICE ADA STANDARD: Coat hooks in all four (4) single user restrooms exceed 54 height above floor (measured at 63 ). Either lower existing coat hooks to 54 height above floor or add new hooks at 54 height above floor. Photo of east men s single user restroom

28 BALLFIELD STORAGE - SHELTER Photo of Ballfield Storage - Shelter

29 BALLFIELD STORAGE - SHELTER ADA STANDARD: 4.1.6(3)(d)(ii), Threshold at building entrance exceeds ¾ height (measured at 3 high). Install gravel, concrete or asphalt ramp to top of threshold and into the building. Photo of double door entry

30 BALLFIELD STORAGE - SHELTER ADA STANDARD: Elevation change between concrete pad and adjacent gravel exceeds ½ height. Install gravel to meet height of concrete pad. Photo of north side

31 BALLFIELD STORAGE- -SHELTER ADA STANDARD: Building logs project out greater than 4 into accessible pathways above 27 from floor (measured at 29 and 37 ). Install barriers so the top of the barricade is at 27 or below underneath building projections. Photo of south side

32 CART BARN Photo of Cart Barn

33 CART BARN ADA STANDARD: , Hose hook located inside door inside southwest corner of Cart Barn does not allow 32 clear passage and maneuvering room. Relocate hose hook location away from the door to allow 32 clear passage. Photo of southwest corner of interior

34 CART BARN ADA STANDARD: Southwest and northeast pedestrian doors have round handles which are difficult for the disabled to grasp. Replace door handles with lever-style handles. Photo of southwest door

35 CART BARN ADA STANDARD: Hose reel projects out more than 4 and has bottom edge higher than 27 above the floor. Lower hose reel so bottom edge is below 27 above the floor. Photo of hose reel

36 CART BARN ADA STANDARD: Fire extinguisher next to southwest door projects out more than 4 and has bottom edge higher than 27 above the floor (measured at 30 ). Lower fire extinguisher so bottom edge is below 27 above the floor. Photo of southwest fire extinguisher

37 CART BARN ADA STANDARD: Double vent on west wall of building projects out more than 4 and is below 80 above the floor. Install barrier below double vent with bottom edge below 27 above the floor (i.e. panels on sides of vent or bumpers or bollards on floor. Photo of double wall vent

38 CART BARN ADA STANDARD: Hose hook projects out more than 4 with bottom edge higher than 27 above the floor. Relocate hose hook to a new location with bottom edge below 27 above the floor. Photo of hose hook

39 CELL PHONE BUILDING - NORTH Photo of Cell Phone Building - North

40 CELL PHONE BUILDING - NORTH ADA STANDARD: 4.1.2(1), 4.3, 4.3.8, 4.1.3(1) Stairs to door at south side of building are not accessible (5 risers at 8 each are more than the ½ maximums required). Add a ramp to north cell phone building (and south cell phone building) to berm and top of stairs. Photo of stairs

41 CELL PHONE BUILDING - NORTH ADA STANDARD: , Fig. 25 On latch pull side of door, there is not 18 of clearance to edge of stair tread (measured at 6 ). Rebuild railings and stairs to provide a full clearance of 18 from edge of latch pull side of door to edge of stair tread and 48 clearance from building to railings. An alternative is to flip door hinge/latch sides and add concrete extension on uphill side of landing to 18 from latch side of door. Photo of stairs

42 CELL PHONE BUILDING - SOUTH Photo of Cell Phone Building - South

43 CELL PHONE BUILDING - SOUTH ADA STANDARD: 4.1.2(1), 4.3, 4.3.8, 4.1.3(1) Stairs to door at south side of building are not accessible (5 risers at 8 each are more than the ½ maximums required). Add a ramp to south cell phone building (and north cell phone building) to berm and top of stairs. Photo of stairs

44 CELL PHONE BUILDING - SOUTH ADA STANDARD: , Fig. 25 On latch pull side of door, there is not 18 of maneuvering clearance to edge of landing (measured at 6 ). Also, there is a hole in concrete landing. Add paving to 18 from edge of latch pull side of door. Fill in hole. Photo of stairs

45 CLUBHOUSE Photo of Clubhouse

46 CLUBHOUSE ADA STANDARD: Overhanging trees on the path to the clubhouse from the parking lot have branches below 80 height. Cut any branches overhanging the path to above 80 height. Photo of path looking west from the parking lot to the Clubhouse

47 CLUBHOUSE ADA STANDARD: Pavement adjacent to the driving range ball dispenser is uneven and not level with adjacent concrete pad. Add asphalt to bring surface level with adjacent concrete pad to permit user to get closer to dispenser. Photo of driving range ball dispenser on east side

48 CLUBHOUSE ADA STANDARD: 4.4, 4.2.1(3), 4.1.3(2) Exterior light fixtures and hanging flower baskets project into accessible routes over 4 and are located between 27 and 80 above the ground (measured at 8 projection and 65 high to the bottom of the light fixtures and 28 projection and 72 high to the bottom of the flower baskets). Replace light fixtures with style that does not project more than 4 into an accessible route. Raise hanging baskets to above 80 ground or relocate to other locations where at least 80 exists. Photo of exterior column on front porch

49 CLUBHOUSE ADA STANDARD: 4.1.3(1), 4.1.6(3)(d)(ii), West entrance to the Clubhouse is not accessible (threshold to doors exceeds ¾ height; measured at 6 risers) and has no sign directing user to the accessible entrance (main south entrance). Install a permanent sign directing disabled users to the main south entrance. Photo of west entrance

50 CLUBHOUSE ADA STANDARD: 4.1.3(1), , Fig. 25 North entrance to the Clubhouse is not accessible (insufficient clearance of 18 on latch side of the door; measured at 6 ) and has no sign directing user to the accessible entrance (main south entrance). Install a permanent sign directing disabled users to the main south entrance or add pavement to latch side of door to provide a minimum of 18 clearance. Photo of north entrance

51 CLUBHOUSE ADA STANDARD: 4.1.3(1), 4.1.6(3)(d)(ii), North entrance to the Clubhouse pro s office is not accessible (threshold exceeds ¾ due to settled asphalt outside the door) and has no sign directing user to the accessible entrance (main south entrance). Install a permanent sign directing disabled users to the main south entrance or add asphalt to top lip of concrete floor. Photo of north entrance to the pro s office

52 CLUBHOUSE ADA STANDARD: Clearance space on the pull side of the latch side of the north office door is less than 18 (measured at 4 ) due to drawer unit and shelf unit. Relocate drawer and shelf unit to provide a minimum of 18 clearance on the latch side of the door. Photo of north office

53 CLUBHOUSE ADA STANDARD: Clearance space on the pull side of the latch side of the door is less than 18 (measured at 5 ) due to metal shelving unit. Relocate shelving unit to provide a minimum of 18 clearance on the latch side of the door. Photo of kitchen storage room

54 CLUBHOUSE ADA STANDARD: Clearance space on the pull side of the latch side of the door from the hallway into the kitchen area is less than 18 (measured at 2 ) due to pop boxes. Relocate pop boxes to provide a minimum of 18 clearance on the latch side of the door. Photo of door from hallway to kitchen area

55 CLUBHOUSE ADA STANDARD: Clearance space on the pull side of the latch side of the door from the pro s office into the driving range machine room is less than 18 (measured at 3 ) due to lockers. Relocate double height locker to provide a minimum of 18 clearance on the latch side of the door. Photo of pro s office driving range machine door

56 CLUBHOUSE ADA STANDARD: The round knob on the door into the driving range machine room is hard to grasp for the disabled. Replace the door knob with a lever type to match the other door knobs in the Clubhouse. Photo of pro s office driving range machine door

57 CLUBHOUSE ADA STANDARD: Clearance space on the pull side of the latch side of the pro s office storage door is less than 18 (measured at 6 ) due to display units. Relocate display units to provide a minimum of 18 clearance on the latch side of the door. Photo of pro s office storage room

58 CLUBHOUSE ADA STANDARD: Interior wall lights (total of 3) in rear hallways project out further than 4 with the bottom edge of the fixture between 27 and 80 above the floor (measured at 10-1/2 projection and 62-1/2 above the floor). Replace fixtures with units that do not project more than 4 from the wall or install with the bottom of the light above 80 from the floor. Photo of rear hallway

59 CLUBHOUSE ADA STANDARD: Interior wall lights (total of 4) in the classroom project out further than 4 with the bottom edge of the fixture between 27 and 80 above the floor (measured at 7 projection and 79 above the floor). Replace fixtures with units that do not project more than 4 from the wall or install with the bottom of the light above 80 from the floor. Photo of classroom

60 CLUBHOUSE ADA STANDARD: Fire extinguisher in rear hallway projects out further than 4 with the bottom edge of the fixture between 27 and 80 above the floor (measured at 5 projection and 33 above the floor). Reset fire extinguisher with the bottom edge at 27 above the floor. Photo of north hallway fire extinguisher

Existing Building Accessibility Quick Checklist (CBC 11B) Job Address Permit

Existing Building Accessibility Quick Checklist (CBC 11B) Job Address Permit Existing Building Accessibility Quick Checklist (CBC 11B) Job Address Permit DIVISON 5: GENERAL SITE AND BUILDING ELEMENTS ENTRY (Items 1.1 & 1.6) Y N Parking Spaces Path from street accessible throughout

More information

Residential Accessible, Type A, and Type B Dwelling Unit Requirements 2012 International Building Code and 2009 ICC/ANSI A117.1

Residential Accessible, Type A, and Type B Dwelling Unit Requirements 2012 International Building Code and 2009 ICC/ANSI A117.1 Residential Accessible, Type A, and Type B Dwelling Unit Requirements 2012 International Building Code and 2009 ICC/ANSI A117.1 20 E Olive Street STE 208 PO Box 1230 Bozeman, MT 59771-1230 Phone: (406)

More information

THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist.

THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist. Nova Scotia Building Accessibility Checklist Note OTE THIS CHECKLIST HAS BEEN AMENDED TO INCLUDE ONLY LEVEL ONE CRITERIA AS REQUESTED BY TIR REAL PROPERTY. As such it does not form a complete Checklist.

More information

Regulation Outline. Under section 59 of the Community Planning Act, the Lieutenant-Governor in Council makes the following Regulation:

Regulation Outline. Under section 59 of the Community Planning Act, the Lieutenant-Governor in Council makes the following Regulation: 1 Regulation Outline Citation....1 Definitions....2 Act Loi Code Code tourist establishment établissement touristique tourist home maison pour touristes Approval of building code....3 Interpretation....4

More information

Schedule C Barrier-Free Design

Schedule C Barrier-Free Design 1 Schedule C Barrier-Free Design As amended by Article 3.1.1.5. of these regulations Section 3.8 Barrier- Free Design of the Code is replaced with the following: Section 3.8 Barrier-Free Design 3.8.1.

More information

Arlington County. Smart Choice Homes. Arlington County. Homes for all of us. Homes for a lifetime. Home

Arlington County. Smart Choice Homes. Arlington County. Homes for all of us. Homes for a lifetime. Home Arlington County Smart Choice Homes Home Arlington County Homes for all of us. Homes for a lifetime Why Smart Choice Homes? Smart design equals smart living. This booklet provides the building blocks to

More information

2012 Texas Accessibility Standards Reference Guide for changes to the code

2012 Texas Accessibility Standards Reference Guide for changes to the code 2012 Texas Accessibility Standards Reference Guide for changes to the code SCOPING ITEMS Children s Mounting Heights Elements primarily used by children are no longer required to comply with the appropriate

More information

Accessibility and ADA: Facility Standards Update. Technical Specifications: Chapters 8-10

Accessibility and ADA: Facility Standards Update. Technical Specifications: Chapters 8-10 Accessibility and ADA: Facility Standards Update Technical Specifications: Chapters 8-10 1 Today s Agenda Chapter 8: Special Rooms, Spaces, and Elements Chapter 9: Built-In Elements Chapter 10: Recreation

More information

Ontario s 2012 Building Code Barrier-Free Design Amendments Ontario Regulation 332/12 Amended by O. Regs. 368/13 and 191/14

Ontario s 2012 Building Code Barrier-Free Design Amendments Ontario Regulation 332/12 Amended by O. Regs. 368/13 and 191/14 Ontario s 2012 Building Code Barrier-Free Design Amendments Ontario Regulation 332/12 Amended by O. Regs. 368/13 and 191/14 Notice: This E Learning module is intended for general information purposes only.

More information

ADA/TAS Plan Review & Inspection Worksheet Texas Access

ADA/TAS Plan Review & Inspection Worksheet Texas Access ADA/TAS Plan Review & Inspection Worksheet Texas Access www.texasaccess.com Client: Project No: Address: City/Town: State/ZIP: Project Type: PLAN REVIEW INSPECTION BY DATE Applicable to project scope Results:

More information

General Information. Location Information. Location Use. Colorado VSPC/Drop-off/Drop-box Accessibility Survey Form. For SOS office use only

General Information. Location Information. Location Use. Colorado VSPC/Drop-off/Drop-box Accessibility Survey Form. For SOS office use only Colorado VSPC/Drop-off/Drop-box Accessibility Survey Form Complete all sections of the survey below if you are using the site as a full VSPC and/or a drop off site. If you are using the site as a Drop

More information

ADAPTABLE DESIGN GUIDELINES

ADAPTABLE DESIGN GUIDELINES ADAPTABLE DESIGN GUIDELINES Adaptable design creates liveable residences for a wider range of persons than current building codes require. By considering design features that can be easily and inexpensively

More information

HANDICAPPED ACCESSIBILITY TOOLKIT

HANDICAPPED ACCESSIBILITY TOOLKIT HANDICAPPED ACCESSIBILITY TOOLKIT By: Mike Ferguson, P.E. Director of Engineering Services As a PCNA provider, we discuss handicapped accessibility design and construction issues daily. Accessibility guidelines

More information

Understanding Accessibility Features to Meet Housing Needs

Understanding Accessibility Features to Meet Housing Needs Understanding Accessibility Features to Meet Housing Needs For more information about the K-W VisitAble Housing initiative: www.waterlooregion.org/visitable spckw@waterlooregion.org 519-579-1096 X *3006

More information

Understanding Accessibility Features to Meet Housing Needs

Understanding Accessibility Features to Meet Housing Needs Understanding Accessibility Features to Meet Housing Needs For more information about the K-W VisitAble Housing initiative: www.waterlooregion.org/visitable trudy@waterlooregion.org 519-579-1096 X *3006

More information

Existing Property Accessibility Checklist

Existing Property Accessibility Checklist (Attachment F) Existing Property Accessibility Checklist DISCLAIMER This information was developed to assist contractors in developing repair lists for existing MFH properties financed through USDA Rural

More information

APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE NEWNHAM CAMPUS TORONTO, ONTARIO

APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE NEWNHAM CAMPUS TORONTO, ONTARIO APPLICATION OF SECTION 3.8 OF THE 2012 ONTARIO BUILDING CODE FOR: BARRIER-FREE AUDIT OF SENECA COLLEGE NEWNHAM CAMPUS TORONTO, ONTARIO Prepared by: Rita Cherniavskaya & Elias Frechette Technical Consultants

More information

During the Civil Rights Era

During the Civil Rights Era LAWS PROHIBITING DISCRIMINATION BASED ON DISABILITY IN HOUSING Debra McGhee Director, Baltimore Center Fair Housing & Equal Opportunity U.S. Department of HUD During the Civil Rights Era Fair Housing Act

More information

/7/2016. During the Civil Rights Era LAWS PROHIBITING DISCRIMINATION BASED ON DISABILITY IN HOUSING. Architectural Barriers Act of 1968

/7/2016. During the Civil Rights Era LAWS PROHIBITING DISCRIMINATION BASED ON DISABILITY IN HOUSING. Architectural Barriers Act of 1968 LAWS PROHIBITING DISCRIMINATION BASED ON DISABILITY IN HOUSING Debra McGhee Director, Baltimore Center Fair Housing & Equal Opportunity U.S. Department of HUD During the Civil Rights Era Fair Housing Act

More information

Section 3: Primary Function, Employee Work Areas, & Kitchens

Section 3: Primary Function, Employee Work Areas, & Kitchens Section 3: Primary Function, Employee Work Areas, & Kitchens TEXAS ACCESSIBILITY ACADEMY Architectural Barriers Program 106.5.45 Primary Function A major activity for which the facility is intended Examples:

More information

12/18/2017. Objective. Accessibility Code MN 1341 Frequent Questions and Key Criteria. Agenda. Code Documents

12/18/2017. Objective. Accessibility Code MN 1341 Frequent Questions and Key Criteria. Agenda. Code Documents Objective Accessibility Code MN 1341 Frequent Questions and Key Criteria Highlight frequently asked Accessibility Code Questions Review the intent of the requirements Clarify the why behind the what of

More information

NEW HOME UNIVERSAL DESIGN CHECKLIST (AB 1400)

NEW HOME UNIVERSAL DESIGN CHECKLIST (AB 1400) Building Division 555 Santa Clara Street Vallejo CA 94590 707.648.4374 NEW HOME UNIVERSAL DESIGN CHECKLIST (AB 1400) Name of Development, if applicable: Home/Lot Address/ID: Developer (Contact) Name: Address:

More information

National Trust Cottages Access Statement/Guide

National Trust Cottages Access Statement/Guide National Trust Cottages Access Statement/Guide 89 Church Lawn Stourton Warminster BA12 6QE Property Ref 003017 Introduction Built from local stone the property is located at the entrance to the garden

More information

CAS PAR. Comprehensive Assessment and Solution Process For Aging Residents INTRODUCTION MATERIALS NEEDED 1 CASPAR

CAS PAR. Comprehensive Assessment and Solution Process For Aging Residents INTRODUCTION MATERIALS NEEDED 1 CASPAR CAS PAR Comprehensive Assessment and Solution Process For Aging Residents INTRODUCTION CASPAR consists of 6 sections.the suggested order of completing the protocol is as follows:. Contact Information.

More information

Accessible Facilities Report Template

Accessible Facilities Report Template Accessible Facilities Report Template Applicant Information Sheet and Report Template CCC Use Only: Project No: TRIM Ref: Project Address: [include Level and Unit No] If you have not used this template

More information

Codes Checklist Document 3

Codes Checklist Document 3 Ohio University Interior Architecture Codes Check p1 of 7 atthew Ziff,.Arch, Associate Professor Codes Checklist Document 3 General Construction Code Requirements Construction type of Building (Table 601)

More information

Utopia Gymnastics Accessibility Guidance. Utopia Gymnastics

Utopia Gymnastics Accessibility Guidance. Utopia Gymnastics Utopia Gymnastics Accessibility Guidance Utopia Gymnastics Units 1&2 Prince of Wales Mill Birds Royd Lane Brighouse HD6 1LQ 01484 717428 info@utopiagymnastics.co.uk www.utopiagymnastics.co.uk Version 1-09/2018

More information

Universal Design Policy

Universal Design Policy Vermont Housing Finance Agency Universal Design Policy 12/6/2018 Universal design is an approach to design that works to ensure products and buildings can be used by virtually everyone, regardless of their

More information

DEPARTMENT OF DEVELOPMENT SERVICES ACCESSIBILITY CHECK LIST FOR MULTI-FAMILY RESIDENTIAL BUILDINGS

DEPARTMENT OF DEVELOPMENT SERVICES ACCESSIBILITY CHECK LIST FOR MULTI-FAMILY RESIDENTIAL BUILDINGS DEPARTMENT OF DEVELOPMENT SERVICES ACCESSIBILITY CHECK LIST FOR MULTI-FAMILY RESIDENTIAL BUILDINGS City staff has compiled this partial checklist to assist developers with designing buildings in conformance

More information

A. Robert Kucab Executive Director

A. Robert Kucab Executive Director Construction Field Guide For 2016 NCHFA-Financed Rental Properties 1 The design and construction of an apartment community is a complex undertaking that requires compliance with numerous codes, requirements,

More information

Access Statement for Primrose Farm

Access Statement for Primrose Farm This access statement does not contain personal opinions as to our suitability for those with access needs, but aims to accurately describe the facilities and services that we offer all our guests. Access

More information

General Statement Regarding Assessment Analysis Recommendations

General Statement Regarding Assessment Analysis Recommendations Summary For Pretlow Gardens Apartments VA018183000 General Statement Regarding Assessment Analysis Recommendations Pursuant to the, VA agreement with The Nelrod Company dated August 23, 2012 a was conducted

More information

Investigation Reference No. Investigation Status. Investigation Description

Investigation Reference No. Investigation Status. Investigation Description IBMS Reports MLS Building Audit Program - Details Property Address : 4 ADANAC DR Legal Description: PLAN 84 PT BLK A PLAN 49 LOT TO 8 PT LOT TO 6PT Roll : 99 Building : 4 ADANAC DR Report : Building Audit

More information

Copyright 2013, Queen s Printer for Ontario

Copyright 2013, Queen s Printer for Ontario Contact Information Building Code Information Officer, George Brown College BuildingCode@GeorgeBrown.ca 416-415-5000x6725 http://ce.georgebrown.ca/buildingcodeinformation This course is based on the Building

More information

Trerice Access Statement

Trerice Access Statement Trerice Access Statement Kestle Mill Newquay Cornwall TR84PG T: 01637 875404 E: trerice@nationaltrust.org.uk Introduction 1. Trerice is a small Cornish manor house accessible by narrow lanes. 2. Mobile

More information

National Trust Cottages Access Statement

National Trust Cottages Access Statement National Trust Cottages Access Statement Cottage Ref:011059 Nanceglos House Trengwainton PENZANCE Cornwall Introduction Nanceglos is a large, stone built house on the boundary of the garden at Trengwainton.

More information

The New NYC Building Code Chapter 11 Accessibility. New York City Department of Buildings. Technical Affairs. Keith Wen, R.A. Copyright Materials

The New NYC Building Code Chapter 11 Accessibility. New York City Department of Buildings. Technical Affairs. Keith Wen, R.A. Copyright Materials The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright

More information

Access Statement for Dellfield Self-Catering unit

Access Statement for Dellfield Self-Catering unit Access Statement for Dellfield Self-Catering unit Introduction and Overview The self-catering flat is on the ground floor in an annexe attached to the main house. The flat is not suitable for guests needing

More information

BUILDING CODE INTERPRETATION

BUILDING CODE INTERPRETATION BUILDING CODE INTERPRETATION March 2008 06-BCI-010 Page 1 of 9 ADAPTABLE DWELLING UNITS DISCUSSION This STANDATA has been developed to clarify the requirements for adaptable dwelling units in residential

More information

11A Accessibility Standards Frequently Asked Questions for Residential Projects

11A Accessibility Standards Frequently Asked Questions for Residential Projects 11A Accessibility Standards Frequently Asked Questions for Residential Projects Faruk Sezer, PE, CASp-659 Revised 02.05.2019 1 Preface This document is intended to provide information and technical guidance

More information

3. Miscellaneous Instructions and Definitions.

3. Miscellaneous Instructions and Definitions. Last page revision- March 31st, 1999 TEXAS ACCESSIBILITY STANDARDS (TAS) TAS Table of Contents 3. Miscellaneous Instructions and Definitions. 3.1 Graphic Conventions. Graphic conventions are shown in Table

More information

ACCESS STATEMENT FOR the Byre AT BIRLING NORTH COTTAGE. Pre-Arrival. Parking. the East Coast Main Line is approximately 4km to the north.

ACCESS STATEMENT FOR the Byre AT BIRLING NORTH COTTAGE. Pre-Arrival. Parking. the East Coast Main Line is approximately 4km to the north. Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about bus services - accessibility, frequency, distance of

More information

Access Statement for Elk Cottage, Glassonby Old Hall, Glassonby, Penrith Introduction

Access Statement for Elk Cottage, Glassonby Old Hall, Glassonby, Penrith Introduction This access statement does not contain personal opinions as to our suitability for those with access needs, but aims to accurately describe the facilities and services that we offer all our guests/visitors.

More information

ACCESSIBILITY CHAPTER 11

ACCESSIBILITY CHAPTER 11 CHAPTER 11 ACCESSIBILITY SECTION 1101 GENERAL 1101.1 Scope. The provisions of this chapter shall control the design and construction of facilities for accessibility to physically disabled persons. 1101.2

More information

ACCESS STATEMENT FOR THE HEMMEL

ACCESS STATEMENT FOR THE HEMMEL Coastal Retreats want to make everyone s stay as enjoyable as possible, and are committed to providing suitable access for all our guests, whatever their individual needs. We aim to accurately describe

More information

Give the name and distance of the nearest railway station. Describe the type of surface from the car park to the main entrance.

Give the name and distance of the nearest railway station. Describe the type of surface from the car park to the main entrance. Westfield Farmhouse, Seahouses, rthumberland NE68 7UR Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about

More information

National Trust Cottages Access Statement

National Trust Cottages Access Statement National Trust Cottages Access Statement Cottage Ref:011059 Lower Pentire Farm House Loe Pool HELSTON Cornwall Introduction Stone built 18 th century farmhouse. Slate, Carpet and vinyl floors and ceiling

More information

National Trust Cottages Access Statement/Guide

National Trust Cottages Access Statement/Guide National Trust Cottages Access Statement/Guide 1 Forge Cottage Branscombe Devon Property Ref: 012006 Introduction The property is located within Branscombe village. It is a thatched cottage sleeping up

More information

National Trust Cottages Access Statement

National Trust Cottages Access Statement National Trust Cottages Access Statement Chatham Bosloe Mawnan Smith Falmouth Ref: 011053 Introduction Chatham is a two-storey apartment occupying the West Wing of Bosloe House The main rooms have views

More information

Access Statement Seaton 22 St Aidan s Seahouses NE68 7SS

Access Statement Seaton 22 St Aidan s Seahouses NE68 7SS Westfield Farmhouse,, Northumberland NE68 7UR Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about bus services

More information

Accessible Plumbing Fixture Requirements

Accessible Plumbing Fixture Requirements Accessible Plumbing Fixture Requirements Module 9 Module 9 1 Objectives Upon completion of this module, you will be better able to: Identify when bathrooms have to be accessible. Identify when family/assisted

More information

Charles Kozminski Elementary Community Academy

Charles Kozminski Elementary Community Academy Facility Assessment Detail This report contains the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual

More information

Fair Housing Amendments Act - Basic Design Issues - FHAA Design Requirements

Fair Housing Amendments Act - Basic Design Issues - FHAA Design Requirements Fair Housing Amendments Act - Basic Design Issues - Bill Hecker, AIA Accessibility Consultant Instructor in the Office of Executive Education Harvard Graduate School of Design October 30, 2014 FHAA Design

More information

Accessibility in Alberta

Accessibility in Alberta Accessibility in Alberta Safety Codes Council #SCCon17 Samantha Proulx, C.E.T. Accessibility Specialist, and Building Code Consultant Copyright Materials This presentation is protected by Canadian and

More information

LOCATION RFM ROAD, CABUYAO, LAGUNA

LOCATION RFM ROAD, CABUYAO, LAGUNA Project Brief LOCATION RFM ROAD, CABUYAO, LAGUNA ACCESSIBILITY SCHOOLS Pamantasan ng Cabuyao 1.19 km Our Lady of Assumption College 1.69 km Malayan College Laguna 2.49 km COMMERCIAL Uniwide Commercial

More information

National Trust Cottages Access Statement Cottage Ref The Farmhouse Middlebere Farm Arne Isle of Purbeck

National Trust Cottages Access Statement Cottage Ref The Farmhouse Middlebere Farm Arne Isle of Purbeck National Trust Cottages Access Statement Cottage Ref. 003013 The Farmhouse Middlebere Farm Arne Isle of Purbeck Introduction The Farmhouse dates from the 16 th century and is located close to the Arne

More information

Give the name and distance of the nearest railway station. Describe the streets in the area surrounding the property

Give the name and distance of the nearest railway station. Describe the streets in the area surrounding the property Westfield Farmhouse, Seahouses, rthumberland NE68 7UR Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about

More information

The Design and Construction Requirements of the Fair Housing Act: Technical Overview

The Design and Construction Requirements of the Fair Housing Act: Technical Overview The Design and Construction Requirements of the Fair Housing Act: Technical Overview (888) 341-7781 (V/TTY) - Technical Guidance www.fairhousingfirst.org 2005-2006 Designed and Developed by: The BearingPoint

More information

National Trust Cottages Access Statement

National Trust Cottages Access Statement National Trust Cottages Access Statement Cottage Ref: 011073 New Lodge Trelissick Feock TRURO Cornwall Introduction New Lodge cottage is a Victorian, stone built, detached Gate house situated on the (nonpublic)

More information

Americans with Disabilities Act Transition Plan Barrier Removal Database Project Listed by Type

Americans with Disabilities Act Transition Plan Barrier Removal Database Project Listed by Type Americans with Disabilities Act Transition Plan Barrier Removal Database Project Listed by Type Parking Lot Priorities Type 1 Program na Use 1 Severity na New Parking Lots and restriping / regradeing existing

More information

Access Statement Aidanfield Fenwick Berwick upon Tweed TD15 2PJ

Access Statement Aidanfield Fenwick Berwick upon Tweed TD15 2PJ Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about bus services - accessibility, frequency, distance of

More information

Campbell 508 OPTIONAL BASEMENT DEVELOPMENT SQ.FT. 3 BED 2.5 BATH 2012 FINISHED SQ.FT. FRONT GARAGE HOME TWO STOREY FOR 34 LOTS. MAIN FLOOR 789 sq. ft.

Campbell 508 OPTIONAL BASEMENT DEVELOPMENT SQ.FT. 3 BED 2.5 BATH 2012 FINISHED SQ.FT. FRONT GARAGE HOME TWO STOREY FOR 34 LOTS. MAIN FLOOR 789 sq. ft. FRONT GARAGE HOME TWO STOREY FOR 34 LOTS FLOOR PLAN 2.5 BATH 3 BED 2012 FINISHED SQ.FT. 508 OPTIONAL BASEMENT DEVELOPMENT SQ.FT. Nook 12'6" x 8'0" Great 12'0" x 13'0" Bonus 12'6" x 19'6" Master Bedroom

More information

Parking. Access Statement Summerhouse Cottage Beadnell. Pre Arrival. Chathill-3.5 miles/ Alnmouth-15 miles/ Berwick upon Tweed-25 miles

Parking. Access Statement Summerhouse Cottage Beadnell. Pre Arrival. Chathill-3.5 miles/ Alnmouth-15 miles/ Berwick upon Tweed-25 miles Pre Arrival Give the name and distance of the nearest railway station State whether an accessible taxi service is available. Give information about bus services- accessibility, frequency, distance of bus

More information

SKYLINE HOMES OF ARKANSAS CIT Y, KANSAS 24' 28' 32' SERIES

SKYLINE HOMES OF ARKANSAS CIT Y, KANSAS 24' 28' 32' SERIES SKYLINE HOMES OF ARKANSAS CIT Y, KANSAS 24' 28' 32' SERIES East Side Homes 12061 SW US Hwy 54 Augusta, KS 57010 316-688-5101 eastsidehomeswichita.net 24' SERIES Living is easy in the generously spacious

More information

Affordable Rental Housing Design Guidelines

Affordable Rental Housing Design Guidelines Affordable Rental Housing Design Guidelines City of Toronto Affordable Housing Office City of Toronto Affordable Housing Office January 2015 Purpose T he Affordable Housing Design Guidelines have been

More information

Housing Accessibility under the Americans with Disabilities Act and the Fair Housing Act. Building Code manual covers.

Housing Accessibility under the Americans with Disabilities Act and the Fair Housing Act. Building Code manual covers. Housing Accessibility under the Americans with Disabilities Act and the Fair Housing Act Will begin at 2PM ET Building Code manual covers 1 About Your Hosts TransCen, Inc. Improving lives of people with

More information

MANDATORY BUILDING STANDARDS FOR ADAPTABLE HOUSING

MANDATORY BUILDING STANDARDS FOR ADAPTABLE HOUSING MANDATORY BUILDING STANDARDS FOR ADAPTABLE HOUSING Effective June 1, 2004 Planning Department BASIC ADAPTABLE HOUSING SCHEDULE "F" TO ZONING BYLAW 8200 BASIC ADAPTABLE HOUSING The following Basic Adaptable

More information

WORKSHEET FOR ACCESSIBILITY UPGRADE REQUIREMENTS FOR EXISTING NON-RESIDENTIAL BUILDINGS

WORKSHEET FOR ACCESSIBILITY UPGRADE REQUIREMENTS FOR EXISTING NON-RESIDENTIAL BUILDINGS Community Development and Sustainability Department 23 Russell Boulevard, Suite 2 Davis, California 95616 Phone: (530)757-5610 Fax: (530)757-5660 TDD: (530)757-5666 Website: http://community-development.cityofdavis.org/

More information

ADAPTATIONS POLICY 2012

ADAPTATIONS POLICY 2012 ADAPTATIONS POLICY 2012 1.0 INTRODUCTION Adaptations make properties more accessible and useable for people with a medical condition or disability and thereby enable them to maximise their independence

More information

La Petit Jardin 118 Ruette Irwin, Fort George, St Peter Port

La Petit Jardin 118 Ruette Irwin, Fort George, St Peter Port 118 Ruette Irwin, Fort George, St Peter Port Sitting room, kitchen/dining room, study, utility, 3 bedroom suites, 2 separate wc. Double garage, parking and gardens. La Petit Jardin is an immaculate detached

More information

CONSTRUCTION COST ESTIMATE AND ANALYSIS

CONSTRUCTION COST ESTIMATE AND ANALYSIS CONSTRUCTION COST ESTIMATE AND ANALYSIS As can be seen in the exhibits to this analysis, the total construction cost for the Alteration project is $790,324.11. However, under the state statute, section

More information

521 CMR: ARCHITECTURAL ACCESS BOARD MULTIPLE DWELLINGS

521 CMR: ARCHITECTURAL ACCESS BOARD MULTIPLE DWELLINGS 9.1 GENERAL A multiple dwelling is considered to be either a lodging facility or a residential facility for hire, rent, lease, or sale containing three or more dwelling units in a building. Facilities

More information

Renovation Progress. June 2-15, Weeks 35 & 36

Renovation Progress. June 2-15, Weeks 35 & 36 Renovation Progress June 2-15, 2012 Weeks 35 & 36 Jun 2 Sisters investigate the progress and ponder the finished arrangement of the reception area (right) and the residence area on 2 nd Ottilia (below)

More information

Ithaca College Accessibility Guide

Ithaca College Accessibility Guide Ithaca College Accessibility Guide This guide was created to offer information about the accessibility features of the Ithaca College campus for individuals with mobility and hearing impairments. While

More information

Access Statement The Hollies Ingram Road Bamburgh NE69 7BT

Access Statement The Hollies Ingram Road Bamburgh NE69 7BT Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about bus services - accessibility, frequency, distance of

More information

Access Statement for COASTGUARD COTTAGE, BAMBURGH

Access Statement for COASTGUARD COTTAGE, BAMBURGH Access Statement for COASTGUARD COTTAGE, BAMBURGH Introduction Coastguards is a stone built single storey semi-detached cottage on a private lane, backing onto the dunes in the village of Bamburh. Pre-Arrival

More information

FOR SALE OR LEASE. Manufacturing / Distribution Facility 43,200± SF ± Acres. 302 Veterans Parkway Barnesville, Lamar County, Georgia 30204

FOR SALE OR LEASE. Manufacturing / Distribution Facility 43,200± SF ± Acres. 302 Veterans Parkway Barnesville, Lamar County, Georgia 30204 FOR SALE OR LEASE PROPERTY VIDEO: https://vimeo.com/253834894/211c8ed6cd Manufacturing / Distribution Facility 43,200± SF - 6.26± Acres 302 Veterans Parkway Barnesville, Lamar County, Georgia 30204 SALES

More information

NEW ACCESSIBILITY CHANGES

NEW ACCESSIBILITY CHANGES NEW ACCESSIBILITY CHANGES TO THE ONTARIO BUILDING CODE An outline of the accessibility changes made to the Ontario Building Code by Ontario Regulation 368/13. May 9, 2014 OAA CONFERENCE Continuing Education

More information

Kieran Boughan. San Francisco Architect RESIDENTIAL

Kieran Boughan. San Francisco Architect RESIDENTIAL LOEVEN/BURRBIDGE RESIDENCE 159 DAY STREET San Francisco, CA Right: Front Sketch Elevation Renovation and 2-story additions to a cottage-style house in Noe Valley. The existing house had living space above

More information

Damascus

Damascus Damascus Flag Locations 1. Sitting on the roof of a building on the north side of the canal. 2. On the second floor of a building in the north east corner of the district. 3. Sitting in a boat on the west

More information

Accessible Housing by Design. CMHC Research & Information Transfer. Jamie Shipley C.E.T. Canada Mortgage and Housing Corporation

Accessible Housing by Design. CMHC Research & Information Transfer. Jamie Shipley C.E.T. Canada Mortgage and Housing Corporation Accessible Housing by Design CMHC Research & Information Transfer Jamie Shipley C.E.T. Canada Mortgage and Housing Corporation CANADA MORTGAGE AND HOUSING CORPORATION 2 CANADA MORTGAGE AND HOUSING CORPORATION

More information

2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS

2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS 2014 OSSC CHAPTER 10 - MEANS OF EGRESS TABLE OF CONTENTS Section 1001 ADMINISTRATIVE 1001.1 General 1001.2 Alterations to existing means of egress 1001.3 Maintenance 1001.4 Fire safety and evacuation plans

More information

Clouds Hill Access Statement

Clouds Hill Access Statement Clouds Hill Access Statement King George V Road, Bovington, Dorset, BH20 7NQ T: 01929 405616 E: cloudshill@nationaltrust.org.uk Introduction 1. Situated off a main road near Bovington, Clouds Hill is a

More information

ARTICLE 3: RESIDENTIAL DISTRICTS

ARTICLE 3: RESIDENTIAL DISTRICTS ARTICLE 3: RESIDENTIAL DISTRICTS SECTION 2.3.010 DISTRICTS 1) Purpose Roseburg s residential Zoning Districts are primarily intended to create, maintain and promote a variety of housing opportunities for

More information

VERANDA ROAD HOUSING PROJECT ADA / UFAS SITE COMPLIANCE STUDY

VERANDA ROAD HOUSING PROJECT ADA / UFAS SITE COMPLIANCE STUDY (AHA) ADA / UFAS SITE COMPLIANCE STUDY VERANDA ROAD NE 87111 PROJECT LOCATION ZONE LOCATION MAP G-20-Z O W N E R 1840 UNIVERSITY BLVD. SE ALBUQUERQUE, NM 87106 TEL: 505.764.3925 E N G I N E E R PROJECT

More information

Give the name and distance of the nearest railway station. Describe the floor surface e.g. tile/wood/rugs/carpet (thick/short pile).

Give the name and distance of the nearest railway station. Describe the floor surface e.g. tile/wood/rugs/carpet (thick/short pile). Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about bus services - accessibility, frequency, distance of

More information

Lodge Park Access Statement

Lodge Park Access Statement Lodge Park Access Statement Lodge Park, Aldsworth, nr Cheltenham, Gloucestershire, GL54 3PP T: 01451 844130 E: lodgepark@nationaltrust.org.uk Introduction 1. Lodge Park is a 17 th century grandstand, surrounded

More information

ADAAG specifically defines requirements for shopping center handicapped parking and signage, sidewalk size, building access and interior layout.

ADAAG specifically defines requirements for shopping center handicapped parking and signage, sidewalk size, building access and interior layout. Avoiding ADA Compliance Drive-By Lawsuits Shopping center landlords are continually barraged with new and unexpected operating expenses. At every turn, another unforeseen cost emerges, further chipping

More information

National Trust Cottages Access Statement

National Trust Cottages Access Statement National Trust Cottages Access Statement Bureside 92, Itteringham Common Norfolk NR11 7AP Ref: 010006 Introduction Bureside is a characterful semi-detached cottage situated in a riverside setting in the

More information

2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC.

2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC. 2018 CSBC / 2018 CSFSC Part III. Chapter #10. Means of Egress. Table of Contents. Based on the 2015 IBC and the 2015 IFC. October 23, 2018 Section 1001. Administration. See Section 107.2.3 for Egress Drawing

More information

The Benezet House. 13 Penn Center Circle E Director-Walter Mack Emergency contact Robert Lee Johnson

The Benezet House. 13 Penn Center Circle E Director-Walter Mack Emergency contact Robert Lee Johnson The Benezet House 13 Penn Center Circle E Director-Walter Mack 838-2432 Emergency contact Robert Lee Johnson 476-6591 The Benezet house The Benezet house is a 50x84 2 story dormitory/conference center

More information

FOR SALE OR LEASE. Manufacturing / Distribution Facility 85,262± Square Feet (Divisible) Acres

FOR SALE OR LEASE. Manufacturing / Distribution Facility 85,262± Square Feet (Divisible) Acres FOR SALE OR LEASE Manufacturing / Distribution Facility 85,262± Square Feet (Divisible) 15.65 Acres 330 Southwell Boulevard Tifton, Tift County, Georgia 31794 SALES PRICE: $4,000,000 LEASE RATE: $2.00/PSF,

More information

Hotel Accessibility Pack

Hotel Accessibility Pack Hotel Accessibility Pack Thank you for considering the Hilton Aberdeen Treetops Hotel. We are pleased to provide you with information about our hotel and our accessible facilities and services that you

More information

714 BRADDOCK VIEW DRIVE LEMONT FURNACE, PA FOR LEASE INDUSTRIAL MARKETING FLYER

714 BRADDOCK VIEW DRIVE LEMONT FURNACE, PA FOR LEASE INDUSTRIAL MARKETING FLYER 714 BRADDOCK VIEW DRIVE LEMONT FURNACE, PA 15456 FOR LEASE INDUSTRIAL MARKETING FLYER PENN STATE FAYETTE THE EBERLY CAMPUS 714 BRADDOCK VIEW DRIVE YOUR NEW LOCATION GREATER UNIONTOWN BUSINESS PARK PARK

More information

Access Statement Cinnamere Cottage, Eastgate, Pickering

Access Statement Cinnamere Cottage, Eastgate, Pickering Access Statement Cinnamere Cottage, Eastgate, Pickering Introduction Cinnamere Cottage is a stone built terraced two storey cottage. It is located off Eastgate a main road into Pickering town centre. The

More information

National Trust Cottages Access Statement Template

National Trust Cottages Access Statement Template National Trust Cottages Access Statement Template Hemmick Cottage Gorran Haven St Austell PL26 6NY Ref:011105 Introduction Hemmick is a two storey cottage located next to Hemmick beach. The sitting room,

More information

Access Statement Henderson House 19 Henderson Street Amble NE65 0AE

Access Statement Henderson House 19 Henderson Street Amble NE65 0AE Pre-Arrival Give the name and distance of the nearest railway station. State whether an accessible taxi service is available. Give information about bus services - accessibility, frequency, distance of

More information

Facilities providing accommodation for the public (e.g. Hotels, hostels, guesthouses, self catering apartments).

Facilities providing accommodation for the public (e.g. Hotels, hostels, guesthouses, self catering apartments). Facilities providing accommodation for the public (e.g. Hotels, hostels, guesthouses, self catering apartments). These buildings shall comply with the Access for All Design Guidelines as well as indicated

More information

SMART Access Assessment

SMART Access Assessment SMART Access Assessment Company Name Premises Date Of Audit Auditor Trinity College Dublin Accomodation 47, 48, 49, 50, 51 and 52 - Zone 8 29 September 2008 Sakinah Abdul-Ibiyeye Priority 1 Priority 2

More information

Renovation Progress. July 21 Aug 3, Week 42 & 43

Renovation Progress. July 21 Aug 3, Week 42 & 43 Renovation Progress July 21 Aug 3, 2012 Week 42 & 43 Jul 21 Saturday work: hardwood sanding on 2nd Ottilia and masonry outside BSRC dining room Jul 23 Carpet removal outside of chapel Jul 23 2 nd Ottilia

More information